4.3.6.3.  AS400 Interface with DB9 output 

(option).

Ŗ

Communication line (COM) is a very low voltage circuit 

of safety. To preserve the quality, it has to be installed 

separate from other lines that have dangerous voltages (energy 
distribution line).

Ŗ

UPS has a dry contact card for the AS400 communication 
protocol, it provides digital signals in a free potential way, with 
a maximum applicable voltage and current of 240 V ac or 
30 V dc and 1A. Pin-out of the DB9 connector are stated in 
figure 10 and detailed in table 5.

Ŗ

The most common use of this type of ports is to provide the 
needed information for the closing file software.

Ŗ

For more information, contact with our S.T.S or our nearest 
distributor.

UPS fault

General alarm

Ground (GND)

Common

Bypass

Low battery

UPS on

AC mains fault

Fig. 10. 

AS400 dry contact pin-out.

Description

Pin-out

Input/output

UPS fault

1

Output

General alarm

2

Output

Ground (GND)

3

Input

Common

5

Input

Bypass

6

Output

Low battery

7

Output

UPS "On"

8

Output

AC mains fault

9

Output

Tabla 5. 

AS400 dry contacts alarms.

Installation.

Ŗ

Remove the screws that fix the protection cover of the slot of 
the equipment and the own cover.

Ŗ

Take the AS400 card and insert it into the smart slot. Make 
sure that it is well connected, so the resistance that the own 
connector inside the slot makes has to be overcome.

Ŗ

Fix the card with the previous removed screws.

Ŗ

Connect the DB9 connector from AS400 with the peripheral 
to be communicated.

4.3.6.4.  Protection against transient voltages for 

modem / ADSL / Fax / ... lines.

Ŗ

 Communication line (COM) is a very low voltage circuit 

of safety. To preserve the quality, it has to be installed 

separate from other lines that have dangerous voltages (energy 
distribution line).

Ŗ

Connect the main line for the modem / ADSL / Fax /... to the 
RJ45 connector of the equipment, labelled as "Input". 

Ŗ

Connect the own modem / ADSL / Fax /... to RJ45 connector 
of the equipment, labelled as "Output". 

4.3.7. Software.

Ŗ

Free software download - WinPower.

WinPower is a UPS monitoring software, which makes a 
user-friendly interface of monitoring and management. This 
software supplies an auto Shutdown for a system based on 
several PCs in case of an electrical blackout. With this soft-
ware, the end-users can monitor and manage any UPS in the 
same IT network, through the RS232 or USB communication 
port, never mind the distance between them.

Fig. 11. 

Main screen of the monitoring software.

Ŗ

Installation procedure:

 

ˆ

Go to website: 

http://support.salicru.com

 

ˆ

Choose the operating platform that you need and follow 
the instructions described in the web site to download the 
software.

 

ˆ

When downloading the needed files from Internet, enter 
the following licence to install the software:

511C1-01220-0100-478DF2A .

When the computer is rebooted, WinPower software will be 
shown as an icon with plug shape and green colour in the 
system tray, near the clock.

4.3.8. Considerations 

before 

commissioning with load 
connected.

Ŗ

 It is recommended to charge the batteries for 2 hours 
as minimum before using the UPS for first time. When 

supplying voltage to the equipment, the battery charger will 
automatically work. 

Ŗ

(B1) equipments with extended back up time has a 
battery charger with higher quality performances. It is 

recommended  to  charge  the  batteries  for  2  hours  as  min-
imum before using the UPS for first time.

Ŗ

 Nevertheless, those equipments with extended back 
up time and with no additional battery charger, it s rec-

ommended to charge the batteries of each battery module for 
2 hours. 

Ŗ

Although the equipment can work without charging the bat-
teries during the stated time without any problem, the risk of 
a long blackout has to be valued during the first operating 
hours and the available autonomy time in the UPS.

Ŗ

Do not start up the equipment and loads completely till 
chapter 6 states it.

Thiele KG • V

orderer W

einberg 26 • D-71522 Backnang • T

el.:(07191)3560-0 • Fax.:(07191)3560-19 • info@thiele-electroni

c.de • www

.thiele-electronic.de

Thiele KG • V

orderer W

einberg 26 • D-71522 Backnang • T

el.:(07191)3560-0 • Fax.:(07191)3560-19 • info@thiele-electroni

c.de • www

.thiele-electronic.de

Vorderer Weinberg 26

 • D-71522 Backnang • 

Tel.:+49 (0)7191 3560-0 (Fax.:-19)

Summary of Contents for SPS.1000.ADV RT

Page 1: ...VANCE RT series UNINTERRUPTIBLE POWER SUPPLY USER S MANUAL Thiele KG Vorderer Weinberg 26 D 71522 Backnang Tel 07191 3560 0 Fax 07191 3560 19 info thiele electronic de www thiele electronic de Thiele...

Page 2: ...x 07191 3560 19 info thiele electronic de www thiele electronic de Thiele KG Vorderer Weinberg 26 D 71522 Backnang Tel 07191 3560 0 Fax 07191 3560 19 info thiele electronic de www thiele electronic de...

Page 3: ...minals in UPSs 1kVA Emergency Power Off 4 3 6 Communication port 4 3 6 1 RS232 and USB interface 4 3 6 2 Smart slot 4 3 6 3 AS400 Interface with DB9 output option 4 3 6 4 Protection against transient...

Page 4: ...ntents the basic in structions and features for the equipment safety To not respect these indications can create material damages on the own equip ment installation or loads Notes of information symbo...

Page 5: ...ne of them It is essential that the cables that supplies the loads have the earth connection cable The protection earth must be connected to the frame or metallic chassis of any electrical equipment i...

Page 6: ...l conditions and avoid the possible condensations The UPS has to be completely dry before starting any instal lation task Do not store install or expose the equipment in corrosive wets dusty inflammab...

Page 7: ...ubber gloves and shoes Use tools with insulated handles Take off watches rings or other metal objects Do not place metal tools or objects over the batteries Never manipulate with your hands or through...

Page 8: ...safety requirements for UPS s used in ac cessible areas by end users EN IEC 60950 1 IT equipments Safety Part 1 General re quirements EN IEC 62040 2 Uninterruptible power supply UPS Part 2 EMC requir...

Page 9: ...with LCD Plastic beauty front Front view battery module for ADVANCE RT Fig 1 Front view models from 0 7 to 10 kVA and battery modules for extended back up times 3 1 2 Legend corresponding to the equip...

Page 10: ...ets LS2 Input connector for modem ADSL Fax line RS232 COM port Standard 3000 VA and B1 model IEC outlets LS1 USB COM port IEC inlet for AC power supply Earth connection for battery module Output conne...

Page 11: ...ule i Note relative to the batteries B0 and B1 acronyms stated the nomenclature related to batteries B0 The equipment is supplied without batteries and without accessories for them screws and electric...

Page 12: ...han 1000 VA it is possible to increase the standard back up time of the equipments by connecting additional modules and or to optimise the recharging time of the accumula tors by fitting chargers with...

Page 13: ...The available SNMP option for SPS ADVANCE RT series is a card to be inserted into the slot that the UPS has in its rear side The connection of the UPS with the SNMP is internal meanwhile the connecti...

Page 14: ...act has to be fitted in residual current device at the output of each transformer because due to its specification of isolation it will prevent the triggering of the protections fitted in the primary...

Page 15: ...s Cut the strips of cardboard enclosure Remove the accessories cables supports Remove the equipment or battery module from the pack aging keeping in mind that the it is needed the help of a second per...

Page 16: ...se way as its removing see section 4 2 4 1 4 2 4 3 Vertical assembling tower type Rotate the control panel according to section 4 2 4 2 Take the 4 plastic pieces A with angle shape supplied with the e...

Page 17: ...eak the needed trims to pass the connection bus Put the beautiful front cover back of the equipment and battery module as it is stated in section 4 2 4 1 4 2 4 5 19 rack cabinet assembling All models...

Page 18: ...of them is 2 units Proceed as follows Fix both adaptor angles A to the equipment and to the battery module as rack on their side by means of the supplied screws C B F G J K K H Fig 9 Model in rack mou...

Page 19: ...to the terminal before connecting the power supply to the input power block All the equipments have female IEC outlets in greater or lesser numbers depending on the power rate of the equipment Models...

Page 20: ...y of the two cables that goes from the button to the UPS were cut damaged On the other hand this failure would be immediately detected in the normally open EPO type with the inconvenience of the sudde...

Page 21: ...nPower is a UPS monitoring software which makes a user friendly interface of monitoring and management This software supplies an auto Shutdown for a system based on several PCs in case of an electrica...

Page 22: ...d that the equipment becomes blocked under the worst conditions It is better to not connect the loads of this kind due to the high quantity of energy resources that take from the UPS USER MANUAL Thiel...

Page 23: ...S start up with mains present For the daily start up of the equipment press over the start up key for more than 3 seconds the acoustic alarm will beep for 1 sec and the UPS will start up Fan will be s...

Page 24: ...Blue OPVH Fault Battery mode with output voltage too high Red OPVL Fault Output voltage is too low Red OPST Fault Short circuit at the output Red OVLD Warning Overload Red BATH Warning Battery voltage...

Page 25: ...e 001 Wide range 002 Gen set EBM External battery module 0 9 it is the quantity of battery modules TEST Auto test 000 Deactive 001 Active AR Automatic restart 000 Deactive 001 Active GF Green mode 000...

Page 26: ...e second to enter into the element to set 4 Select the configuration value Press the key to select the quantity of battery mod ules available for the UPS 5 Confirm the configuration Press the key for...

Page 27: ...he batteries so there are hazardous voltages in side Therefore before doing any reparation or maintenance task the internal battery fuses and or the interlink connections be tween them and the UPS hav...

Page 28: ...dequate testing tentative of repairing or not authorized modification or any other cause beyond the foreseen use or by accident fire lightnings or other dangers Neither it will cover in any case compe...

Page 29: ...al or total way with the purpose to be adapted to the customer s need Consult our Website to have more information 7 5 Technical service network Coverage both national and international from our Servi...

Page 30: ...Voltage accuracy battery mode 5 Voltage THD linear load 10 3 Voltage THD non linear load 12 6 Frequency With mains present synchronised to nominal of the input 45 55 55 65 Hz Free running battery mode...

Page 31: ...example the one supplied by the battery it is con tinuous any current that always maintain the polarity DSP It is the acronym of Digital Signal Processor A DSP is a system based on a processor or mic...

Page 32: ...irect cur rent This is done by rectifier diodes which can be solid state semiconductors vacuum or gassy valves as the mercury vapour Depending on the features of the alternating current power supply u...

Reviews: