Analog input/output module XC-E4AD2DA
1.Specification
Characteristic
:
4 channels 14 bits analog input and 2
channels 12 bits analog output
4 channels selectable voltage
0~5V
、
0~10V
,
current
0~20mA
、
4~20mA input and 2
channels selectable voltage
0~5V
、
0~10V
,
current
0~20mA
、
4~20mA output. Set via
host machine.
As special function module of XC, 7
modules could be connected at most
4 channels A/D have PID adjustment
function
Items
Analog input
(
AD
)
Analog output
(
DA
)
Voltage input
Current input
Voltage output
Current output
Analog input bound
DC0~5V
、
0~10V
DC0~20mA
、
4~20m
A
-
Max input bound
DC±18V
DC0~40mA
-
Analog output bound
-
DC0~5V
、
0~10V
(Exterior load
resistance
2KΩ~1MΩ)
DC0~20mA
、
4~20mA
(Exterior
load
resistance is less
than 500Ω)
Digital input bound
-
12 bits binary data
(
0~4095
)
Digital output bound
14 bits binary data
(
0~16383
)
-
Distinguish ratio
1/16383(14Bit); the converted data is
stored into PLC in the format of HEX
format (14Bit)
1/4095(12Bit); the converted data is
stored into PLC with the format of HEX.
(12Bit)
PID control value
0~4095
-
Integrate precision
0.8%
Convert speed
15ms per channel
2ms per channel
Power used by analog
DC24V±10%,100mA
Install format
Fixed with M3 screws or directly installed on orbit of DIN46277 (Width: 35mm)
Exterior size
63mm×102mm×73.3mm
[Extend cable]: Realize data transfer via the connection of extend cable and PLC extend port
[Extend port]
:
Connect with other expansions