background image

DRAFT AND PSA-1 FAN PROVER ADJUSTMENT PROCEDURES 

DRAFT ADJUSTMENT FOR MECHANICAL DRAFT INSTALLATIONS

IMPORTANT:

If installation includes a CPC-2 Controller, disregard these procedures and refer to the CPC-2 & System instructions for

draft and PSA-1 Fan Prover adjustment procedures.

Close all access doors and openings to the mechanical room that would typically be closed during the heating equipment operation.
Fire all other heating equipment not connected to this vent system and operate exhaust fans or air consuming devices within the facil-
ity that could affect the air pressure of the mechanical room.

1. Follow the heating equipment manufacturer’s instructions for sampling draft. In their absence drill a draft sampling hole in the vent 

riser after each draft diverter or between the flue outlet and the draft hood / barometric draft control of each appliance. 

2. It is important to note that various environmental and temperature conditions will cause draft levels to fluctuate. Set draft in the 

middle of appliance manufacturer’s acceptable range.

3. For installations with a barometric draft control: Adjust weight on draft control to minimum or most responsive “open” position (Less 

Draft). Turn adjustment screw on the PSA-1 counter-clockwise until it stops. Activate the VSUB Blower by installing a jumper be-
tween positions MS3 and MS4 on the VFD terminal strip. Adjust the speed control knob on the face of the VFD until approximately 
-0.10" W.C. is measured at the draft sampling location referenced in step #1. If multiple heaters are being vented by a single VSUB
Blower, adjust balancing baffles so that approximately -0.10" W.C. is measured at each draft sampling location.

4. Remove jumper from MS3 and MS4 positions on VFD terminal strip. Activate burner farthest from the VSUB Blower at full capacity.

Adjust the draft within the manufacturer’s requirements by opening/closing the balancing baffle for that heater. Perform combustion 
test and make any adjustments necessary to the burner so that it operates efficiently. If the desired draft cannot be maintained 
through adjustment of the balancing baffle(s) adjust VSUB Blower speed to achieve desired draft range.

5. Fire each successive heater repeating the same procedure for each heater as outlined within step #3. Keep the previously adjusted

heaters operating as each successive heater’s draft is being adjusted. 

6. After the draft has been adjusted for all heaters, and with all heaters operating, reverify that the draft on all heaters is within the 

manufacturer’s specified range. Make any slight adjustments necessary to the balancing baffle, draft control or VSUB Blower speed
to allow all heaters to operate within the range specified. Record the final Hz _____ (speed) setting as referenced on the VFD 
display. 

SIDEWALL TERMINATIONS:

It is normal for the draft control damper to be nearly wide open.  This will allow the VSUB Blower to

respond to high wind loads.

PSA-1 FAN PROVER SET POINT ADJUSTMENT FOR MECHANICAL DRAFT INSTALLATIONS

1. Activate all heaters at full fire for 5 minutes.

2. Reduce the VSUB Blower speed slowly to the point that a negative draft cannot be maintained or flue gas spillage is detected at 

any of the heaters.

3. Turn PSA-1 adjustment screw clockwise in 1/4 turn steps waiting 30 seconds between each turn until the PSA-1 switch opens, 

causing the heaters to be disrupted. Turn the PSA-1 adjustment screw 1/4 turn counter-clockwise and replace electrical box cover.

4. Increase the VSUB Blower speed back to its original setting that was recorded in step #6 above.   Hz _____ (speed) 

5. Cycle all heaters and verify proper light-off and operation. Return all non-connected heaters, exhaust fans and air consuming 

devices to their previous condition.

PSA-1 FAN PROVER SET POINT ADJUSTMENT FOR COMBUSTION AIR INSTALLATIONS 

IMPORTANT: 

If installation includes a CPC-2 Controller, disregard these procedures and refer to the CPC-2 & System instructions for

draft and PSA-1 Fan Prover adjustment procedures.

Close all access doors and openings to the mechanical room that would typically be closed during the heating equipment operation.
Fire all other heating equipment not connected to this vent system and operate exhaust fans or air consuming devices within the facil-
ity that could affect the air pressure of the mechanical room.

