TC5-8SDA rev.03
TC5-8SDA
Humidity Compensation on Mist Cooling
Mist cooling can be turned off automatically if humidity levels are too
high. There are two modes of operation:
Mode I:
In this mode, mist units are turned off if the relative humidity
is greater than the humidity cut-off. To use this mode, set internal
switch # 10 to OFF.
Mode II:
In this mode, mist units are turned off if the last ventilation
stage is active and the relative humidity is greater than the humidity
cut-off. To use this mode, set internal switch # 10 to ON.
1
Adjusting Mist Differential
The mist differential is the variation in room temperature between the
moment the mist units turn on and the moment they turn off.The
differential can be adjusted between 0.5°F and 20.0°F (0.3°C and
11.1°C).
Set the parameter selection
knob to
MIST — TIMER/
OFFSET/DIFF/HUMIDITY
CUT-OFF
. The current time
on for the mist cycle is
displayed, alternating with the
letters "
On
".
Press the push-button three times. The mist differential is
displayed, alternating with the letters "
dIF
",
Using the adjustment knob, set the differential to the desired
value.