1. Introduction.

1.1. Acknowledgement 

letter.

We would like to thank you in advance for the trust you have 
placed in us by purchasing this product. Read this instruction 
manual carefully before starting up the equipment and keep it for 
any possible future consult that can arise.

We remain at you entire disposal for any further information or 
any query you should wish to make.

 Yours 

sincerely.

 

 

ˆ

 The equipment here described can cause important 
physical damages due to wrong handling
. This is 
why, the maintenance and/or fixing of the here described 
equipment must be done by our staff or specifically au-
thorised
.

 

ˆ

According to our policy of constant evolution, we reserve 
the right to modify the specifications in part or in 
whole without forewarning

 

ˆ

 All  reproduction or third party concession of this 
manual is prohibited
 without the previous written au-
thorization
 of our firm.

1.2.  Using this manual.

The target of this manual or publication is to provide information 
regarding the safety and to give explanations about the proce-
dures for the installation and operating of the equipment. This 
manual and rest of support documentation has to be read care-
fully before installing, location change, setting or any handling of 
any kind, including the start up and shutdown operation.

Keep this document for future consults.

In the next pages, the “equipment” and “S.T.S.” terms, are re-
ferred to the Uninterruptible Power Supply or UPS and Service 
and Technical Support respectively.

1.2.1.  Conventions and used symbols.

Some or all the symbols of this section can be used and shown 
in the equipment and/or in the description of this document. It is 
advisable to be familiar with them and understand their meaning.

 

«Danger of electrical discharge» symbol. Pay special 

attention to it, both in the indication on the equipment and 

in the paragraph referred to this user’s manual, because it con-
tents features and basic informations for person safety. To not 
respect these indications can result in serious incidents or even 
the death due to electrical discharges 

 

«Warning» symbol. Carefully read the indicated para-

graph and take the stated prevention measures, so it con-

tents basic safety instructions for persons. To not respect such 

instructions can cause serious incidents. Those indications with 
“CAUTION ” symbol content features and basic instructions for 
safety of the things. To not respect such instructions can damage 
the goods.

«Precaution» symbol. Read the paragraph text and take 

the stated preventive mediums, it contents the basic in-

structions and features for the equipment safety. To not respect 
these indications can create material damages on the own equip-
ment, installation or loads.

«Notes of information» symbol. Additional topics that 

complement the basic procedures. These instructions are 
important for the equipment use and its optimum efficiency.

«Main protective earthing terminal» symbol. Connect 

the earth cable coming from the installation to this terminal.

«Earth bonding terminal». Connect the earth cable coming 

from the load and the external battery cabinet to this terminal.

Preservation of the environment: The presence of this 

symbol in the product or in their associated documentation 
states that, when its useful life is expired, it will not be dis-

posed together with the domestic residuals. In order to avoid 
possible damages to the environment, separate this product 
from other residuals and recycle it suitably. The users can con-
tact with their provider or with the pertinent local authorities to be 
informed on how and where they can take the product to be recy-
cled and/or disposed correctly.

Alternating Current A.C..

Direct Current D.C..

Recycle.

1.2.2.  For more information and/or help.

For  more  information  and/or  help  of  your  specific  unit,  contact 
with our Service and Technical Support (S.T.S.).

1.2.3. Safety 

instructions.

Ŗ

Check the data of the nameplate are the required by the in-
stallation.

Ŗ

Never forget that the UPS is a generator of elec-
trical energy
, therefore the user has to take precau-

tions about against direct and indirect contacts

Its energy source, a part from the AC mains, lies on the bat-
teries, usually included in the same case or cabinet that the 
equipment electronics. However, some models and/or ex-
tended back up times, batteries can be supplied in a separate 
case or cabinet.

If the batteries are connected to the equipment and their pro-
tections are switched “On”, whenever they are, it is irrelevant 
if the UPS is or not connected to mains, as well as the status 
of the mains protection. The outlets or output power blocks 
will supply voltage meanwhile the battery set has energy.

Ŗ

Compliance as regards to “Safety instructions“ is 
mandatory, being the user the legal responsible 

regarding to its observance and application. Read them care-
fully and follow the stated steps in the established order, keep 
them for future consults that may arise. 

USER MANUAL

Thiele KG • V

orderer W

einberg 26 • D-71522 Backnang • T

el.:(07191)3560-0 • Fax.:(07191)3560-19 • info@thiele-electroni

c.de • www

.thiele-electronic.de

Thiele KG • V

orderer W

einberg 26 • D-71522 Backnang • T

el.:(07191)3560-0 • Fax.:(07191)3560-19 • info@thiele-electroni

c.de • www

.thiele-electronic.de

Vorderer Weinberg 26

 • D-71522 Backnang • 

Tel.:+49 (0)7191 3560-0 (Fax.:-19)

Summary of Contents for SPS.1000.ADV RT

Page 1: ...VANCE RT series UNINTERRUPTIBLE POWER SUPPLY USER S MANUAL Thiele KG Vorderer Weinberg 26 D 71522 Backnang Tel 07191 3560 0 Fax 07191 3560 19 info thiele electronic de www thiele electronic de Thiele...

Page 2: ...x 07191 3560 19 info thiele electronic de www thiele electronic de Thiele KG Vorderer Weinberg 26 D 71522 Backnang Tel 07191 3560 0 Fax 07191 3560 19 info thiele electronic de www thiele electronic de...

Page 3: ...minals in UPSs 1kVA Emergency Power Off 4 3 6 Communication port 4 3 6 1 RS232 and USB interface 4 3 6 2 Smart slot 4 3 6 3 AS400 Interface with DB9 output option 4 3 6 4 Protection against transient...

Page 4: ...ntents the basic in structions and features for the equipment safety To not respect these indications can create material damages on the own equip ment installation or loads Notes of information symbo...

Page 5: ...ne of them It is essential that the cables that supplies the loads have the earth connection cable The protection earth must be connected to the frame or metallic chassis of any electrical equipment i...

Page 6: ...l conditions and avoid the possible condensations The UPS has to be completely dry before starting any instal lation task Do not store install or expose the equipment in corrosive wets dusty inflammab...

Page 7: ...ubber gloves and shoes Use tools with insulated handles Take off watches rings or other metal objects Do not place metal tools or objects over the batteries Never manipulate with your hands or through...

Page 8: ...safety requirements for UPS s used in ac cessible areas by end users EN IEC 60950 1 IT equipments Safety Part 1 General re quirements EN IEC 62040 2 Uninterruptible power supply UPS Part 2 EMC requir...

Page 9: ...with LCD Plastic beauty front Front view battery module for ADVANCE RT Fig 1 Front view models from 0 7 to 10 kVA and battery modules for extended back up times 3 1 2 Legend corresponding to the equip...

Page 10: ...ets LS2 Input connector for modem ADSL Fax line RS232 COM port Standard 3000 VA and B1 model IEC outlets LS1 USB COM port IEC inlet for AC power supply Earth connection for battery module Output conne...

Page 11: ...ule i Note relative to the batteries B0 and B1 acronyms stated the nomenclature related to batteries B0 The equipment is supplied without batteries and without accessories for them screws and electric...

Page 12: ...han 1000 VA it is possible to increase the standard back up time of the equipments by connecting additional modules and or to optimise the recharging time of the accumula tors by fitting chargers with...

Page 13: ...The available SNMP option for SPS ADVANCE RT series is a card to be inserted into the slot that the UPS has in its rear side The connection of the UPS with the SNMP is internal meanwhile the connecti...

Page 14: ...act has to be fitted in residual current device at the output of each transformer because due to its specification of isolation it will prevent the triggering of the protections fitted in the primary...

Page 15: ...s Cut the strips of cardboard enclosure Remove the accessories cables supports Remove the equipment or battery module from the pack aging keeping in mind that the it is needed the help of a second per...

Page 16: ...se way as its removing see section 4 2 4 1 4 2 4 3 Vertical assembling tower type Rotate the control panel according to section 4 2 4 2 Take the 4 plastic pieces A with angle shape supplied with the e...

Page 17: ...eak the needed trims to pass the connection bus Put the beautiful front cover back of the equipment and battery module as it is stated in section 4 2 4 1 4 2 4 5 19 rack cabinet assembling All models...

Page 18: ...of them is 2 units Proceed as follows Fix both adaptor angles A to the equipment and to the battery module as rack on their side by means of the supplied screws C B F G J K K H Fig 9 Model in rack mou...

Page 19: ...to the terminal before connecting the power supply to the input power block All the equipments have female IEC outlets in greater or lesser numbers depending on the power rate of the equipment Models...

Page 20: ...y of the two cables that goes from the button to the UPS were cut damaged On the other hand this failure would be immediately detected in the normally open EPO type with the inconvenience of the sudde...

Page 21: ...nPower is a UPS monitoring software which makes a user friendly interface of monitoring and management This software supplies an auto Shutdown for a system based on several PCs in case of an electrica...

Page 22: ...d that the equipment becomes blocked under the worst conditions It is better to not connect the loads of this kind due to the high quantity of energy resources that take from the UPS USER MANUAL Thiel...

Page 23: ...S start up with mains present For the daily start up of the equipment press over the start up key for more than 3 seconds the acoustic alarm will beep for 1 sec and the UPS will start up Fan will be s...

Page 24: ...Blue OPVH Fault Battery mode with output voltage too high Red OPVL Fault Output voltage is too low Red OPST Fault Short circuit at the output Red OVLD Warning Overload Red BATH Warning Battery voltage...

Page 25: ...e 001 Wide range 002 Gen set EBM External battery module 0 9 it is the quantity of battery modules TEST Auto test 000 Deactive 001 Active AR Automatic restart 000 Deactive 001 Active GF Green mode 000...

Page 26: ...e second to enter into the element to set 4 Select the configuration value Press the key to select the quantity of battery mod ules available for the UPS 5 Confirm the configuration Press the key for...

Page 27: ...he batteries so there are hazardous voltages in side Therefore before doing any reparation or maintenance task the internal battery fuses and or the interlink connections be tween them and the UPS hav...

Page 28: ...dequate testing tentative of repairing or not authorized modification or any other cause beyond the foreseen use or by accident fire lightnings or other dangers Neither it will cover in any case compe...

Page 29: ...al or total way with the purpose to be adapted to the customer s need Consult our Website to have more information 7 5 Technical service network Coverage both national and international from our Servi...

Page 30: ...Voltage accuracy battery mode 5 Voltage THD linear load 10 3 Voltage THD non linear load 12 6 Frequency With mains present synchronised to nominal of the input 45 55 55 65 Hz Free running battery mode...

Page 31: ...example the one supplied by the battery it is con tinuous any current that always maintain the polarity DSP It is the acronym of Digital Signal Processor A DSP is a system based on a processor or mic...

Page 32: ...irect cur rent This is done by rectifier diodes which can be solid state semiconductors vacuum or gassy valves as the mercury vapour Depending on the features of the alternating current power supply u...