Note 1
See section 10.3: Weather compensation for details of outside air temperature sensor and wiring to
the air curtain.
Set DIP switch 2 and 4 to the ON position in the air curtain that has the outdoor air temperature
sensor wired into it. For Master/Slave multiple installations this must be the Thermostat Master unit.
Note 2
When remote controller is set to automatic the outdoor air temperature determines the heat output as
follows:
Less than 10°C / 50°F, full heat operates.
Between 10°C / 50°F and 15°C / 60°F, half-heat operates.
More than 15°C / 60°F, no heat operates
When controlling multiple air curtains in a master/slave arrangement, plug the remote controller into
any one of the units.
Connect this unit to other unit(s) with a Thermoscreen RJ extension lead (not supplied), as per the
diagram below. Each air curtain must have its own electrical supply.
12. MULTIPLE AIR CURTAINS