background image

TCSG5270 Sounder Strobe User Manual

Ver 1.0 2022.03

Liaoning

·

Yingkou Tiancheng Fire Protection Equipment Co., Ltd

3

进线管

预埋盒

3.13 Application environment

indoor

non-residential

3.14 Outline

140mm×115mm×55mm(l×w×h)

3.15 Standard

EN 54-3:2001 + A1:2002 + A2:2006; EN 54-3:2014 + A1:2019

3.16 Indoor type

A

3.17 IP level:IP21C
3.18 Weight:200g

4. Structure and Function

4.1 Outline of the sounder strobe is shown as Fig.1.

2831-CPR-F4719

Fig. 1 TCSG5270 Sounder Strobe--Outline Structure and Installation Dimensions

4.2 Working principle
The sounder strobe has a built-in microprocessor, which realizes the communication with the control panel and
the activation of sound and light signals. As the sounder strobe receives the start command of the control panel,
it starts light and sound signals. The sound chip is amplified by the transistor and inductor to drive the speaker to
make a sound; the timing circuit is used to control the ultra-high light-emitting diode to emit a shining light
signal.

5. Installation and Wiring

5.1.1 Take the base. The TCSG5270 sounder strobe is composed of two parts: "base" and "top cover (including
circuit board)". Remove the "base" first after taking it out of the box. (Note: If the two parts have been fastened,
turn counterclockwise to loosen them and store them separately).
5.1.2 Fix the base. Pass the wire through the threading hole from the back of the base, and fix the base according
to the characters on both sides of the threading hole and the arrow direction.
5.1.3 The sounder strobe is installed with pre-embedded pipes, the bottom box is installed on the 86H50
embedded box with a distance of 60mm (see Figure 3). The installation diagram is shown in Figure 2.

Summary of Contents for TCSG5270

Page 1: ...Manual Ver 1 0 2022 03 Liaoning Yingkou Tiancheng Fire Protection Equipment Co Ltd 1 Please read this user manual carefully before installation TCSG5270 Sounder Strobe User Manual Liaoning Tiancheng Fire Protection Equipment Co Ltd ...

Page 2: ...With self diagnosis function to ensure its reliable operation 2 5 The status signal value can be provided which intuitively reflects the current working status of the sounder strobe 2 6 Multi level filtering with software and hardware can effectively suppress interference signals 2 7 When the sounder strobe is activated it can emit strong light and produce a harsh alarm sound 2 8 The appearance de...

Page 3: ...rol panel it starts light and sound signals The sound chip is amplified by the transistor and inductor to drive the speaker to make a sound the timing circuit is used to control the ultra high light emitting diode to emit a shining light signal 5 Installation and Wiring 5 1 1 Take the base The TCSG5270 sounder strobe is composed of two parts base and top cover including circuit board Remove the ba...

Page 4: ...se 6 2 Before the sounder strobe is tested the relevant management department should be notified that the system will be maintained and will temporarily stop working due to this At the same time the logic control function of the area or system to be maintained should be cut off to avoid unnecessary alarm linkage 6 3 Test content A start command is issued from the control panel to the sounder strob...

Page 5: ...coding succeeds it displays successful otherwise displays failed 8 Application The signal bus of the sounder strobe is connected to the loop bus of the control panel If it is necessary to start the sounder strobe the fire alarm controller can directly start it or start through a linkage programming 9 Documents and Maintenance Manual 9 1 Packing documents 1 Packing list 1 2 User manual 1 9 2 Warran...

Reviews: