BOILER START-UP 

 

20 

 

 

Use  the  „+”  and  „-”  buttons  to  respectively  increase  or  decrease  the  preset  emission 
temperature; please note that the value in the upper part of the thermometer symbol is x10, 
e.g.: 20°C, means 200°C. The preset emission temperature should generally be between 160 
and 250°C.  

The optimal preset emission temperature depends on the type of fuel and the heat necessity, 
and  it  should  be  determined  experimentally.  When  burning  wood,  the  flame  should  be  blue-
yellow, and when burning coal – yellowish. For example, the optimal temperature for wood is 
between 190 and 260°C. 

If optimal emission temperature causes excessive heating up of the boiler, it is best to store the 
surplus energy in a thermal buffer.  If the  central heating system does not  feature a thermal 
buffer, you must find such preset emission temperature at which the temperature of water in 
the  boiler  is  at  the  desired  level.  If  it  is  too  hot  in  a  room,  decrease  the  preset  emission 
temperature, and increase it in the opposite case. The preset boiler temperature is in this method 
of  secondary  importance,  it  prevents  exceeding  undesirable  temperature  of  the  boiler.  It  is 
recommended  to  preset  the  boiler  temperature  as  10°C  higher  than  the  expected  boiler 
temperature  after  the  emission  temperature  settles.  After  the  boiler  reaches  the  preset 
temperature, the regulator switches to SUPERVISION mode. 

Note: the regulator will automatically switch from regulation mode 3 to mode 1, if the 
emission  sensor  is  damaged  or  if  the  emission  temperature  exceeds  the  emission 
sensor measuring capacity. Therefore, it is important to set proper parameters for the 
regulator to operate in mode 1, without causing any danger.  
 

Setting  emission  temperatures  lower  than  160°C  can  cause  condensing  in  the 
chimney! 
 
If PID-S mode is chosen, it is recommended to use combined with a buffer tank.  
 
High  emission  temperature,  even  if  the  fan  rotates  slowly,  can  mean  that  the 
boiler is blocked of ash and need to be cleaned.  

 

If  emission  temperature  reaches  higher  than  400

o

C  the  boiler  will  stope  and 

alarm will be activated. 

 
 
 

 

 

 

 

 

 

 

 

Summary of Contents for ECOWOOD PLUS

Page 1: ...SOLID FUEL BOILER ECOWOOD STANDARD PLUS INSTALLATION AND USER MANUAL VERSION 2 2 UPDATE 20 08 2017...

Page 2: ...ONNECTIONS 13 5 1 General instructions 13 5 2 Control panel functions PLUS VERSION 13 5 3 Electrical connections PLUS VERSION 15 5 4 Hydraulic function scheme 16 5 5 Connecting exhaust temperature sen...

Page 3: ...f the appliance unless you have contacted the company and an authorized service contractor Only original accessories and spare parts must be used to ensure correct and safe function Make sure you resp...

Page 4: ...etrical construction causes a high yield DESCIPTION OF COMPONENTS Steel boiler body with cylindrical heat exchanger Removable rear smoke box with inspection cleaning door Upper door for ignition fuel...

Page 5: ...45x475 1380 1320 650 1015 1300 1190 2 220 ECW 60 345x475 1380 1320 650 1015 1400 1290 2 220 Nominal output is obtained with good quality wood with 15 humidity TECHNICAL DATA Boiler Type Nominal Output...

Page 6: ...nominal data presented in this manual are calculated for humidity content 15 For proper and efficient function and a long lifespan it is strictly recommended that only dry wood is used with a humidit...

Page 7: ...n In the documentation folder you will find Technical manual Warranty leaflet 3 2 Boiler room 3 2 1 General requirements The boiler must be installed in a special and separate room This room must be c...

Page 8: ...boiler s efficient and safe function The chimney must be positioned if possible in the interior of the building It must be vertical with no changes in the direction The cross section of the chimney c...

Page 9: ...BOILER MOUNTING 9 Each boiler should be connected to an independent chimney Connection of multiple boilers to the same chimney is not recommended Fig 3 Chimney distances Fig 4 Chimney connection...

Page 10: ...of the boiler a three way thermostatic valve Having a return temperature less than 55o C is very dangerous for the boiler long life and can cause warranty loss 4 3 Filling the system After completing...

Page 11: ...ERSION ECOWOOD STANDARD is equipped with an air door on the lower part and is delivered with chain thermostatic regulator Install the regulator at the connection pipe on the upper side of the boiler a...

Page 12: ...ssure reducer 17 Drainage valve F Filter 18 Cold water valve A Air relief valve 19 24 One way valves FD Water softener 4 5 2 Closed expansion vessel connection Legend 1 9 Separation valves B Hot water...

Page 13: ...ERMOSTAHL ROMANIA SRL declines any liability for damage caused to people animals and goods due to defects caused by faulty electrical connections or lack of connecting the boiler to an efficient groun...

Page 14: ...thermostat 11 Service menu symbol 12 Hot utility water temperature sensor 13 Boiler pump symbol 14 Hot utility water pump symbol HUW 15 Boiler temperature sensor 16 Exhaust temperature sensor 17 Airfl...

Page 15: ...n Terminals L N and number 1 8 are intended only for connecting devices with mains supply 230V Terminals 9 20 are intended for cooperation with low voltage devices below 12 V Tips of the connected wir...

Page 16: ...preset boiler temperature in order to fill the hot utility water tank After filling the hot utility water tank the hot utility water pump can continue work for a preset time in order to collect heat f...

Page 17: ...n sensor should be installed in such distance from the boiler at which it is not directly exposed to flames and where the emission temperature does not exceed 450 C 5 6 Connecting temperature sensors...

Page 18: ...he upper door fire chamber and introduce a sufficient amount of small and thin pieces of wood Using sheets of thin paper light the wood placed inside the boiler Close the door of the boiler Wait sever...

Page 19: ...method is based on boiler temperature indications T1 it consists in constant smooth modulation of the fan revolutions in order to stabilize the preset boiler temperature The regulator itself selects t...

Page 20: ...preset emission temperature and increase it in the opposite case The preset boiler temperature is in this method of secondary importance it prevents exceeding undesirable temperature of the boiler It...

Page 21: ...upply The flame is too fast dry and might make a noise 6 7 Supervision mode After the boiler has reached the preset temperature it will enter in SUPERVISION mode In the SUPERVISION mode the fan is ena...

Page 22: ...move the turbinators from the tubes and clean the tubes with the appropriate tool Afterwards clean the exterior surface of the cylindrical heat exchanger with the exchanger cleaning tool as shown in F...

Page 23: ...and pumps function properly 7 3 2 Weekly maintenance The boiler must be cleaned every 3 4 days or at least once a week depending on the ash quantity accumulated on the boiler walls and in the heat ex...

Page 24: ...hly all the surfaces of the boiler as described in the corresponding paragraph Also clean the chimney box and all the chimney parts where ash might be deposited After cleaning all the ash empty the as...

Page 25: ...the boiler but low temperature at the radiators too high hydraulic resistance in the heating network thermostatic mixing valve is connected wrong increase the pump speed check replace the mixing valve...

Page 26: ...care utilizeaz combustibili solizi cu nc rcare manual i automat cu puterea util mai mic sau egal cu 500 kW Terminologie cerin e ncercare i marcare Heating boilers Part 5 Heating boilers for solid fuel...

Page 27: ...THERMOSTAHL ROMANIA HEATING SYSTEMS S R L DRUMUL OSIEI 57 59 sector 6 Bucharest 062395 Romania www thermostahl ro...

Reviews: