If the instructions are not in total or partial and in 
special referred to the safety, do not carry on with 

the installation or commissioning tasks, because there 
could be a risk on your safety or on the other/s persons, 
being able to make serious injuries even the death, also it 
can cause damages to the equipment and/or to the loads 
and installation
.

Ŗ

The local electrical regulations and the different re-
strictions of the client's site, they can invalidate some 

recommendations included in the manuals. When discrepan-
cies exist, the user has to comply the local regulations.

Ŗ

The equipments provided with power cord with plug 
and outlets, can be connected and used by personnel 

without any kind of experience.

Ŗ

A person is defined as qualified, if it has experience of as-
sembling, commissioning and perfect control operating of 
the equipment, if he has the requirements to do the job and 
if has read and understand all the things described in this 
manual, in particular the safety indications. Such preparation 
is considered only valid if it is certified by our S.T.S..

Ŗ

Place the equipment the closest to the power supply and 
loads to be supplied, leaving an easy access if it were needed 
an urgent disconnection.

Ŗ

Warning labels should be placed on all primary power 
switches installed in places away from the equipment to alert 
the electrical maintenance personnel of the presence of a 
UPS in the circuit 

The label will bear the following text or an equivalent one:

Before working in this circuit.

Ŗ

Isolate the Uninterruptible Power System (UPS).

Ŗ

Check the voltage between all terminals including the 
protective earth.

Risk of voltage feedback from UPS.

1.2.3.1.  General safety warnings.

Ŗ

All connections and disconnections of the cables from the 
equipment, including the control ones, will be done with no 
power supply and the switches on rest, position «O» or «Off».

Ŗ

Shutdown the equipment completely by switching «Off» the 
button of the control panel first. Next disconnect the cable or 
by switching «Off» the input circuit breaker of the installation.

 The indiscriminate manoeuvring of the switches may 
involve production losses and/or equipment dam-

ages. Consult the documentation before doing any action 

Ŗ

Pay special attention to the labelling of the equipment 
that warns about the «Electrical shock hazard». Inside 

the equipment there are dangerous voltages, never open the 
enclosure,  the  access  has  to  be  done  by  qualified  staff.  In 
case of maintenance or fault, consult to the closest (S.T.S.).

Ŗ

Cross cable sections used to supply the equipment and loads, 
will be according to the nominal current stated in the nameplate 
label of the equipment, and respecting the Low Voltage Electro-
technical Regulations or standards of the country.

Use approved cables only

Ŗ

Protection Earth cable of the UPS drives the leakage 
current of the load devices. An isolated earth cable has 

to be installed as part of the circuit that supplies the equip-
ment. Cross cable section and its features will be same as 
the power supply cables, but with green colour with or without 
the yellow strip.

All outlets of the UPS has an earth bonding, duly connected 

and those equipments with power blocks there is an exclusive 
terminal for the load earth connection. When an outgoing dis-
tribution is done, i.e power strips, it is essential that they have 
an earth terminal connected to each one of them.

It is essential that the cables that supplies the loads have the 
earth connection cable. 

The protection earth must be connected to the frame 
or metallic chassis of any electrical equipment (in our 

case to the UPS, battery cabinet or case and loads), assuring 
that it is done before connecting the input voltage.

Check the quality and availability of the earth, it has to be 
between the defined parameters by the local or national 
regulations.

Ŗ

For the smallest devices (the ones connected with the fore-
seen power cord with plug), the user has to check the wall 
outlet corresponds with the type of supplied plug, with earth 
duly installed and connected to the local protection earth.

Ŗ

During the normal UPS operation, the power cord 
cable can't be disconnected from wall outlet, because 

the protection earth of the own UPS would be disconnected 
and also the earth from the loads connected to the output.

For this reason, the general protection earth cable of the 
building or switchgear panel that supplies the UPS will not 
be disconnected.

Ŗ

Check that the sum of the leakage currents of the UPS and 
connected load/s do not exceed over 3,5mA.

Ŗ

The installation will have input protections sized to the cur-
rents of the equipment and stated in the nameplate label 
(RCD devices type B and circuit breakers with C character-
istic or any other equivalent one).

Overload conditions are considered as a nonpermanent an 
exceptional operating mode, so these currents will not be 
kept in mind when sizing the protections.

Ŗ

Do not overload the UPS by connecting loads with inrush 
consumptions at its output, like laser printers.

Ŗ

Output protection will be done with a circuit breaker of C char-
acteristic or an equivalent one.

It  is  recommended  to  distribute  the  output  power,  into  four 
lines as minimum. Each one of them will have a protection 
circuit breaker sized to the quarter of the nominal power. 
This kind of outgoing distributions will allow that any fault in 
any device connected to the equipment, that makes a short-
circuit,  will  affect  to  the  line  with  the  faulty  device  only.  An 
uninterruptible power supply will be guaranteed to the rest of 
connected loads, due to the protection tripping of the affected 
line by the short-circuit only.

Ŗ

When replacing a fuse, do it for another of the same type, char-
acteristics format and size.

Ŗ

Under any concept the input power cord will be connected to the 
output of the equipment, either directly or through other ways.

Ŗ

All the equipments have an auxiliary terminal strip to install 
an external emergency power off button (EPO), and it will be-
long to the user property.

Type of circuit is selectable through the LCD panel of the equip-
ment. The contact is preset from factory as normally open, so 
the button must be switched to close the circuit and the voltage 
to the loads is broken. To establish the power supply to the 
loads again, the EPO button must be deactivated.

EPO doesn't affect to the power supply of the equipment, it 
only breaks the power supply to the loads as a safety measure.

Ŗ

When supplying input voltage to a UPS with fitted in or 
separate static bypass, although the inverter is still 

turned «Off» (deactivated) it doesn't mean that at the output 
there will not be voltage.

Thiele KG • V

orderer W

einberg 26 • D-71522 Backnang • T

el.:(07191)3560-0 • Fax.:(07191)3560-19 • info@thiele-electroni

c.de • www

.thiele-electronic.de

Thiele KG • V

orderer W

einberg 26 • D-71522 Backnang • T

el.:(07191)3560-0 • Fax.:(07191)3560-19 • info@thiele-electroni

c.de • www

.thiele-electronic.de

Vorderer Weinberg 26

 • D-71522 Backnang • 

Tel.:+49 (0)7191 3560-0 (Fax.:-19)

Summary of Contents for SPS.1000.ADV RT

Page 1: ...VANCE RT series UNINTERRUPTIBLE POWER SUPPLY USER S MANUAL Thiele KG Vorderer Weinberg 26 D 71522 Backnang Tel 07191 3560 0 Fax 07191 3560 19 info thiele electronic de www thiele electronic de Thiele...

Page 2: ...x 07191 3560 19 info thiele electronic de www thiele electronic de Thiele KG Vorderer Weinberg 26 D 71522 Backnang Tel 07191 3560 0 Fax 07191 3560 19 info thiele electronic de www thiele electronic de...

Page 3: ...minals in UPSs 1kVA Emergency Power Off 4 3 6 Communication port 4 3 6 1 RS232 and USB interface 4 3 6 2 Smart slot 4 3 6 3 AS400 Interface with DB9 output option 4 3 6 4 Protection against transient...

Page 4: ...ntents the basic in structions and features for the equipment safety To not respect these indications can create material damages on the own equip ment installation or loads Notes of information symbo...

Page 5: ...ne of them It is essential that the cables that supplies the loads have the earth connection cable The protection earth must be connected to the frame or metallic chassis of any electrical equipment i...

Page 6: ...l conditions and avoid the possible condensations The UPS has to be completely dry before starting any instal lation task Do not store install or expose the equipment in corrosive wets dusty inflammab...

Page 7: ...ubber gloves and shoes Use tools with insulated handles Take off watches rings or other metal objects Do not place metal tools or objects over the batteries Never manipulate with your hands or through...

Page 8: ...safety requirements for UPS s used in ac cessible areas by end users EN IEC 60950 1 IT equipments Safety Part 1 General re quirements EN IEC 62040 2 Uninterruptible power supply UPS Part 2 EMC requir...

Page 9: ...with LCD Plastic beauty front Front view battery module for ADVANCE RT Fig 1 Front view models from 0 7 to 10 kVA and battery modules for extended back up times 3 1 2 Legend corresponding to the equip...

Page 10: ...ets LS2 Input connector for modem ADSL Fax line RS232 COM port Standard 3000 VA and B1 model IEC outlets LS1 USB COM port IEC inlet for AC power supply Earth connection for battery module Output conne...

Page 11: ...ule i Note relative to the batteries B0 and B1 acronyms stated the nomenclature related to batteries B0 The equipment is supplied without batteries and without accessories for them screws and electric...

Page 12: ...han 1000 VA it is possible to increase the standard back up time of the equipments by connecting additional modules and or to optimise the recharging time of the accumula tors by fitting chargers with...

Page 13: ...The available SNMP option for SPS ADVANCE RT series is a card to be inserted into the slot that the UPS has in its rear side The connection of the UPS with the SNMP is internal meanwhile the connecti...

Page 14: ...act has to be fitted in residual current device at the output of each transformer because due to its specification of isolation it will prevent the triggering of the protections fitted in the primary...

Page 15: ...s Cut the strips of cardboard enclosure Remove the accessories cables supports Remove the equipment or battery module from the pack aging keeping in mind that the it is needed the help of a second per...

Page 16: ...se way as its removing see section 4 2 4 1 4 2 4 3 Vertical assembling tower type Rotate the control panel according to section 4 2 4 2 Take the 4 plastic pieces A with angle shape supplied with the e...

Page 17: ...eak the needed trims to pass the connection bus Put the beautiful front cover back of the equipment and battery module as it is stated in section 4 2 4 1 4 2 4 5 19 rack cabinet assembling All models...

Page 18: ...of them is 2 units Proceed as follows Fix both adaptor angles A to the equipment and to the battery module as rack on their side by means of the supplied screws C B F G J K K H Fig 9 Model in rack mou...

Page 19: ...to the terminal before connecting the power supply to the input power block All the equipments have female IEC outlets in greater or lesser numbers depending on the power rate of the equipment Models...

Page 20: ...y of the two cables that goes from the button to the UPS were cut damaged On the other hand this failure would be immediately detected in the normally open EPO type with the inconvenience of the sudde...

Page 21: ...nPower is a UPS monitoring software which makes a user friendly interface of monitoring and management This software supplies an auto Shutdown for a system based on several PCs in case of an electrica...

Page 22: ...d that the equipment becomes blocked under the worst conditions It is better to not connect the loads of this kind due to the high quantity of energy resources that take from the UPS USER MANUAL Thiel...

Page 23: ...S start up with mains present For the daily start up of the equipment press over the start up key for more than 3 seconds the acoustic alarm will beep for 1 sec and the UPS will start up Fan will be s...

Page 24: ...Blue OPVH Fault Battery mode with output voltage too high Red OPVL Fault Output voltage is too low Red OPST Fault Short circuit at the output Red OVLD Warning Overload Red BATH Warning Battery voltage...

Page 25: ...e 001 Wide range 002 Gen set EBM External battery module 0 9 it is the quantity of battery modules TEST Auto test 000 Deactive 001 Active AR Automatic restart 000 Deactive 001 Active GF Green mode 000...

Page 26: ...e second to enter into the element to set 4 Select the configuration value Press the key to select the quantity of battery mod ules available for the UPS 5 Confirm the configuration Press the key for...

Page 27: ...he batteries so there are hazardous voltages in side Therefore before doing any reparation or maintenance task the internal battery fuses and or the interlink connections be tween them and the UPS hav...

Page 28: ...dequate testing tentative of repairing or not authorized modification or any other cause beyond the foreseen use or by accident fire lightnings or other dangers Neither it will cover in any case compe...

Page 29: ...al or total way with the purpose to be adapted to the customer s need Consult our Website to have more information 7 5 Technical service network Coverage both national and international from our Servi...

Page 30: ...Voltage accuracy battery mode 5 Voltage THD linear load 10 3 Voltage THD non linear load 12 6 Frequency With mains present synchronised to nominal of the input 45 55 55 65 Hz Free running battery mode...

Page 31: ...example the one supplied by the battery it is con tinuous any current that always maintain the polarity DSP It is the acronym of Digital Signal Processor A DSP is a system based on a processor or mic...

Page 32: ...irect cur rent This is done by rectifier diodes which can be solid state semiconductors vacuum or gassy valves as the mercury vapour Depending on the features of the alternating current power supply u...

Reviews: