3

INSTALLATION RESTRICTIONS

Failure to install, maintain and/or operate the VSUB Blower in accordance with manufacturer's instructions may result in
conditions which can produce bodily injury and property damage.

The VSUB Blower must be installed by a qualified installer in accordance with these instructions and all local codes or in their
absence in accordance with the latest edition of The National Fuel Gas Code (NFPA 54), NFPA 211 or 31 when applicable, the latest
edition of the National Electrical Code (NFPA 70) and the Occupational Safety and Health Act (OSHA) when applicable.  In the
absence of local codes in Canada, installations must comply with the Canadian Electrical Code (CSA Std 22.1), the latest edition of
the Natural Gas Installation Code (CAN/CGA-B149.1), the Propane Installation Code (CAN/CGA-B149.2) and the Installation Code for
Oil Burning Equipment (CSA Std B139-M91).

Improper installation can create a hazardous condition such as an explosion, fire, electrical shock or carbon monoxide poisoning
resulting in property damage, personal injury or death.

1. The VSUB Blower is intended to be installed on natural gas, LP-gas or oil-fired heating appliance systems. The VSUB Blower is 

not Listed for use on condensing equipment in Canada.

2. The VSUB Blower was tested with exit flue gas temperatures of 575

O

F (300

O

C).

3. The VSUB Blower may not be installed on incinerators, incinerating toilets or solid-fuel burning appliances.

4. The VSUB Blower shall not be installed on an appliance with an automatic valve having a manual opener unless the manual 

opener has been rendered inoperative or the automatic valve has been replaced with a valve not equipped with a manual opener.

5. VSUB Blowers not utilizing the Tjernlund CPC-2 Constant Pressure Control may only be installed on appliances equipped 

with a draft hood, draft diverter or barometric draft control.

6. Tjernlund’s Model FFP-1, Fire and Freeze Protection Limit must be installed when using the VSUB as a combustion air intake to 

protect the boiler room from temperature extremes.  Do not install FFP-1 when VSUB is used as a draft inducer.  It is designed to 
disrupt power to a combustion air supply blower in the event of a boiler room fire or an extended period where frigid outdoor air 
supply could cause pipes to freeze.

D

Never operate a mechanical draft or combustion air system without a proving device that proves the flow of flue gasses or combustion
air and is interlocked with all of the heating appliances. If installing a VSUB Blower in conjunction with a CPC-2 controller, the CPC-2
provides the safety interlock. If installing a VSUB Blower without a CPC-2 controller the PSA-1 fan proving switch must be installed in
conjunction with a UC1 Universal interlock control and any additional MAC-Series multiple appliance controls necessary to interlock
all heaters being vented.

IONS

INSTALLER CAUTIONS

Disconnect the power supply when making wiring connections or when working around the fan impeller and motor.  Failure
to do so can result in electrical shock, personal injury, death or property damage.

1. The VSUB Blower must be interlocked with the heating appliance burner(s).

2. Plan the vent system so that the code required clearances are maintained from plumbing, wiring and combustibles.

3. Make certain the power supply is adequate for VSUB Blower motor and VFD requirements.  Do not add the VSUB Blower to a 

circuit where the total load is unknown.

4. The installer must verify that the appliance on which the VSUB Blower will be installed is in a safe operating condition. 

Consult appliance manufacturer’s Instructions for details.

5. VSUB Blower housing is single wall.  Standard clearances to combustibles must be maintained when venting flue products.  

6. VSUB Blowers must use the appropriate Tjernlund VFD model.

REQUIREMENTS WHEN USING THE VSUB BLOWER FOR COMBUSTION AIR INTAKE

Unless properly screened or guarded to prohibit contact with the blower wheel, a minimum of 3' of pipe must be connected to the
inlet/discharge of the VSUB Blower.

Use the FFP-1, Fire and Freeze Protection Limit that was provided in the VSUB Blower. Place this limit in the physical location as
defined in the limit installation instructions and wire into the control circuit as recommended for your type of installation. This limit is
designed to shut off the combustion air supply if excessive heat or extremely cold air is present in the mechanical room. Do not mount
the limit next to hot or cold surfaces or in the flow of the blower discharge.

1. Make sure the VSUB specified is large enough to supply the combustion air for all heating appliances in the mechanical room. 

Tjernlund Products, Inc. is not responsible for vent layout, appliance type, size or design changes to the air supply system. The 
Mechanical room must be sealed to keep the supplied air from being bypassed to other parts of the building or outdoors. We rec-
ommend that the blower be oversized by 25% to accommodate any unforeseen leakage.

Summary of Contents for AUTO-DRAFT VSUB Series

Page 1: ...G EXPLOSION PERSONAL INJURY OR PROPERTY DAMAGE DO NOT DESTROY PLEASE READ CAREFULLY AND KEEP IN A SAFE PLACE ON JOB SITE FOR FUTURE REFERENCE MODELS VSUB8 VSUB12 VSUB16 VSUB20 AUTO DRAFT VSUB SERIES V...

Page 2: ...er All models are supplied with the model PSA 1 Fan Proving Switch which will disable the burner s if an exhaust supply malfunction should occur and a FFP 1 fire freeze limit that will shut the VSUB B...

Page 3: ...add 0 60 W C to vent system resistance to accommodate the effects of wind loading Consideration must be given to the temperature of the gases being handled and the elevation above sea level of the in...

Page 4: ...ves the flow of flue gasses or combustion air and is interlocked with all of the heating appliances If installing a VSUB Blower in conjunction with a CPC 2 controller the CPC 2 provides the safety int...

Page 5: ...discharge Make sure the clear ance to combustible surfaces inside and outside the building are followed as discussed in your state and local codes or in their absence the National fuel gas code NFPA...

Page 6: ...t be less than 7 feet above grade when located adjacent to public walk ways At least 3 feet above any forced air inlet located within 10 feet At least 4 feet below 4 feet horizontally from or 1 foot a...

Page 7: ...hen a source conta minant is located within 10 feet 3048mm of an intake opening such opening shall be located a minimum of 2 feet 610mm below the contami nant source IN ADDITION TO THESE CODES THE MAN...

Page 8: ...s as a mechanical exhauster never orient the discharge vertically without installing a rain cap or a vent pipe that alters the discharge to horizontal Rain caps must be raised a distance equal to the...

Page 9: ...ference Make sure there are no sharp bends or kinks in flexible tubing Do not mount the PSA 1 so that is direct ly in the path of the VSUB Blower discharge unit heater or duct discharges Doing so may...

Page 10: ...e Frequency Drives UC1 Universal Control TD 2 TD 3 Pressure Transducer or MAC1E and MAC4E Multiple Appliance Controls are not covered by this manual Please refer to those accessory installation manual...

Page 11: ...onduit All wiring must be in metal conduit best or shielded cable 230 VAC OR 460 VAC 5 VDC BOARD GENERATED POWER DO NOT SUPPLY POWER 115 VAC NOTES FIGURE 8089002 03 23 04 6 5 3 2 1 LEGEND 24 VDC FOR A...

Page 12: ...UC1 INSTRUCTIONS VFD SPEED ADJUST 1 ORANGE BLUE GREEN BLACK BLACK BLACK M1 M2 M3 MGND L1 L2 F2 F1 L3 MS3 MS4 WEATHERPROOF BOX AND WHIP FIGURE 8089004 03 23 04 will be off if power has been removed fr...

Page 13: ...t is being adjusted 6 After the draft has been adjusted for all heaters and with all heaters operating reverify that the draft on all heaters is within the manufacturer s specified range Make any slig...

Page 14: ...ion air to the equipment room When installing the VSUB Blower as a draft inducer it is not necessary to supply any more combustion air than normally required when con ventional venting MAINTENANCE SER...

Page 15: ...5 4208 When contacting Tjernlund Products Inc please have the following information available 1 Model and Lot of the VSUB Blower 2 Name and address of installer and service agency 3 Date of original i...

Page 16: ...al defects due to faulty material or workman ship for a period of 2 years from the date of original purchase or delivery to the original purchaser whichever is earlier Remedies under this warranty are...

Reviews: