![Thinget XC-E4AD2DA Operator'S Manual Download Page 31](http://html1.mh-extra.com/html/thinget/xc-e4ad2da/xc-e4ad2da_operators-manual_1106980031.webp)
A0
C0 C1
A1
C2
A2 A3
C3
A4
C4
A5
C5
Y0
COM0
Y2
Y5
COM2
Y1
Y4
Y3
COM1
Y
AI
PWR
54
32
10
Output terminals
Transistor output terminals, please choose DC5V~30V flat power.
Circuit insulation
Between PLC’s interior circuit and output transistor, use optical insulation. Each public module is also
separate.
Response time
The time from PLC drive (or cut) optical coupling device to transistor ON/OFF, no more than 0.2ms.
Output current
Each point has electricity 0.8A, but to avoid temperature rising, please use as every 4 points 1.2A or
every 8 points 2.0A
Open circuit leak current
Below 0.1mA
The output circuit is the following:
Take channel 0 and channel 1 as the example: