background image

17

Post-purge:

A post-purge is always necessary on oil installations.  The factory default post-purge time period is 2 minutes.  Just as a chimney contin-

ues to draft after the burner has shut-down, the SS2 will continue to run to clear the vent system of residual gases.  The duration of the post-purge cycle
is adjustable from 0 to 16 minutes.  We recommend a minimum of 2 minutes post-purge on oil.  

Draft Adjustment:

The SS2 Draft Adjustment, located on the rear housing of the SS2 is used for setting up the appliance for proper draft.  See “Draft

Adjustment Procedure” on  pages 15, 16.

Burner Adjustment:

Verify that the over-fire draft matches that recommended by the heating equipment manufacturer.  Adjust the combustion effi-

ciency and smoke characteristics to optimum levels of performance.  See  “Draft Adjustment Procedure” on pages 15, 16.

Combustion Air:

Modern construction methods and materials have reduced natural air infiltration rates to extremely low levels.  Even older homes can

lack adequate air for combustion, when insulation upgrades and other weatherization methods have been installed. It is recommended that fuel burning
appliances have dedicated sources of outside air for combustion.  This may be simply accomplished by running a properly sized duct from outdoors and
terminating it near the burner air intake.  Accessory air intakes are available that connect to the burner motor, using it to pull in the outdoor air.  The
Tjernlund IN-FORCER

TM

Combustion Air Intake tempers the raw outdoor air as it is delivered to the burner.  Without a source of outdoor air for combus-

tion, a tight home's negative pressures will draw odors back through the venting system during the appliance off cycle.

Chronic Oil Odor Conditions:

Certain features of the specific appliance and installation, e.g. high heat-retention combustion chamber; low-mass, dry-

base; piping system design; oil impurities; air in lines, can all contribute to an increased production of oil odor and cannot always be anticipated.  For
extreme cases of oil odor nuisance Tjernlund recommends the practice of post-purging the burner during the vent system post-purge.  A burner post-
purge cycle can eliminate any shortcomings of compatibility between the specific installation and the SS2.  Burner post-purge kits, such as, Tjernlund's
P/N 950-2043, are available from most oil equipment distributors.  Burner post-purge kits should be used on installations where the combustion air is
being adequately supplied, yet oil odors continue.

TROUBLESHOOTING ELECTRICAL PROBLEMS

The following guide is intended to be used if a problem occurs during the use of the SS2 side wall vent system.  It may be necessary to measure volt-
age during troubleshooting. 

Extreme caution must be exercised to prevent injury.

If you are unable to determine the defective part with the use of

this guide, call your Tjernlund distributor or Tjernlund Products direct at 1-800-255-4208 for further assistance.

LED STATUS & FAULT INDICATORS

LED INDICATOR LIGHTS 

LED #1 (Amber) 

Appliance call for heat.

LED #2 (Blue) 

Safety circuit through P1 & P2 (SS2 Limit & Fan Prover). Indicates SS2 Limit & Prover are closed during run cycle. 
Burner circuit is energized with Interlock Relay contact closure from terminal 3 to 4.  

LED #3 (Green) 

Power switched to SS2 motor & Cooling Fan from L to MTR & M.

LED #4 (Red) 

Status / Fault indicator.

LED #5 (Red)

Used as a status indicator.

LED #6 (Red)

115 VAC power supplied to board. 

LED STATUS INDICATORS

LED #4 & #5 (Red) Flashing Alternately = Venter in Pre-purge. (Pre-Purge options 0, 5, 20, 35 seconds)

LED #4 & #5 (Red) Flashing in Unison =  Venter in Post-Purge.  (Post-Purge options 0, 30 seconds or 1, 2, 4, 8, 16 minutes)

LED #4 Flashing Continuously*

=  Fan Prover opened for more than 10 seconds during burner cycle.

(Venter will run for 10 minutes, attempting to make Fan Prover)

LED #5 (Red) Flashing Intermittently

=  With no call for heat, flashes 3 seconds on / 3 seconds off if microcontroller is working properly.

LED FAULT INDICATORS 

Fault conditions are indicated by counting the number of times LED #4 (Red) flashes.
LED #4 Flashes 2 Times

Fan Prover was in electrically closed position prior to venter operation.

LED #4 Flashes 3 Times*

Fan Prover does not close within 60 seconds after call for heat.

LED #4 Flashes 4 Times*

Fan Prover did not re-close after 10 minutes of Venter operation.

LED #4 Flashes 5 Times*

Fan Prover opened for more than 10 seconds during burner cycle but closed within 10 minutes.

* Investigate causes of Fan Prover not making, i.e; Firing burner at capacities or temperatures exceeding Venter limits, excessive vent pipe runs, high 

winds, plugged / kinked Fan Prover sensing tube or a faulty Fan Prover. Reset SS2 High Limit.  If Limit was tripped and SS2 fires, investigate cause 
of high heat.

CHECKING MEMORY FOR LAST FAULT CODE 
IMPORTANT:

Prior to accessing the fault code memory, note the settings of the dip switches so that they can be returned to their original Pre / Post-

Purge positions.  When power is supplied to the UC1 use caution when moving dip switches.

The last fault code can be retrieved at any time by setting all dip switches 1-8 to the up, or “on” position.  The last fault code, or lack there of, will be indi-
cated by counting the number of times LED 4 flashes.  By moving any of the dip switches back to their original position, the fault code will be cleared.

NOTE:

The UC1 board must have its 115 VAC power supply present when any of the (1-8) dip switches are moved back to their original position for  
the fault code to clear.  

IMPORTANT:

Fault codes will automatically be displayed after a fault condition occurs.  If the call for heat interlock signal or 115 VAC power is

removed, the UC1 board will reset and the fault will be stored in memory instead of displayed.  Any new fault will replace any previous fault.

IMPORTANT

Any adjustment to the draft setting must be followed by an over-fire draft measurement and necessary adjustments to the 
primary air intake on the burner and barometric draft control. See “Draft Adjustment Procedure” on pages 15, 16.

Summary of Contents for SIDESHOT SS2

Page 1: ...eries Because of the low set point of the SS1 Fan Prover as low as 03 w c cross winds may cause the Fan Prover to close prior to a call for heat Activating the Prover Status Check on the SS1 may cause...

Page 2: ...es exceeding Venter limits excessive vent pipe runs elbows directly on venter discharge high winds plugged kinked Fan Prover sensing tube or a faulty Fan Prover switch In Forcer model s intake screen...

Page 3: ...G IN FIRE ELECTRICAL SHOCK CARBON MONOXIDE POISONING EXPLOSION PERSONAL INJURY OR PROPERTY DAMAGE NOTE Oil burner capacities exceeding 1 GPH may require the burner to be adjusted to more efficient 12...

Page 4: ...ipment to the outdoors By recirculating indoor air with a cooling fan surrounding com bustible materials remain at safe temperatures After each burner cycle the SS2 will continue to operate in post pu...

Page 5: ...be connected to a natural draft chimney 5 The SS2 shall not be installed where flue gas temperatures exceed 650oF 343oC at its inlet Flue gas temperature verification A On oil fuel verify flue gas te...

Page 6: ...OF A PREVIOUSLY USED APPLIANCE Perform prior to SS2 installation The following procedure is intended as a guide to aid in determining that an appliance is properly installed and is in safe condition...

Page 7: ...LIANCE INTERLOCK RELAY VENTER MOTOR RELAY A B 1 2 3 4 L N J1 J2 XL XN P1 P2 C GND F 1 9 N M MTR 4 C GND F AUXILIARY DEVICE COMMUNICATION TERMINALS 2 mA 5VDC For Tjernlund MAC1E or MAC4E auxiliary devi...

Page 8: ...ilure to do so may result in personal injury and or equipment damage LED 6 RED should not be on if 115 VAC supply power is removed from the control Pre purge Used for longer vent runs to get draft ful...

Page 9: ...code for Oil burning Equipment CSA Std B139 M91 See Diagram A1 A venting system shall not terminate underneath a veranda porch or deck or above a paved sidewalk or a paved driveway that is located bet...

Page 10: ...ng Saw SS2 VENT SYSTEM CLEARANCES FROM COMBUSTIBLES OBSTRUCTIONS With an inlet flue gas temperature of 650oF 343oC or below the SS2 has been Listed for Zero Clearance from combustibles NOTE You must a...

Page 11: ...r easy one person installations remove 3 screws from rear and bottom of vent cabinet Slide venter assembly out of SS2 cabinet and set aside being careful not to dam age housing After SS2 cabinet is se...

Page 12: ...apered reducers and increasers as shown below Determine vent pipe layout which will allow for the least amount of elbows to the appliance Calculate the equivalent vent pipe length from the appli ance...

Page 13: ...e to wire the SS2 as outlined in these instructions call Tjernlund s Customer Service Department toll free at 1 800 255 4208 for assistance IMPORTANT If the call for heat interlock signal or 115 VAC p...

Page 14: ...N 9183046 6 115 VAC LEGEND CALL JUMPER Ignitor CRIMP GROUND WIRE TO GROUNDING SPADE TERMINAL IN SS2 ELECTRICAL BOX IMPORTANT Line Voltage Thermostat or Aquastat Control Low Voltage Jumper 1 Separate t...

Page 15: ...D CALL JUMPER CRIMP GROUND WIRE TO GROUNDING SPADE TERMINAL IN SS2 ELECTRICAL BOX IMPORTANT Limit or Aquastat Control Low Voltage Jumper 1 Disconnect B1 from L1 of oil burner primary control burner re...

Page 16: ...sure RED voltage jumper on UC1 is on 115V SIDESHOT WITH INTEGRAL UC1 UNIVERSAL CONTROL CONNECTED TO AN OIL FIRED FURNACE WITH A HONEYWELL T87 OR EQUIVALENT NON POWERED THERMOSTAT XN R UNIVERSAL CONTR...

Page 17: ...ELECTRICAL BOX CRIMP GROUND WIRE TO GROUNDING SPADE TERMINAL IN IMPORTANT 1 Remove the wire on MV at gas valve and connect it on 1 on UC1 terminal block 2 Connect 2 on UC1 terminal block to MV PV 3 Co...

Page 18: ...resulting in fire carbon monoxide poisoning explosion personal injury or property damage 1 Insert a stack thermometer into the vent pipe as close as possible to the SS2 inlet NOTE plug hole when fini...

Page 19: ...he main burner is burning properly i e no floating lifting or flash back C If the heater has a two stage or modulating gas valve verify that burner operates properly at both low and high fire If the d...

Page 20: ...direct at 1 800 255 4208 for further assistance LED STATUS FAULT INDICATORS LED INDICATOR LIGHTS LED 1 Amber Appliance call for heat LED 2 Blue Safety circuit through P1 P2 SS2 Limit Fan Prover Indica...

Page 21: ...J2 on UC1 circuit board if using typical wiring where supply voltage from ter minal 1 is routed to terminal 3 through call jumper then to 4 when appliance interlock relay makes With call for heat esta...

Page 22: ...roubleshooting guide to determine defective component If unable to determine faulty component contact your Tjernlund distributor or Tjernlund Products Technical Customer Service Department at 1 800 25...

Reviews: