3. Lock in place with compression nut. With the VSUB Blower on, a positive pressure reading on a draft gauge is an indication that 

the tube has been orientated properly.

4. Fan Proving Switch diaphragm must be mounted in a 

VERTICAL

position within six feet of the sensing location. Firmly insert flexi-

ble tubing on sampling tube and Fan Proving Switch fitting marked (HIGH). Leave the other Fan Proving Switch port open to room 
atmosphere for reference. Make sure there are no sharp bends or kinks in flexible tubing. Do not mount the PSA-1 so that is direct-
ly in the path of the VSUB Blower discharge, unit heater or duct discharges. Doing so may cause a false reference pressure reading.

WIRING

All wiring from the VSUB Blower to the appliance must be in compliance with local codes or in their absence, the National Electric
Code (NFPA 70).

All wiring from the VSUB Blower to the appliance must be appropriate class 1 wiring as follows: Installed in rigid metal conduit, inter-
mediate metal conduit, rigid non-metallic conduit, electrical metallic tubing, Type M1 cable or be otherwise suitably protected from
physical damage.

IMPORTANT:
All wiring from the VFD Variable Frequency Drive or CPC-2 constant Pressure Controller must be in metal conduit or shield-
ed cable where appropriate.  Do not route these wires with any other wires. Improper system operation could result.

This installation manual does not contain any system design documentation. Installation and use of Tjernlund controls like the CPC-2
Constant Pressure controller, EXP-4 Appliance Interlock Expansion Boards, VFD-Series Variable Frequency Drives, UC1 Universal
Control, TD-2/TD-3 Pressure Transducer or MAC1E and MAC4E Multiple Appliance Controls are not covered by this manual. Please
refer to those accessory installation manuals.

WIRING VSUB MOTOR FOR PROPER VOLTAGE

IMPORTANT: CONFIRM PROPER IMPELLER ROTATION

If this VSUB Blower is being installed in conjunction with a CPC-2 Controller, follow impeller rotation check instructions outlined in the
CPC-2 installation instructions. Failure to insure correct rotation will result in higher power usage and poor blower performance.

All VSUB Blowers must use a Variable Frequency Drive (VFD) supplied by Tjernlund which is factory programmed specifically for the
VSUB model being installed.  

VISUAL METHOD TO VERIFY PROPER ROTATION:

VSUB Series impeller must rotate counter-clockwise as viewed from the motor side, (See Diagram I). Verify motor cooling fan at back
of motor rotates counter-clockwise. While the VSUB Blower is running at a slow speed, starting up or coming to a stop, visually deter-
mine if the rotation is correct.  Perform step 4 on page 10 if rotation is in the reverse direction.

MOTOR

WINDINGS

MOTOR

LIMIT

GROUND

P1

P2

BLACK

BLACK

BLACK

BLUE

ORANGE

GREEN

BLACK

BLACK

BLACK

BLUE

ORANGE

GREEN

VSUB MOTOR

4 x 4 WEATHERPROOF BOX

FLEXIBLE CONDUIT

WIRE NUTS BY INSTALLER

FACTORY CONNECTORS

IMPORTANT:

T4

T7

T1

T5

T8

T2

T6

T9

T3

BLACK

BLACK

BLACK

T4

T1

T5

T6

BLACK

BLACK

BLACK

T7

T2

T8

T3

T9

MOTOR WIRING

460 VOLT VFD

MOTOR WIRING

230 VOLT VFD

(FACTORY WIRING)

FIGURE 8055001    4/5/04

RED

RED

RED

RED

H2

H1

ARCTIC-DUTY

230 VAC OR 460 VAC

5 VDC BOARD-GENERATED

DO NOT SUPPLY POWER!

230 VAC

LEGEND:

POWER.

MOTOR HEATER

(15 WATTS FOR VSUB8,12,16

MOTOR HEATER T-STAT

460 VAC

BELOW FREEZING.

& 30 WATTS FOR VSUB20)

VSUB ROTATION    2/27/04

I

M

P

E

L

L

E

R

R

O

T

A

T

I

O

N

DIAGRAM I

Summary of Contents for AUTO-DRAFT VSUB Series

Page 1: ...G EXPLOSION PERSONAL INJURY OR PROPERTY DAMAGE DO NOT DESTROY PLEASE READ CAREFULLY AND KEEP IN A SAFE PLACE ON JOB SITE FOR FUTURE REFERENCE MODELS VSUB8 VSUB12 VSUB16 VSUB20 AUTO DRAFT VSUB SERIES V...

Page 2: ...er All models are supplied with the model PSA 1 Fan Proving Switch which will disable the burner s if an exhaust supply malfunction should occur and a FFP 1 fire freeze limit that will shut the VSUB B...

Page 3: ...add 0 60 W C to vent system resistance to accommodate the effects of wind loading Consideration must be given to the temperature of the gases being handled and the elevation above sea level of the in...

Page 4: ...ves the flow of flue gasses or combustion air and is interlocked with all of the heating appliances If installing a VSUB Blower in conjunction with a CPC 2 controller the CPC 2 provides the safety int...

Page 5: ...discharge Make sure the clear ance to combustible surfaces inside and outside the building are followed as discussed in your state and local codes or in their absence the National fuel gas code NFPA...

Page 6: ...t be less than 7 feet above grade when located adjacent to public walk ways At least 3 feet above any forced air inlet located within 10 feet At least 4 feet below 4 feet horizontally from or 1 foot a...

Page 7: ...hen a source conta minant is located within 10 feet 3048mm of an intake opening such opening shall be located a minimum of 2 feet 610mm below the contami nant source IN ADDITION TO THESE CODES THE MAN...

Page 8: ...s as a mechanical exhauster never orient the discharge vertically without installing a rain cap or a vent pipe that alters the discharge to horizontal Rain caps must be raised a distance equal to the...

Page 9: ...ference Make sure there are no sharp bends or kinks in flexible tubing Do not mount the PSA 1 so that is direct ly in the path of the VSUB Blower discharge unit heater or duct discharges Doing so may...

Page 10: ...e Frequency Drives UC1 Universal Control TD 2 TD 3 Pressure Transducer or MAC1E and MAC4E Multiple Appliance Controls are not covered by this manual Please refer to those accessory installation manual...

Page 11: ...onduit All wiring must be in metal conduit best or shielded cable 230 VAC OR 460 VAC 5 VDC BOARD GENERATED POWER DO NOT SUPPLY POWER 115 VAC NOTES FIGURE 8089002 03 23 04 6 5 3 2 1 LEGEND 24 VDC FOR A...

Page 12: ...UC1 INSTRUCTIONS VFD SPEED ADJUST 1 ORANGE BLUE GREEN BLACK BLACK BLACK M1 M2 M3 MGND L1 L2 F2 F1 L3 MS3 MS4 WEATHERPROOF BOX AND WHIP FIGURE 8089004 03 23 04 will be off if power has been removed fr...

Page 13: ...t is being adjusted 6 After the draft has been adjusted for all heaters and with all heaters operating reverify that the draft on all heaters is within the manufacturer s specified range Make any slig...

Page 14: ...ion air to the equipment room When installing the VSUB Blower as a draft inducer it is not necessary to supply any more combustion air than normally required when con ventional venting MAINTENANCE SER...

Page 15: ...5 4208 When contacting Tjernlund Products Inc please have the following information available 1 Model and Lot of the VSUB Blower 2 Name and address of installer and service agency 3 Date of original i...

Page 16: ...al defects due to faulty material or workman ship for a period of 2 years from the date of original purchase or delivery to the original purchaser whichever is earlier Remedies under this warranty are...

Reviews: