172-65608MA-03 (RGDS) 5 Oct 2021
13
Maintenance and Inspection
When disassembling or removing the system, wait until the internal
pressure equals atmospheric pressure and the surface of the system has
cooled to room temperature. Disassembling or removing the system
when it is hot or under pressure may lead to discharge of fluids, causing
burns, other injuries or damage.
CAUTION
Be sure to use only the recommended components when repairing the
system, and NEVER attempt to modify the product in any way. Failure to
observe these precautions may result in damage to the system or burns
or other injury due to malfunction or the discharge of fluids.
CAUTION
Make sure the power supply is OFF before carrying out work on the
wiring or inspections involving disassembly. If such work is carried out
with the power on, there is a danger that components may malfunction
or electric shock may occur, leading to injury or other accidents.
CAUTION
Make sure that installation work requiring a special license is carried out
by qualified personnel. Improper work may cause falls, dropped items,
overheating and electrical leaks, leading to injury, burns, fires, damage
and other accidents.
CAUTION
When using this system, NEVER stand close to, or leave tools anywhere
near moving parts, such as the shaft. Contact with moving parts or
objects becoming caught in moving parts could lead to injury, damage
or other accidents.
CAUTION
Periodically inspect and check the following items as preventive maintenance.
For details regarding maintenance considerations, refer to the individual instruction
manual for each component.
Maintenance Checklist
To promote trouble-free operation of the system, inspections and maintenance of the
following items should be carried out periodically.
Injector pump
Daily inspection
Leakage from pump mechanical seal
Abnormal sounds from the pump or motor
Values indicated by the pressure/temp. gauges
Monthly inspection,
maintenance point
Pump suction pressure changes
Cracks in the tank and piping or water leakage
When there is a risk of freezing or the system will not be used for
a long time, water must be blown from the tank and pump interior
Valves
Daily inspection
Leakage from the valve body
Control valve air pressure and valve aperture
Annual inspection
Disassemble and clean the control valves
Other accessories
Daily inspection
Values indicated by the pressure/temp. gauges
Monthly inspection,
maintenance point
Disassemble and clean Y strainers, blow strainers with
condensate blow valves
Steam trap and condensate separator operation
Spray nozzle is not blocked