background image

14

SIDESHOT WITH INTEGRAL UC1 UNIVERSAL CONTROL CONNECTED 

WITH A SINGLE ZONE 24 VAC THERMOSTAT

XN

R

U

N

IVER

SAL C

O

N

T

R

O

LLER

THERMOSTAT

G

G

INTERNAL CONTROL

OF FURNACE

W

C
Y

R

R

Y

AS APPLIANCE INTERLOCK VOLTAGE.

RED JUMPER POSITION MUST BE THE SAME

115 VAC
50/60 Hz

SUPPLY

XL

J1

J2

W

DRY

115V

24V

IMPORTANT:

D/N 9183046-5

115 VAC

24 VAC

LEGEND:

CALL
JUMPER

CRIMP GROUND WIRE TO GROUNDING SPADE TERMINAL IN SS2 ELECTRICAL BOX.

IMPORTANT:

SIDESHOT WITH INTEGRAL UC1 CONTROL CONNECTED WITH A 24 VAC ELECTRONIC IGNITION MODULE

XN

R

UN
IV

E

R

S

A

L CO
NT
RO
LLE

R

D/N 9183046-8

115 VAC

24 VAC

LEGEND:

HONEYWELL IGNITION

CONTROL

MV

MV

PV

CALL

AS APPLIANCE INTERLOCK VOLTAGE.

RED JUMPER POSITION MUST BE THE SAME

115 VAC
50/60 Hz

SUPPLY

XL

J1

J2

DRY

115V

24V

IMPORTANT:

PV

MV / PV    (2)

MV    (1)

PV    (3)

BNR GND    (4)

24V GND    (5)

24V    (6)

(7)

(8)

SPARK    (9)

OR

PI

YE

GR

YE

WH

OR

YE

WH

OR

GR

GAS VALVE

JUMPER

SS2 ELECTRICAL BOX.

CRIMP GROUND WIRE TO GROUNDING SPADE TERMINAL IN 

IMPORTANT:

1. Remove the wire on MV at gas valve and connect it on #1 on UC1 terminal block. 
2. Connect #2 on UC1 terminal block to MV/PV. 
3. Connect #4 on UC1 terminal block to MV on gas valve.
4. Connect 115 VAC supply voltage to L & N terminals on UC1.  Installer must supply overload and disconnect protection.
5. Crimp ground wire to grounding spade in SS2 electrical box.
6. Make sure RED voltage jumper on UC1 is on 24V.

1. Connect W from t-stat to #1 on terminal block of UC1. 
2. Connect #2 on UC1 terminal block to C on internal control terminal strip of furnace/boiler. 
3. Connect #4 on UC1 terminal block to W on internal control terminal strip of furnace/boiler. 
4. Connect 115 VAC supply voltage to L & N terminals on UC1.  Installer must supply overload and disconnect protection.
5. Crimp ground wire to grounding spade in SS2 electrical box.
6. Make sure RED voltage jumper on UC1 is on 24V.

NOTE:

If burner safety control goes out on lockout, the SideShot will continue to run as long as a call for heat is present.

Summary of Contents for SIDESHOT SS2

Page 1: ...eries Because of the low set point of the SS1 Fan Prover as low as 03 w c cross winds may cause the Fan Prover to close prior to a call for heat Activating the Prover Status Check on the SS1 may cause...

Page 2: ...es exceeding Venter limits excessive vent pipe runs elbows directly on venter discharge high winds plugged kinked Fan Prover sensing tube or a faulty Fan Prover switch In Forcer model s intake screen...

Page 3: ...G IN FIRE ELECTRICAL SHOCK CARBON MONOXIDE POISONING EXPLOSION PERSONAL INJURY OR PROPERTY DAMAGE NOTE Oil burner capacities exceeding 1 GPH may require the burner to be adjusted to more efficient 12...

Page 4: ...ipment to the outdoors By recirculating indoor air with a cooling fan surrounding com bustible materials remain at safe temperatures After each burner cycle the SS2 will continue to operate in post pu...

Page 5: ...be connected to a natural draft chimney 5 The SS2 shall not be installed where flue gas temperatures exceed 650oF 343oC at its inlet Flue gas temperature verification A On oil fuel verify flue gas te...

Page 6: ...OF A PREVIOUSLY USED APPLIANCE Perform prior to SS2 installation The following procedure is intended as a guide to aid in determining that an appliance is properly installed and is in safe condition...

Page 7: ...LIANCE INTERLOCK RELAY VENTER MOTOR RELAY A B 1 2 3 4 L N J1 J2 XL XN P1 P2 C GND F 1 9 N M MTR 4 C GND F AUXILIARY DEVICE COMMUNICATION TERMINALS 2 mA 5VDC For Tjernlund MAC1E or MAC4E auxiliary devi...

Page 8: ...ilure to do so may result in personal injury and or equipment damage LED 6 RED should not be on if 115 VAC supply power is removed from the control Pre purge Used for longer vent runs to get draft ful...

Page 9: ...code for Oil burning Equipment CSA Std B139 M91 See Diagram A1 A venting system shall not terminate underneath a veranda porch or deck or above a paved sidewalk or a paved driveway that is located bet...

Page 10: ...ng Saw SS2 VENT SYSTEM CLEARANCES FROM COMBUSTIBLES OBSTRUCTIONS With an inlet flue gas temperature of 650oF 343oC or below the SS2 has been Listed for Zero Clearance from combustibles NOTE You must a...

Page 11: ...r easy one person installations remove 3 screws from rear and bottom of vent cabinet Slide venter assembly out of SS2 cabinet and set aside being careful not to dam age housing After SS2 cabinet is se...

Page 12: ...apered reducers and increasers as shown below Determine vent pipe layout which will allow for the least amount of elbows to the appliance Calculate the equivalent vent pipe length from the appli ance...

Page 13: ...e to wire the SS2 as outlined in these instructions call Tjernlund s Customer Service Department toll free at 1 800 255 4208 for assistance IMPORTANT If the call for heat interlock signal or 115 VAC p...

Page 14: ...N 9183046 6 115 VAC LEGEND CALL JUMPER Ignitor CRIMP GROUND WIRE TO GROUNDING SPADE TERMINAL IN SS2 ELECTRICAL BOX IMPORTANT Line Voltage Thermostat or Aquastat Control Low Voltage Jumper 1 Separate t...

Page 15: ...D CALL JUMPER CRIMP GROUND WIRE TO GROUNDING SPADE TERMINAL IN SS2 ELECTRICAL BOX IMPORTANT Limit or Aquastat Control Low Voltage Jumper 1 Disconnect B1 from L1 of oil burner primary control burner re...

Page 16: ...sure RED voltage jumper on UC1 is on 115V SIDESHOT WITH INTEGRAL UC1 UNIVERSAL CONTROL CONNECTED TO AN OIL FIRED FURNACE WITH A HONEYWELL T87 OR EQUIVALENT NON POWERED THERMOSTAT XN R UNIVERSAL CONTR...

Page 17: ...ELECTRICAL BOX CRIMP GROUND WIRE TO GROUNDING SPADE TERMINAL IN IMPORTANT 1 Remove the wire on MV at gas valve and connect it on 1 on UC1 terminal block 2 Connect 2 on UC1 terminal block to MV PV 3 Co...

Page 18: ...resulting in fire carbon monoxide poisoning explosion personal injury or property damage 1 Insert a stack thermometer into the vent pipe as close as possible to the SS2 inlet NOTE plug hole when fini...

Page 19: ...he main burner is burning properly i e no floating lifting or flash back C If the heater has a two stage or modulating gas valve verify that burner operates properly at both low and high fire If the d...

Page 20: ...direct at 1 800 255 4208 for further assistance LED STATUS FAULT INDICATORS LED INDICATOR LIGHTS LED 1 Amber Appliance call for heat LED 2 Blue Safety circuit through P1 P2 SS2 Limit Fan Prover Indica...

Page 21: ...J2 on UC1 circuit board if using typical wiring where supply voltage from ter minal 1 is routed to terminal 3 through call jumper then to 4 when appliance interlock relay makes With call for heat esta...

Page 22: ...roubleshooting guide to determine defective component If unable to determine faulty component contact your Tjernlund distributor or Tjernlund Products Technical Customer Service Department at 1 800 25...

Reviews: