VIII
、
XC-E3AD4PT2DA
1
.
Specifications
Specilities:
3 channels 14 bits current input
、
4
channels PT100 temperature input and 2
channels 12 bits voltage output
3 channels current 0~20mA
、
4~20mA
input (selectable) and 2 channels voltage
0~5V
、
0~10V output (selectable), set via
the software
Pt resistor input (PT100)
3 channels A/D and 4 channels PT input,
with PID adjustment function
ITEMS
Analog Current Input
(AD)
Temperature Input (PT)
Analog Voltage Output
(DA)
Analog Input
DC0~20mA
、
4~20mA
PT100
-
Temperature
Testing Bound
-
-100~350
℃
-
Maximum Output
Bound
DC0~40mA
-
-
Analog Output
Bound
-
-
DC0~5V
、
0~10V
External load resistor
(2KΩ~1MΩ)
Digital
Input
Bound
-
-
12 bits binary (0~4095)
Digital Output
Bound
14 bits binary (0~16383)
-1000~3500
-
Distinguish
1/16383(14Bit);
the
converted data is stored
into PLC(14Bit) in the
form of Hex.
0.1
℃
1/4095(12Bit);
the
converted data is stored
into PLC(12Bit) in the
form of Hex.
PID Output Value 0~K4095
-
General
Precision
0.8%
±0.5
℃
0.8%
Convert Speed
20ms per channel
3ms per channel
Power Supply for
Analog Using
DC24V±10%,100mA
Installation
Fix with M3 screws or install on DIN46277 (Width: 35mm) leader directly
Dimension
63mm×102mm×73.3mm
[Extend Cable]: Via the connection of the extend cable and PLC’s extend port, realize data transfer
[Extend Port]: Connect with other expansions