1. Follow the heating equipment manufacturer’s instructions for sampling draft. In their absence drill a draft sampling hole in the vent 

riser after each draft diverter or between the flue outlet and the draft hood / barometric draft control of each appliance. 

2. Turn adjustment screw on the PSA-1 counter-clockwise until it stops. Turn the speed control knob on the face of the VFD complete-

ly clockwise (maximum Hz).

3. Activate all heating equipment within mechanical room at full fire and allow to reach steady state operation. Steady state operation 

is achieved when flue gas temperatures stabilize.

12

Summary of Contents for AUTO-DRAFT VSUB Series

Page 1: ...G EXPLOSION PERSONAL INJURY OR PROPERTY DAMAGE DO NOT DESTROY PLEASE READ CAREFULLY AND KEEP IN A SAFE PLACE ON JOB SITE FOR FUTURE REFERENCE MODELS VSUB8 VSUB12 VSUB16 VSUB20 AUTO DRAFT VSUB SERIES V...

Page 2: ...er All models are supplied with the model PSA 1 Fan Proving Switch which will disable the burner s if an exhaust supply malfunction should occur and a FFP 1 fire freeze limit that will shut the VSUB B...

Page 3: ...add 0 60 W C to vent system resistance to accommodate the effects of wind loading Consideration must be given to the temperature of the gases being handled and the elevation above sea level of the in...

Page 4: ...ves the flow of flue gasses or combustion air and is interlocked with all of the heating appliances If installing a VSUB Blower in conjunction with a CPC 2 controller the CPC 2 provides the safety int...

Page 5: ...discharge Make sure the clear ance to combustible surfaces inside and outside the building are followed as discussed in your state and local codes or in their absence the National fuel gas code NFPA...

Page 6: ...t be less than 7 feet above grade when located adjacent to public walk ways At least 3 feet above any forced air inlet located within 10 feet At least 4 feet below 4 feet horizontally from or 1 foot a...

Page 7: ...hen a source conta minant is located within 10 feet 3048mm of an intake opening such opening shall be located a minimum of 2 feet 610mm below the contami nant source IN ADDITION TO THESE CODES THE MAN...

Page 8: ...s as a mechanical exhauster never orient the discharge vertically without installing a rain cap or a vent pipe that alters the discharge to horizontal Rain caps must be raised a distance equal to the...

Page 9: ...ference Make sure there are no sharp bends or kinks in flexible tubing Do not mount the PSA 1 so that is direct ly in the path of the VSUB Blower discharge unit heater or duct discharges Doing so may...

Page 10: ...e Frequency Drives UC1 Universal Control TD 2 TD 3 Pressure Transducer or MAC1E and MAC4E Multiple Appliance Controls are not covered by this manual Please refer to those accessory installation manual...

Page 11: ...onduit All wiring must be in metal conduit best or shielded cable 230 VAC OR 460 VAC 5 VDC BOARD GENERATED POWER DO NOT SUPPLY POWER 115 VAC NOTES FIGURE 8089002 03 23 04 6 5 3 2 1 LEGEND 24 VDC FOR A...

Page 12: ...UC1 INSTRUCTIONS VFD SPEED ADJUST 1 ORANGE BLUE GREEN BLACK BLACK BLACK M1 M2 M3 MGND L1 L2 F2 F1 L3 MS3 MS4 WEATHERPROOF BOX AND WHIP FIGURE 8089004 03 23 04 will be off if power has been removed fr...

Page 13: ...t is being adjusted 6 After the draft has been adjusted for all heaters and with all heaters operating reverify that the draft on all heaters is within the manufacturer s specified range Make any slig...

Page 14: ...ion air to the equipment room When installing the VSUB Blower as a draft inducer it is not necessary to supply any more combustion air than normally required when con ventional venting MAINTENANCE SER...

Page 15: ...5 4208 When contacting Tjernlund Products Inc please have the following information available 1 Model and Lot of the VSUB Blower 2 Name and address of installer and service agency 3 Date of original i...

Page 16: ...al defects due to faulty material or workman ship for a period of 2 years from the date of original purchase or delivery to the original purchaser whichever is earlier Remedies under this warranty are...

Reviews: