TCSG5270 Sounder Strobe User Manual

Ver 1.0 2022.03

Liaoning

·

Yingkou Tiancheng Fire Protection Equipment Co., Ltd

2

1. General

The TCSG5270 sounder strobe uses two buses to connect to the control panel. It is mainly installed in public
places. When a fire occurs, the sounder strobe generates dazzling strong light and emits an alarm sound, which is
used as a fire alarm. Its built-in microprocessor has independent measurement and processing functions. Fuzzy
logic processing is performed on the collected information, and various measurement data are transmitted to the
control panel, and judged by the control panel so that the alarm information can be issued quickly and accurately.
This sounder strobe has the characteristics of reliable performance, convenient installation, and beautiful
appearance. It is a fire alarm device with high reliability and strong anti-interference ability.

2. Characteristics

2.1 Adopt two-bus system: two-bus without polarity signal.
2.2 Built-in microprocessor, with intelligent judgment ability.
2.3 The address is set through electronic coding, and there is no dial switch, which increases the airtight property
in structure.
2.4 With self-diagnosis function to ensure its reliable operation.
2.5 The status signal value can be provided, which intuitively reflects the current working status of the sounder
strobe.
2.6 Multi-level filtering with software and hardware can effectively suppress interference signals.
2.7 When the sounder strobe is activated, it can emit strong light and produce a harsh alarm sound.
2.8 The appearance design is beautiful, the installation and wiring are convenient and reliable.

3. Specifications

3.1 Working voltage

Signal bus voltage

bus 24V

Allowed range: 17V

28V

3.2 Working current

Bus standby current≤0.2mA

Bus alarm current≤4mA

3.3 Temperature

:-

10

℃~+

50

3.4 Humidity

≤95% (40±2

)

3.5 Main sound frequency

1.67KHZ~5.9KHZ

3.6 Frequency range

1.67KHZ~5.9KHZ

3.7

Sound type: constant

3.8 Sound mode: alarm
3.9 Tone variety:1
3.10 Sound pressure level

db@1m

The test was carried out in accordance with Clause 5.3.1 of EN 54-3:2014 + A1:2019.

Operational performance

Specimen № 1 Maximum Volume

Angle

Sound Pressure level dB(A)

Horizontal Plane

Vertical Plane

Max

26

V

Min

16

V

Difference

Max

26

V

Min

16

V

Difference

15°

90.1

85.0

5.1

86.1

81.5

4.6

45°

85.7

81.5

4.2

81.3

78.9

2.4

75°

89.7

84.8

4.9

87.5

84.5

3.0

105°

87.4

84.2

3.2

88.7

84.5

4.2

135°

87.1

84.1

3.0

88.4

85.6

2.8

165°

86.3

82.9

3.4

85.9

81.8

4.1

3.11 Tone modification cycle

3.5S~4.5S

3.12 Flash frequency

1HZ~2HZ

Summary of Contents for TCSG5270

Page 1: ...Manual Ver 1 0 2022 03 Liaoning Yingkou Tiancheng Fire Protection Equipment Co Ltd 1 Please read this user manual carefully before installation TCSG5270 Sounder Strobe User Manual Liaoning Tiancheng Fire Protection Equipment Co Ltd ...

Page 2: ...With self diagnosis function to ensure its reliable operation 2 5 The status signal value can be provided which intuitively reflects the current working status of the sounder strobe 2 6 Multi level filtering with software and hardware can effectively suppress interference signals 2 7 When the sounder strobe is activated it can emit strong light and produce a harsh alarm sound 2 8 The appearance de...

Page 3: ...rol panel it starts light and sound signals The sound chip is amplified by the transistor and inductor to drive the speaker to make a sound the timing circuit is used to control the ultra high light emitting diode to emit a shining light signal 5 Installation and Wiring 5 1 1 Take the base The TCSG5270 sounder strobe is composed of two parts base and top cover including circuit board Remove the ba...

Page 4: ...se 6 2 Before the sounder strobe is tested the relevant management department should be notified that the system will be maintained and will temporarily stop working due to this At the same time the logic control function of the area or system to be maintained should be cut off to avoid unnecessary alarm linkage 6 3 Test content A start command is issued from the control panel to the sounder strob...

Page 5: ...coding succeeds it displays successful otherwise displays failed 8 Application The signal bus of the sounder strobe is connected to the loop bus of the control panel If it is necessary to start the sounder strobe the fire alarm controller can directly start it or start through a linkage programming 9 Documents and Maintenance Manual 9 1 Packing documents 1 Packing list 1 2 User manual 1 9 2 Warran...

Reviews: