5.3. FV-200RF-AS Microphone Receiver Panel
The FV-200RF-AS is used to connect the RM-200M to FV-200 Series Emergency Public Address System.
Up to 4 RM-200M units can be connected using the FV-200RF-AS. It is possible to control 50 speaker lines
as well as all-zone calls.
POWER
MICROPHONE RECIEVER PANEL FV-200RF-AS
24V, 230mA
ERROR
MICROPHONE RECEIVER PANEL
FV-200RF-AS
ALL 9 7 5 3 1
GND 10 8 6 4 2
ALL 9 7 5 3 1
GND 10 8 6 4 2
ALL 9 7 5 3 1
GND 10 8 6 4 2
ALL 9 7 5 3 1
GND 10 8 6 4 2
ALL 9 7 5 3 1
GND 10 8 6 4 2
ON
1 2 3 4
2. DC Power Input Terminal
Connect this terminal
to 24 V DC power supply.
Power is
supplied from the
FV-200PS-AS
.
(M3 screw terminal; barrier distance: 6.4 mm)
3. Chime Volume
Adjust the volume of the built-in 4-tone chime.
4. ALL CALL Terminal
Connect this terminal to the FV-200PP.
5.RF-PP LINK Terminal
Connect this terminal to the FV-200PP. Audio and
control signals from the RM-200M are output.
6. RM-200M Link Terminals
The following terminals are available for
connection of the RM-200M.
7. Error Indicator
Lights if any failure is detected in communications
with the RM-200M.
8. SS Zone Control Terminals
Connect these terminals to the Speaker Selector
(SS-2010, SS-1010, SS-1010R ), Data of zones
selected via the RM-200M is output from these
terminals.
9. Function Setting Switch
This switch performs the following settings:
the number of RM-200M units to 1 through 4.
Sets priorities among the RM-200M units to
"Last-In-First-Out," "First-In-First-Out," or
Individual. (Default: "Last-In-First-Out", "1 unit")
10. Functional Earth Terminal
Connect this terminal to the functional earth
terminal of external equipment if excessive noise is
generated when the external equipment is
connected to the FV-200RF-AS. This could reduce
noise. Note: This terminal is not for protective earth.
1
2
4
8
10
9
7
6
5
3
-AS