channels
temperature
control
bound
Description
:
Start signal
(
Y
):
When Y is 0, close PID control; when being 1, start PID control
Parameter
P:
proportion parameter, mainly reflect system’s difference,
control as soon as difference
occurs to
decrease this difference.
Parameter
I:
Integral parameter, mainly used to remove the whisht and improve the system’s no
difference degree
Parameter
D:
differential parameter, mainly control signal’s changing trend and decrease the system’s
shake.
Temp. control bound
Diff :
in the assigned bound, carry on PID control, beyond that bound, no PID
control
Each parameter’s reference value
:
Kp=20~100
;
Ki=5~20
;
Kd=200~700
;
DIFF=100~200
3.
Setting of input filter
1
)
Every input of expansion has option of filter, set via
special FLASH data register FD in PLC.
Seethe following chart:
Module
channel’s ID
0CH~3CH
4CH~5CH
1#module
FD8250
FD8251low byte
2# module
FD8258
FD8259 low byte
3# module
FD8266
FD8267 low byte
4# module
FD8274
FD8275 low byte
5# module
FD8282
FD8283 low byte
6# module
FD8290
FD8291 low byte
7# module
FD8298
FD8299 low byte
Each channel’s filter mode is assigned via correspond register’s 4 bits! Each bit’s definition is showed in the
following table:
Take module 1 as the example:
Register FD8250
:
Take 1# module as example:
FD8250 H O O O O
0CH
1CH
2CH
3CH
FD8251 H O O O O
4CH
5CH