31
TC5-8SDA rev.03
TC5-8SDA
If the room temperature rises:
When
Room T
o
< Set Point + Differential 1
, the Stage 1 fans run
according to the minimum ventilation cycle.
When
Room T
o
= Set Point + Differential 1
, the Stage 1 fans run
continuously.
When
Room T
o
= Set Point + Differential 1 + Differential 2
, the
Stage 2 fans start to run.
A new cooling stage is turned on when the room temperature reaches
the set point plus the sum of the differentials of the preceding stages
plus the current stage differential.
If the room temperature falls:
When
Room T
o
= Set Point + Differentials 1 to 7
, the Stage 8 fans
return to a stop.
When
Room T
o
= Set Point
, the Stage 1 fans stop running continu-
ously and start to run according to the minimum ventilation cycle.
When the room temperature drops below this point, the stage 1 fans
operate according to the minimum ventilation cycle.
• • •
• • •