Adjusting Mist Offset
The mist offset is the temperature difference from the set point at
which the mist units turn off. The offset can be adjusted between
0.5°F and 40.0°F (0.3°C and 22.2°C).
Set the parameter selection knob to
MIST — TIMER/OFFSET/
DIFF/HUMIDITY CUT-OFF
. The current time on for the mist
cycle is displayed, alternating with the letters "
On
".
Press the push-button twice. The mist offset is displayed,
alternating with the letters "
Oft
".
Using the adjustment knob, set the offset to the desired value.
3
Adjusting Mist Timer Settings
Time on and time off can be adjusted between 0 and 60 minutes, in
increments of 1 minute. To deactivate mist cooling, set time on to
zero.
Set the parameter selection knob to
MIST — TIMER/OFFSET/
DIFF/HUMIDITY CUT-OFF
. The current time on for the mist
cycle is displayed, alternating with the letters "
On
".
Use the adjustment knob to set time on to the desired value (in
minutes).
Press the push-button. The current time off for the mist cycle is
displayed, alternating with the letters "
Off
".
Use the adjustment knob to set time off to the desired value (in
minutes).