background image

5

Pre-Purge

Post-Purge

Pre-Cycle Fan Prover 
Status Check Activated

DIP SWITCH NUMBERING

1

ON

2

3 4 5 6 7 8

9

LED FAULT INDICATORS 

Fault conditions are indicated by counting the number of times LED #4 (Red) flashes.
LED #4 Flashes 2 Times

Fan Prover was in electrically closed position prior to venter operation.

LED #4 Flashes 3 Times*

Fan Prover does not close within 60 seconds after call for heat.

LED #4 Flashes 4 Times*

Fan Prover did not re-close after 10 minutes of Venter operation.

LED #4 Flashes 5 Times*

Fan Prover opened for more than 10 seconds during burner cycle but closed within 10 minutes.

* Investigate causes of Fan Prover not making, i.e; Firing burner at capacities or temps exceeding Venter limits, excessive vent pipe runs, high winds, 

plugged / kinked Fan Prover sensing tube or faulty Fan Prover. Reset SS2 High Limit.  If Limit was tripped and SS2 fires, investigate cause 
of high heat. 

tripped and SS2 fires, investigate cause of high heat.

CHECKING MEMORY FOR LAST FAULT CODE 

IMPORTANT:

Prior to accessing the fault code memory, note the settings of the dip switches so that they can be returned to their original Pre / Post-

Purge positions.  When power is supplied to the UC1 use caution when moving dip switches.

The last fault code can be retrieved at any time by setting all dip switches 1-8 to the up, or “on” position.  The last fault code, or lack there of, will be indi-
cated by counting the number of times LED #4 flashes.  By moving any of the dip switches back to their original position, the fault code will be cleared.

NOTE:

The UC1 board must have its 115 VAC power supply present when any of the (1-8) dip switches are moved back to their original position for the

fault code to clear.  

PRE / POST PURGE AND PROVER STATUS CHECK DIP SWITCH SETTINGS

Remove power to SS2 and heating equipment when installing, servicing or changing dip switch settings. Failure to do so may result in 
personal injury and/or equipment damage.  LED #6 (RED) should not be on if 115 VAC supply power is removed from the control.

Pre-purge 

Used for longer vent runs to get draft fully established throughout the vent system prior to burner ignition.  Also beneficial for negative pressure prone
environments.

IMPORTANT:

Nuisance equipment lockouts may occur if our pre-purge is running in conjunction with and is longer than any equipment

timing circuit.  Pre-purge settings must be shorter than burner control lockout time unless wired prior to burner control timing circuit (i.e. aquastat / thermostat).

Post-purge

A Venter post-purge has been factory set at 2 minutes.  Confirm that dip switch #5 is in the up or "on" position.  Oil fired equipment requires that the
post-purge be long enough to eliminate post cycle nozzle drip odor. A longer post-purge may be necessary for longer vent runs or high heat retention,
refractory lined combustion chambers. A shorter post-purge may be desired for gas installations. 

IMPORTANT:

Fault codes will automatically be displayed after a fault condition occurs.  If the call for heat interlock signal or 115 VAC power is

removed, the UC1 board will reset and the fault will be stored in memory instead of displayed.  Any new fault will replace any previous fault.

LED 1 AMBER
LED 2 BLUE
LED 3 GREEN
LED 4 RED
LED 5 RED

LED 6 RED
POWER LED

ON

ON

ON

POST-PURGE SETTINGS 

(SEE “POST-PURGE” ABOVE PRIOR TO SETTING)

ON

4

3

4

8

6

5

7

3

5 6 7 8

3 4 5 6 7 8

3

7

5

4

6

8

4

3

4

8

6

5

7

3

5 6 7 8

3 4 5 6 7 8

4 Minutes

8 Minutes

16 Minutes

1 Minute

0 Seconds

30 Seconds

2 Minutes

PRE-PURGE SETTINGS 

(SEE “PRE-PURGE” ABOVE PRIOR TO SETTING)

1 2

1 2

1 2

1 2

0 Seconds

5 Seconds

20 Seconds

35 Seconds

P1 & P2 PRE-CYCLE FAN PROVER STATUS CHECK

The Pre-Cycle Prover Status Check is activated from the factory.  When activated the UC1
Universal Control checks across P1 & P2 safety circuit (SS2 Prover & Limit) to verify that the Fan
Prover switch is “Open” upon a call for heat and not stuck “Closed”.  

Pre-Cycle
Prover Status
Check Activated

9

1        9

Summary of Contents for SIDESHOT SS2

Page 1: ...eries Because of the low set point of the SS1 Fan Prover as low as 03 w c cross winds may cause the Fan Prover to close prior to a call for heat Activating the Prover Status Check on the SS1 may cause...

Page 2: ...es exceeding Venter limits excessive vent pipe runs elbows directly on venter discharge high winds plugged kinked Fan Prover sensing tube or a faulty Fan Prover switch In Forcer model s intake screen...

Page 3: ...G IN FIRE ELECTRICAL SHOCK CARBON MONOXIDE POISONING EXPLOSION PERSONAL INJURY OR PROPERTY DAMAGE NOTE Oil burner capacities exceeding 1 GPH may require the burner to be adjusted to more efficient 12...

Page 4: ...ipment to the outdoors By recirculating indoor air with a cooling fan surrounding com bustible materials remain at safe temperatures After each burner cycle the SS2 will continue to operate in post pu...

Page 5: ...be connected to a natural draft chimney 5 The SS2 shall not be installed where flue gas temperatures exceed 650oF 343oC at its inlet Flue gas temperature verification A On oil fuel verify flue gas te...

Page 6: ...OF A PREVIOUSLY USED APPLIANCE Perform prior to SS2 installation The following procedure is intended as a guide to aid in determining that an appliance is properly installed and is in safe condition...

Page 7: ...LIANCE INTERLOCK RELAY VENTER MOTOR RELAY A B 1 2 3 4 L N J1 J2 XL XN P1 P2 C GND F 1 9 N M MTR 4 C GND F AUXILIARY DEVICE COMMUNICATION TERMINALS 2 mA 5VDC For Tjernlund MAC1E or MAC4E auxiliary devi...

Page 8: ...ilure to do so may result in personal injury and or equipment damage LED 6 RED should not be on if 115 VAC supply power is removed from the control Pre purge Used for longer vent runs to get draft ful...

Page 9: ...code for Oil burning Equipment CSA Std B139 M91 See Diagram A1 A venting system shall not terminate underneath a veranda porch or deck or above a paved sidewalk or a paved driveway that is located bet...

Page 10: ...ng Saw SS2 VENT SYSTEM CLEARANCES FROM COMBUSTIBLES OBSTRUCTIONS With an inlet flue gas temperature of 650oF 343oC or below the SS2 has been Listed for Zero Clearance from combustibles NOTE You must a...

Page 11: ...r easy one person installations remove 3 screws from rear and bottom of vent cabinet Slide venter assembly out of SS2 cabinet and set aside being careful not to dam age housing After SS2 cabinet is se...

Page 12: ...apered reducers and increasers as shown below Determine vent pipe layout which will allow for the least amount of elbows to the appliance Calculate the equivalent vent pipe length from the appli ance...

Page 13: ...e to wire the SS2 as outlined in these instructions call Tjernlund s Customer Service Department toll free at 1 800 255 4208 for assistance IMPORTANT If the call for heat interlock signal or 115 VAC p...

Page 14: ...N 9183046 6 115 VAC LEGEND CALL JUMPER Ignitor CRIMP GROUND WIRE TO GROUNDING SPADE TERMINAL IN SS2 ELECTRICAL BOX IMPORTANT Line Voltage Thermostat or Aquastat Control Low Voltage Jumper 1 Separate t...

Page 15: ...D CALL JUMPER CRIMP GROUND WIRE TO GROUNDING SPADE TERMINAL IN SS2 ELECTRICAL BOX IMPORTANT Limit or Aquastat Control Low Voltage Jumper 1 Disconnect B1 from L1 of oil burner primary control burner re...

Page 16: ...sure RED voltage jumper on UC1 is on 115V SIDESHOT WITH INTEGRAL UC1 UNIVERSAL CONTROL CONNECTED TO AN OIL FIRED FURNACE WITH A HONEYWELL T87 OR EQUIVALENT NON POWERED THERMOSTAT XN R UNIVERSAL CONTR...

Page 17: ...ELECTRICAL BOX CRIMP GROUND WIRE TO GROUNDING SPADE TERMINAL IN IMPORTANT 1 Remove the wire on MV at gas valve and connect it on 1 on UC1 terminal block 2 Connect 2 on UC1 terminal block to MV PV 3 Co...

Page 18: ...resulting in fire carbon monoxide poisoning explosion personal injury or property damage 1 Insert a stack thermometer into the vent pipe as close as possible to the SS2 inlet NOTE plug hole when fini...

Page 19: ...he main burner is burning properly i e no floating lifting or flash back C If the heater has a two stage or modulating gas valve verify that burner operates properly at both low and high fire If the d...

Page 20: ...direct at 1 800 255 4208 for further assistance LED STATUS FAULT INDICATORS LED INDICATOR LIGHTS LED 1 Amber Appliance call for heat LED 2 Blue Safety circuit through P1 P2 SS2 Limit Fan Prover Indica...

Page 21: ...J2 on UC1 circuit board if using typical wiring where supply voltage from ter minal 1 is routed to terminal 3 through call jumper then to 4 when appliance interlock relay makes With call for heat esta...

Page 22: ...roubleshooting guide to determine defective component If unable to determine faulty component contact your Tjernlund distributor or Tjernlund Products Technical Customer Service Department at 1 800 25...

Reviews: