TCSG5270 Sounder Strobe User Manual
Ver 1.0 2022.03
Liaoning
·
Yingkou Tiancheng Fire Protection Equipment Co., Ltd
3
进线管
预埋盒
3.13 Application environment
:
indoor
(
non-residential
)
3.14 Outline
:
140mm×115mm×55mm(l×w×h)
3.15 Standard
:
EN 54-3:2001 + A1:2002 + A2:2006; EN 54-3:2014 + A1:2019
3.16 Indoor type
:
A
3.17 IP level:IP21C
3.18 Weight:200g
4. Structure and Function
4.1 Outline of the sounder strobe is shown as Fig.1.
2831-CPR-F4719
Fig. 1 TCSG5270 Sounder Strobe--Outline Structure and Installation Dimensions
4.2 Working principle
The sounder strobe has a built-in microprocessor, which realizes the communication with the control panel and
the activation of sound and light signals. As the sounder strobe receives the start command of the control panel,
it starts light and sound signals. The sound chip is amplified by the transistor and inductor to drive the speaker to
make a sound; the timing circuit is used to control the ultra-high light-emitting diode to emit a shining light
signal.
5. Installation and Wiring
5.1.1 Take the base. The TCSG5270 sounder strobe is composed of two parts: "base" and "top cover (including
circuit board)". Remove the "base" first after taking it out of the box. (Note: If the two parts have been fastened,
turn counterclockwise to loosen them and store them separately).
5.1.2 Fix the base. Pass the wire through the threading hole from the back of the base, and fix the base according
to the characters on both sides of the threading hole and the arrow direction.
5.1.3 The sounder strobe is installed with pre-embedded pipes, the bottom box is installed on the 86H50
embedded box with a distance of 60mm (see Figure 3). The installation diagram is shown in Figure 2.