ELECTRICAL CONNECTIONS
13
5.
ELECTRICAL CONNECTIONS
5.1.
General instructions
All electrical connection must be performed by an authorized professional, in conformity with the
local regulations and the indications of this manual. Connections must be done according to
norms EN 60529 and EN 60335-1, and protection norms IP 40 and IP 44.
All wiring must be waterproof insulated. Exposed cables should be protected within plastic
channel. The main electrical supply of the boiler must be connected to an independent safety of
max 16A. The boiler room lighting must be on a separate circuit.
The user is obliged to connect the boiler to an efficient grounding system.
THERMOSTAHL ROMANIA SRL declines any liability for damage caused to
people, animals and goods, due to defects caused by faulty electrical
connections or lack of connecting the boiler to an efficient grounding system.
5.2.
Control panel functions (PLUS VERSION)
5.2.1.
Description of buttons and display
After turning the regulator on, the START and STOP buttons are used to enable and disable
airflow respectively.
ECOWOOD PLUS version is equipped with a safety thermostat (STB). If the boiler reach a
temperature of 95°C safety thermostat interrupts power fan. Restarting the boiler can only be
done by detecting and removing the cause that produced overheating, or waiting for the boiler
to cool down below 90°C.
Legend
1. “F” button:
-short press – access the menu
-long press – exit submenu
2. STOP button, value decrease
4. START button, value increase
5. Mains switch
6. Fuse holder