Toa FV-200 Series Instruction Manual Download Page 40

40

7.10. Connecting the Speaker and Attenuator  

   

 

When an  emergency broadcast is made,   then   24 V DC power    will be supplied to the    attenuators   from 
FV-200EV-AS to allow these broadcasts to be made at maximum volume by overriding the attenuators.    

 

 

 

 

 

FV-224PA-AS

(100V)
(COM)

DC24V

DC Power
Unit

Relay Circuit

In 4-wire system attenuator the volume
automatically  set  to   maximum  when 
24 V DC power is supplied. 

24V, 250mA

FA INPUT

CONTROL OUTPUT

USB

EV OUTPUT

MICROPHONE

GROUND

VOL

DC IN

FV-200EV-AS

EMERGENCY MESSAGE PANEL

TOA Corporation , 

JAPAN

MADE IN INDONESIA

FV-224PA-AS

(70V)
(COM)

FV-200EV-AS

If use 70V line, the connection is follow.   Do not use 70V and 100V line at the same time.  

-

+ -

Hot In

COM

SP

NC NC

N

R

2,4 wire
3 wire

SP

Summary of Contents for FV-200 Series

Page 1: ...ns in this manual to ensure long trouble free use of your equipment FV 200 SERIES DC DC POWER SUPPLY PANEL FV 200PS AS AMPLIFIER CHANGEOVER PANEL FV 200CA AS AC MONITOR PANEL MP 210 AS MIN MAX OFF 10 MONITOR VOLUME MONITOR VOLUME 1 2 3 4 5 6 7 8 9 0dB 3dB 6dB 12dB 18dB 24dB BUZZER CTRL ON OFF FAULT CHANGEOVER AMP1 AMP2 AMP3 AMP4 AMP5 AMP6 STANDBY POWER ...

Page 2: ...nterruptible Power Supply UPS System 7 17 2 Power Backup Using the VX 2000DS Emergency Power Supply Panel TABLE OF CONTENTS 4 6 7 7 8 8 10 13 28 29 30 31 31 32 33 34 35 36 36 37 37 37 38 39 39 40 43 43 43 44 44 45 45 45 45 5 4 FV 200CA AS Amplifier Changeover Panel 14 5 5 FV 224PA AS 240W Power Amplifier Panel 5 6 FV 248PA AS FV 248PA AS 4 F00 480W Power Amplifier Panel 5 7 RM 200M Remote Micropho...

Page 3: ...cy operating procedures 9 4 Broadcasting from the RM 200M 10 FAILURE INDICATION 11 SPECIFICATION 11 1 FV 200EV AS Emergency Message Panel 11 2 FV 200PP AS Pre Amplifier Mixer Panel 11 3 FV 200RF AS Microphone Receiver Panel 11 5 FV 224PA AS 240W Power Amplifier Panel 11 6 FV 248PA AS FV 248PA AS 4 F00 480W Power Amplifier Panel 11 7 VP 200VX Power Amplifier Input Module 11 8 RM 200M Remote Microph...

Page 4: ...y Symbol and Message Conventions Safety symbols and messages described below are used in this manual to prevent bodily injury and property damage which could result from mishandling Before operating your product read this manual first and understand the safety symbols and messages so you are thoroughly aware of the potential safety hazards When installing the unit All units When the unit is in use...

Page 5: ... 248PA AS FV 224PA AS FV 248PA AS FV 248PA AS 4 F00 Only FV 200PS AS FV 224PA AS FV 248PA AS FV 200PS AS FV 224PA AS FV 248PA AS FV 248PA AS 4 F00 Only FV 248PA AS 4 F00 FV 248PA AS 4 F00 Only The power plug is used as disconnection device and must be easily accessible Make sure that power cord is not stepped on or compressed particularly near the power plug power socket and at the point where it ...

Page 6: ...6X J DSPQIPOF MIC LINE 1 4 J OQVU 11 3 LI K VEJ P 11 3 LI K VEJ P 11 3 LI K POUSPM 11 3 LI K POUSPM LL B M M LL B M M SPVQ 41 LJ OF 41 PVUQVU SPVQ 3 SPVQ SPVQ SPVQ _ 7 7 D T VQQM J FE UP SB DL J OUFSOB M DPNQPOFOUT LFHFOE VEJ P LJ OF POUSPM LJ OF 1PXFS LJ OF Speaker Selector SS 2010 FV 200PS AS FV 200EV AS FV 200RF AS Max 50 zones FV 200PP AS FV 224AS AS OR FV 248PA AS FV 200CA AS 1 JOQVU FV 224AS...

Page 7: ...of all equipment in the system to ensure sufficient power capacity Note that the system may not work properly due to breaker cutoff or power voltage drops when the total supply voltage is insufficient FV 248PA AS 4 F00 When mounting the FV 200PS AS and FV 224PA AS or FV 248PA AS or FV 248PA AS 4 F00 in an equipment rack mount a Perforated Panel larger than 1U size just above and below each compone...

Page 8: ... EMERGENCY MESSAGE PANEL FV 200EV AS 9 Alert Announcement Button Press this button to play back alert annonucements 10 Evacuation Announcement Button Press this button to play back evacuation announcements 11 False Announcement Button Press this button to play back false announcements 12 Clear Announcement Button Press this button to play back clear announcements 13 Stop Announcement Button When i...

Page 9: ... 17 18 19 20 21 22 20 EV Output Terminal Connect the FV 200PP AS to this terminal 22 Functional Earth Terminal Connect this terminal to the functional earth terminal of external equipment if excessive noise is generated when the external equipment is connected to the FV 200EV AS This could reduce noise Note This terminal is not for protective earth E H FV 200PS AS ...

Page 10: ...djust high and low frequencies of the output Frequencies are accentuated when the control is rotated clockwise and attenuated when rotated counter clockwise Controls are arranged from left to right as follows the rear panel the rear panel 3 Power Indicator Lights when power is supplied and the FV 200PP AS is ready for operation 1 2 3 The FV 200PP AS is a standard operation panel for the FV 200 Ser...

Page 11: ...nals are closed Audio 20 dB 600 unbalanced Control Open voltage 24 V DC short circuit current under 2 mA 2P terminal block for audio and 2P terminal block for control 12 Timer Input Volume Adjust the input volume of Timer Input 11 Turning the control clockwise increases the volume while turning it counterclockwise decreases the volume 13 EV Input Terminal 14 EV Input Volume control clockwise incre...

Page 12: ...12 AS Default 0 dB Note If using unbalanced connection in BGM output terminal and Priority output terminal connect H and E only and remain C left open ...

Page 13: ... 5 RF PP LINK Terminal Connect this terminal to the FV 200PP Audio and control signals from the RM 200M are output 6 RM 200M Link Terminals The following terminals are available for connection of the RM 200M 7 Error Indicator Lights if any failure is detected in communications with the RM 200M 8 SS Zone Control Terminals Connect these terminals to the Speaker Selector SS 2010 SS 1010 SS 1010R Data...

Page 14: ...n with more six duty amplifier with only one standby CHANGEOVER AMPLIFIER PANEL FV 200CA AS POWER Front FAULT IN CA LINK OUTPUTINPUT INPUT STANDBY C H A B A B CT 6 5 4 3 2 1 SB C H C H C H C H C H C H C H C H C H C H C H C H OUT IN OUT IN OUT IN OUT IN OUT IN OUT IN AMP 1 AMP 2 AMP 3 AMP 4 AMP 5 AMP 6 24V 240mA DC IN 6 7 8 9 10 6 DC Power Input Terminal Connect this terminal to 24V DC power supply...

Page 15: ... Earth Terminal Connect this terminal to the functional earth terminal of external equipment if excessive noise is generated when the external equipment is connected to the FV 224PA AS This could reduce noise Note This terminal is not for protective earth 2 1 3 4 5 6 7 8 9 10 11 12 Lights when Power off for a few seconds Overheat Fuse broken Short circuit 15 ...

Page 16: ... terminal of external equipment if excessive noise is generated when the external equipment is connected to the FV 248PA AS FV 248PA AS 4 F00 This could reduce noise Note This terminal is not for protective earth 5 6 FV 248PA AS FV 248PA AS 4 F00 480W Power Amplifier Panel 2 4 1 3 5 6 9 10 11 7 8 12 Lights when Power off for a few seconds Overheat Fuse broken Short circuit 16 ...

Page 17: ...ne sound source to that which is connected to this jack Right Side 17 Extension connector EXTENSION Connects the RM 210 Remote Microphone Extension using the cable supplied to the RM 210 18 Function setting switch Used for setting the Remote Microphone s Unit numbers 1 4 and functions as shown in the 8 2 REMOTE MICROPHONE SETTINGS AS 9 Not use 10 11 12 13 14 15 1 2 3 4 5 6 7 8 9 10 11 12 9 16 13 1...

Page 18: ...l is provided on the other side as well e d i S p o T 1 2 3 4 5 5 9 VP 200VX Power Amplifier Input Module Insert this module into the Power Amplifier s Input module slot when in use 1 Input Connector PA LINK This RJ45 connector connects to the SX 2100AO s PA LINK ZONE 1 8 STANDBY connector or VX 200SP module s or VX 200SZ module s PA LINK connector Output audio signals are transmitted to the power...

Page 19: ... for operation on AC power Connect the supplied power cord to this inlet 5 Battery Power In Terminal Connect this terminal to the 24 V DC input of each system unit Current capacity 5 A total M4 screw terminal barrier distance 12 mm Connect to battery or Emergency Power Supply panel M3 screw terminal barrier distance 6 4 mm DC AC POWER SUPPLY PANEL FV 200PS AS GROUND 220 230V 50 60Hz 160W TOTAL MAX...

Page 20: ... cabinet rack The installation work of each panel to the cabinet rack can work safely and easily if put upward the front of the rack as shown in the figure on the below 6 1 2 Cabinet Rack Installation In order to facilitate maintenance please install as shown below as possible Front Ceiling Wall over 2 0 m front side over 0 5 m over 0 6 m Cabinet Rack over 0 5 m Warning 20 ...

Page 21: ...S 0 Rack CR 273 FV 200EV AS FV 200PP AS CD 2011R AS TT 104B Install power amplifier and others heavy module unit at lower rack Install Speaker selector near the power amplifier to reduce the length of connection cable Install FV 200RF AS near the speaker selector to reduce the length of connection cable Install FV 200EV AS to make Emergency broadcasting 21 FV 200CA AS FV 200PS AS PF or BK FV 248PA...

Page 22: ...nk cable to the RM 200M link connector Positional dimensions of the WB RM200 Install the RM 200M only in a location that can structurally support the weight of the unit and the WB RM200 bracket Doing otherwise may result in the unit falling down and causing personal injury and or property damage Use 2 or more screws to fix the WB RM200 to the wall WARNING 60 8 83 5 220 3 Unit mm RM 200M WB RM200 o...

Page 23: ...supplied with the RM 210 between both extension connectors on the RM 200M s side and the RM 210 s side Step 4 Hook the RM 210 s bottom onto the WB RM200 Positional dimensions of the WB RM200s Extension cable supplied with the RM 210 WB RM200 Wall Mounting Bracket option RM 200M RM 210 4 3 2 1 60 8 83 5 220 3 123 111 30 28 71 5 6 Unit mm WB RM200 when one RM 210 is added as required WB RM200 option...

Page 24: ...JFE XJUI UIF 3 JOLBHF SBDLFU TVQQMJFE XJUI UIF 3 5BQQJOH TDSFX Y TVQQMJFE XJUI UIF 3 YUFOTJPO DBCMF TVQQMJFE XJUI UIF 3 PUF 6TF UIF TBNF TUFQT BCPWF XIFO BOPUIFS 3 JT BEEFE YUFOTJPO DBCMF 3 3 JOLBHF CSBDLFU 3 2 PUUPN TJEF JOLBHF CSBDLFU 3 3 PUUPN TJEF PUFT VTF UIFN UP MJOL CPUI VOJUT JG UIF EFTJHOBUFE TDSFX UISFBEFE IPMFT BSF EBNBHFE CFUXFFO CPUI VOJUT SFNPWF BMM UIF CSBDLFU GJYJOH TDSFXT UP EJTBT...

Page 25: ...nserting the name label Zone 6 Zone 7 Zone 8 Zone 9 Zone 10 Zone 1 Zone 2 Zone 3 Zone 4 Zone 5 Name label A 6 2 5 Dimensional diagram for printing devices 30 13 13 13 13 13 5 13 5 136 13 x 9 117 39 110 0 3 25 ...

Page 26: ...6 2 6 Pattern paper for hand writing B l e b a l e m a N A l e b a l e m a N Shown in actual size Cutting guideline 26 ...

Page 27: ...VX module Attach the VP 200VX s panel to the mounting location and the VP 200VX unit to the back of the mounting location then secure them to the amplifier using the screws removed in Step 3 Notes Step 5 Plug the VP 200VX s connector into the connector on the circuit board inside the amplifier Step 6 After mounting is completed for all required channels replace the top panel Z FV224PA AS Cut off w...

Page 28: ...ess the Ground Lift jumper connector take out the internal VP 200VX from the amplifier Make sure that the system power is switched OFF before starting the work Step 1 Remove the Amplifier s top panel Step 2 Take out the VP 200VX Step 3 Unplug the jumper socket and plug it to the LIFT position on the VP 200VX board as shown below Step 4 Fit the VP 200VX back into place Step 5 Replace the top panel ...

Page 29: ... 4 2 ALL 9 7 5 3 1 GND 10 8 6 4 2 ALL 9 7 5 3 1 GND 10 8 6 4 2 ALL 9 7 5 3 1 GND 10 8 6 4 2 ON 1 2 3 4 FV 200EV AS FV 200PP AS FV 200RF AS SS 2010 RM 200M Speaker Line FAULT IN CA LINK OUTPUTINPUT INPUT STANDBY C H A B A B CT 6 5 4 3 2 1 SB C H C H C H C H C H C H C H C H C H C H C H C H OUT IN OUT IN OUT IN OUT IN OUT IN OUT IN AMP 1 AMP 2 AMP 3 AMP 4 AMP 5 AMP 6 24V 240mA DC IN FV 200CA AS NAME ...

Page 30: ...IER MIXER PANEL TOA Corporation JAPAN MADE IN INDONESIA 24V 110mA 24V 230mA ERROR MICROPHONE RECEIVER PANEL FV 200RF AS ALL 9 7 5 3 1 GND 10 8 6 4 2 ALL 9 7 5 3 1 GND 10 8 6 4 2 ALL 9 7 5 3 1 GND 10 8 6 4 2 ALL 9 7 5 3 1 GND 10 8 6 4 2 ALL 9 7 5 3 1 GND 10 8 6 4 2 ON 1 2 3 4 FV 200EV AS FV 200PP AS FV 200RF AS FAULT IN CA LINK OUTPUTINPUT INPUT STANDBY C H A B A B CT 6 5 4 3 2 1 SB C H C H C H C H...

Page 31: ...PANEL TOA Corporation JAPAN MADE IN INDONESIA GROUND FV 200PP AS PRE AMPLIFIER MIXER PANEL TOA Corporation JAPAN MADE IN INDONESIA 24V 110mA FV 200EV AS FV 200PP AS 7 4 Timer Operated Equipment To make timer operated broadcasts connect the device equipped with the play make output to the FV 200PP AS s Timer Input as follows While the Timer Input s and terminals are closed audio signals entering th...

Page 32: ... FV 200PP AS s Paging Input While the Paging Input s and terminals are closed audio signals entering the Paging Input are output to all speaker lines Connection Diagram GROUND FV 200PP AS PRE AMPLIFIER MIXER PANEL TOA Corporation JAPAN MADE IN INDONESIA 24V 110mA FV 200PP AS Telephone Exchange C E H Play make output Audio output 32 ...

Page 33: ...CetXeeO 7 2 11 4 BOE 7 2 3 4 7 2 11 4 7 2 3 4 7 2 11 4 7 2 3 4 306 7 11 4 13 1 3 9 3 1 50 PSQPSBUJPO 1 0 4 7 N 7 N 3303 301 0 3 7 3 1 7 3 4 1 2 1 2 1 2 1 2 1 2 0N 1 2 3 306 7 11 4 13 1 3 9 3 1 50 PSQPSBUJPO 1 0 4 7 N 7 N 3303 301 0 3 7 3 1 7 3 4 1 2 1 2 1 2 1 2 1 2 0N 1 2 3 ...

Page 34: ...7 7 RM 200M Connection 34 ...

Page 35: ...Notes R M 2 0 0 M I D 1 ID ID3 ID4 tot 4 t 7 7 1 RM 200M Connection without AC adapter 3 6 ø 6 4 9 ø 1 ø 35 ...

Page 36: ...le hook If the DC plug is pulled out the LINK connector takes over the unit s power supply and is connected to the system power line This may cause the voltage drop of power supply and increase the current consumption from the FV 200RF AS resulting in the system malfunction 7 8 BGM Instrument The FV 200PP AS is equipped with 4 MIC LINE Inputs and 2 AUX inputs for broadcasting background sound The ...

Page 37: ...NEL TOA Corporation JAPAN MADE IN INDONESIA 24V 110mA FV 200PP AS CH2 CH1 FV 224PA AS 7 9 2 2 Channel Broadcast GROUND FV 200PP AS PRE AMPLIFIER MIXER PANEL TOA Corporation JAPAN MADE IN INDONESIA 24V 110mA FV 200PP AS CH2 CH1 FV 224PA AS FV 224PA AS 37 Selector switch to CH1 Selector switch to CH2 ...

Page 38: ...38 7 9 3 Power Amplifier Expansion GROUND FV 200PP AS PRE AMPLIFIER MIXER PANEL TOA Corporation JAPAN MADE IN INDONESIA 24V 110mA FV 200PP AS FV 224PA AS FV 224PA AS ...

Page 39: ...r Connection with VX 2000 system FV 200 series Amplifier unit can use with VX 2000 system Please refer to VX 2000 series instruction manual PA LINK VP 200VX DS SF LINK 1 2 IN OUT SLOT No AUDIO LINK DC POWER IN STANDBY PALINK DATA LINK model VX 2000SF SURVEILLANCE FRAME ENGINEEREDINJAPAN ASSEMBLEDINTAIWAN TOA corporation 10 9 8 7 6 5 4 2 1 3 STANDBY PA BUS VX 200SP PA LINK H LINE MONITOR C H SP OUT...

Page 40: ...00V COM DC24V DC Power Unit Relay Circuit In 4 wire system attenuator the volume automatically set to maximum when 24 V DC power is supplied 24V 250mA FA INPUT CONTROL OUTPUT USB EV OUTPUT MICROPHONE GROUND VOL DC IN FV 200EV AS EMERGENCY MESSAGE PANEL TOA Corporation JAPAN MADE IN INDONESIA FV 224PA AS 70V COM FV 200EV AS If use 70V line the connection is follow Do not use 70V and 100V line at th...

Page 41: ... connect standby power amplifier output into FV 200CA AS STANDBY INPUT Connect FV 200CA AS duty amplifier output into speaker selector or directly into speaker FAULT IN CA LINK OUTPUTINPUT INPUT STANDBY C H A B A B CT 6 5 4 3 2 1 SB C H C H C H C H C H C H C H C H C H C H C H C H OUT IN OUT IN OUT IN OUT IN OUT IN OUT IN AMP 1 AMP 2 AMP 3 AMP 4 AMP 5 AMP 6 24V 240mA DC IN DUTY AMPLIFIER NO 2 DUTY ...

Page 42: ...C H C H C H C H C H C H C H C H C H C H C H C H OUT IN OUT IN OUT IN OUT IN OUT IN OUT IN AMP 1 AMP 2 AMP 3 AMP 4 AMP 5 AMP 6 24V 240mA DC IN FAULT IN CA LINK OUTPUTINPUT INPUT STANDBY C H A B A B CT 6 5 4 3 2 1 SB C H C H C H C H C H C H C H C H C H C H C H C H OUT IN OUT IN OUT IN OUT IN OUT IN OUT IN AMP 1 AMP 2 AMP 3 AMP 4 AMP 5 AMP 6 24V 240mA DC IN FAULT IN CA LINK OUTPUTINPUT INPUT STANDBY ...

Page 43: ...T 6 5 4 3 2 1 SB C H C H C H C H C H C H C H C H C H C H C H C H OUT IN OUT IN OUT IN OUT IN OUT IN OUT IN AMP 1 AMP 2 AMP 3 AMP 4 AMP 5 AMP 6 24V 240mA DC IN FAULT IN CA LINK OUTPUTINPUT INPUT STANDBY C H A B A B CT 6 5 4 3 2 1 SB C H C H C H C H C H C H C H C H C H C H C H C H OUT IN OUT IN OUT IN OUT IN OUT IN OUT IN AMP 1 AMP 2 AMP 3 AMP 4 AMP 5 AMP 6 24V 240mA DC IN FAULT IN CA LINK OUTPUTINP...

Page 44: ...SB EV OUTPUT MICROPHONE GROUND VOL DC IN FV 200EV AS EMERGENCY MESSAGE PANEL TOA Corporation JAPAN MADE IN INDONESIA Fire Alarm System 7 14 3 1 Channel Mode using SS 1010R E H 2nd SS 1010R To attenuator 3 wire and Speaker Zone 1 10 Zone 11 20 44 FAULT IN CA LINK OUTPUTINPUT INPUT STANDBY C H A B A B CT 6 5 4 3 2 1 SB C H C H C H C H C H C H C H C H C H C H C H C H OUT IN OUT IN OUT IN OUT IN OUT I...

Page 45: ... it may shorten the amount of time that backup power can operate and or may prevent continued broadcasts Therefore it is important that the UPS selected meets the necessary requirements UPS Requirements time 7 17 2 Power Backup Using the VX 2000DS Emergency Power Supply Panel Using the VX 2000DS as a backup power source permits both emergency and general purpose broadcasts to continue without inte...

Page 46: ...are also included Discharge Capacity Conversion Time minutes Time K hours 10 0 333 20 0 575 30 0 820 40 1 06 50 1 30 60 1 55 70 1 80 80 2 05 90 2 28 100 2 50 When capacity conversion coefficients corresponding to the operation time discharge time of more than 100 minutes is needed approximate values can be obtained from the following expression Capacity conversion time K 0 0217 x Discharge time 0 ...

Page 47: ...S ER Lead acid Battery Lead acid Battery Caution The charging current from VX 2000DS is 5 A maximum QQMJDBCMF BUUFSJFT 1BOBTPOJD 9 1 1 PS FRVJWBMFOU Recomended connection to VX 2000DS Online Connection 24V 230mA ERROR MICROPHONE RECEIVER PANEL FV 200RF AS ALL 9 7 5 3 1 GND 10 8 6 4 2 ALL 9 7 5 3 1 GND 10 8 6 4 2 ALL 9 7 5 3 1 GND 10 8 6 4 2 ALL 9 7 5 3 1 GND 10 8 6 4 2 ALL 9 7 5 3 1 GND 10 8 6 4 2...

Page 48: ...g methods as follows The announcement from the RM 200M last operated takes precedence The announcement from the RM 200M first operated takes precedence Until this announcement is completed other RM 200M microphones cannot make broadcasts The announcement from the RM 200M assigned a smaller address number takes precedence The RM 200M with an address number smaller than that of the RM 200M currently...

Page 49: ...ttings use the DIP switch No 6 for RM 200M Note The DIP switch is located on the side surface for the RM 200M Setting the DIP switch to ON enable announcements to be broadcast without distortion even if excessive input signal is applied to the microphone Default ON 8 2 3 Talk Key Settings Switch 4 operation Set the operating system of the RM 200M s front mounted Talk key Setting the DIP switch 4 l...

Page 50: ... the corresponding volume control so that the red peak indicator lights intermittently Note that the sound quality is downgraded when the peak indicator remains lit GROUND FV 200PP AS PRE AMPLIFIER MIXER PANEL TOA Corporation JAPAN MADE IN INDONESIA 24V 110mA PRE AMPLIFIER MIXER PANEL FV 200PP AS POWER FV 200PP AS 24V 250mA FA INPUT CONTROL OUTPUT USB EV OUTPUT MICROPHONE GROUND VOL DC IN FV 200EV...

Page 51: ...When an emergency broadcast ends The broadcast will resume if the paging operation or timer input activation still continues Refer to Types of General Purpose Broadcasts explained in the following section Pre recorded voice alarm messages set at the factory are as follows Attention please The fire alarm has been activated We are now investigating the cause Please wait for further information There...

Page 52: ...s an audio signal and a control signal from a music play component the broadcast is made to all zones during operation of the music play component Paging When the Paging Input on the rear of the FV 200PP AS receives an audio signal and a control signal from a telephone exchange a paging call from a telephone set is made to all zones Announcements from the RM 200M with the FV 200RF AS and RM 200M i...

Page 53: ...ed and other broadcasts will not be made Order of priority among the RM 200M units When multiple RM 200M units are connected the following modes are available for determining broadcast priority among them Select the desired mode using the Setting Switch on the rear of the FV 200RF AS Last in first out LIFO Priority is given to the RM 200M unit that last selected a broadcast area First in first out...

Page 54: ...cement Indicator 7 False Announcement Indicator Manual activation Operator Press the alert announcement button ALERT Check the site EMERGENCY ALERT EVACUATION FALSE CLEAR STOP POWER EMERGENCY MESSAGE PANEL FV 200EV AS 3 1 2 4 5 6 7 8 10 11 12 13 14 9 8 Clear Announcement Indicator 9 Alert Announcement Button 10 Evacuation Announcement Button 11 False Announcement Button 12 Clear Announcement Butto...

Page 55: ...light Make microphone broadcast Press the fireman s talk switch to broadcast to all zone 8IFO UIF GJre was extinguished Finish emergency broadcast Press the clear announcement button Reset the fire alarm system and press the stop button CLEAR STOP Clear message will be broadcasted to all zones Clear announcement indicator will light Fire indicator will unlit General purpose broadcast will start No...

Page 56: ...ector key Zone indicator RM 200M Step 2 Press the Talk key to make an broadcast The talk indicator lights green while the Talk key is pressed Notes Two modes are available for Talk key operation PTT and Lock modes down Releasing the Talk key terminates the broadcast and extinguishes the indicator the broadcast and extinguishes the indicator Refer to 8 2 3 Talk Key Settings Talk key Talk indicator ...

Page 57: ...adcast zone The In use indicator will flashes green 3 2 After chime play completion make an announcement using the microphone Step 4 End of broadcast Releasing the Talk key The In use indicator goes out Lock operation Step 3 Start of broadcast 3 1 One touch press the TALK key A start chime tone will be sounded over the broadcast zone The In use indicator will light green 3 2 After the chime play i...

Page 58: ...auses may be considered Symptom Possible Cause Check Remedy FV 200RF AS s Confirm that the number that has been Fault indicator lights red set using the setting switch agree with the actual number of the connected RM 200M units Confirm that the RM 200M s address is set correctly Confirm that there is no fault with the wiring leading to the RM 200M RM 200M s Fault Communication with the FV 200RF AS...

Page 59: ...icator automatically goes out within 30 minutes after it has lit FV 248PA AS FV 248PA AS 4 F00 If overheat failure happens Fault indicator lights red If an indicator lights continuously the following possible causes may be considered Check the following points if the indicator automatically goes out within 30 minutes after it has lit Check input and output cables are installed correctly 48 ...

Page 60: ...y amplifier Fault Normal Normal Duty Amp 1 Duty Amp 2 Duty Amp 3 Changeover by standby amplifier Fault Normal Fault Duty Amp 1 Duty Amp 2 Duty Amp 3 Changeover by standby amplifier Fault Fault Normal Duty Amp 1 Fault Duty Amp 3 Fault BUZZER CTRL ON OFF FAULT CHANGEOVER AMP 1 AMP 2 AMP 3 AMP 4 AMP 5 AMP 6 STANDBY CHANGEOVER AMPLIFIER PANEL FV 200CA AS POWER FV 200CA AS have 7 LED fault indicator fo...

Page 61: ...minal block 2 pins Emergency ON output Relay contact output rated voltage 24 V DC at4contacts Removable terminal block 2 pins Operation Alert announcement button Evacuation announcement button False announcement button Clear announcement button Stop announcement button LED Indicator Power Green Fire Red Alert announcement Green Evacuation announcement Green False announcement Green Clear announcem...

Page 62: ...n s microphone EV Timer Paging Remote microphone Mic Line1 Mic Line2 4 AUX1 2 Tone Control Bass 10dB at 100Hz 10dB at 100Hz for INPUT BGM Treble 10dB at 10kHz 10dB at 10kHz for INPUT BGM S N Ratio Over 60 dB Distortion Under 1 1kHz rated output Control Input Timer No voltage make contact input open voltage 24 V DC short circuit current Under 5 mA Removable terminal block 2pins Paging No voltage ma...

Page 63: ... 0 dB unbalanced Removable terminal block 2pins Usable Remote Microphone RM 200M Remote microphone extension unit RM 210 Max 4 unit No of Connectable to Remote Microphone Max 4 RJ 45 Connector Maximum Cable Distance Total 800 m S N Ratio Over 60 dB Distortion Under 1 1kHz rated output Operating Temperature 0 to 40 Operating Humidity Under 90 RH no condensation Finish Panel Aluminium black alumite ...

Page 64: ...re Detection Display Operating Temperature Operating Humidity Finish Dimensions Weight Usable power supply unit FV 200PS AS 24 V DC operating range 21 6 26 4 V M3 screw terminal 240 mA 6 Duty Amplifiers 1 Standby Amplifier 6 Outputs Fault Buzzer with Buzzer CTRL switch Power indicator Green Changeover indicator Orange Fault indicator Red Buzzer CTRL indicator Red 0 C to 40 C Under 90 RH no condens...

Page 65: ...peaker Output M4 screw terminal distance between barriers 12 mm Control Output Fault output Make Normal Break Error or Power Off S N Ratio Over 60 dB Total Harmonic Distortion Under 1 1kHz 1 3 rated output Frequency Response 80Hz 15kHz 3dB 1kHz Ventilation Fan Cooling Panel Indicator Power Green Signal Green Peak Red Fault Red Operating Temperature 0 C to 40 C Operating Humidity Under 90 RH no con...

Page 66: ...Fault Red Operating Temperature Operating Humidity Under 90 RH no condensation Finish Panel Aluminium black alumite Dimensions 482 w x 132 h x 333 2 d mm Weight 18 5 kg Note 0 dB 1V The design and specification are subject to change without notice for improvement Accessory Removable terminal plug 3 pins 3 Option VP 200VX Input Module Power Source Supplied from FV 224PA AS FV 248PA AS FV 248PA AS 4...

Page 67: ... 5 h x 215 d mm Gooseneck microphone excluded 750 g Power Source Current Consumption Audio Output Frequency Response Distortion S N Ratio Microphone Function Key Volume Control Connection and Cable Connector Finish Dimensions Weight Note 1 Use the AC adapter AD 246 or equivalent 2 0 dB 1 V Link cable 3 m 1 Optional Wall Mounting Bracket WB RM200 11 9 RM 210 Remote Microphone Extension 10 ABS resin...

Page 68: ...C to 40 C Under 90 RH no condensation Panel Alumunium Black Alumite 482 w X 44 h X 335 d mm 3 2 kg Output Display AC Operation 24 V DC 0 5 5 A total AC Operation Voltage lowering DC input voltage approx by 2 V M4 screw terminal AC Power Indicator Green DC Power Indicator Orange Note The design and specification are subject to change without notice for improvement Accessory Power Cable YA 301 FV 20...