background image

 
 

9901098-2-2 

 

Page | 6  

 

1

 

 

The air curtain is designed to be recessed within ceiling voids or bulkheads within a building and 
located horizontally over a doorway. It must not be installed outside of the building. 

 

7.1 Location 

 

Mount the air curtain above and as close to the doorway as 
possible, with: 
 

 

the recessed grille not more than 3.5m / 11ft 6in 
above floor level 

 

the air discharge (see 1, Fig 1) section of the 
recessed grille nearest the doorway and the air inlet 
section (see 2, Fig 1) furthest from the doorway 

 
Beware of doorway top edges, structural beams, door 
opening/closure devices, etc., which may interfere with  
the air stream and affect the location of the unit. 

 
 

7.2 Ceiling 

Suspension 

 
Step 1

 

 Cut an aperture in the ceiling to the dimensions 

 

in Appendix 1. Cut notches, if necessary, to clear  

 

screws in the air curtain casing. 

 

 

Step 2

 

Fix M10 / 3/8” UNC threaded rods (not supplied) 

 

through the 2 holes at each end in the top casing 

 

(see Fig 2). Feed the rods through the casing and 

 

attach to fixing brackets near the bottom of the  

 

unit (see Fig 3, looking up into the air curtain). Use  

 

M10 / 3/8” UNC lock-nuts either side of the fixing 

 

bracket to secure the hanging rod. 

 
 
 

7. INSTALLATION 

NOTE:

 For the air curtain to work well the doorway should be less than the width of the airstream.

 

Fig 1 

NOTE

For LPHW models, pipework will need to be 

installed above the curtain. Allow sufficient access and 
height clearance within the ceiling void to do this.

 

Fig 2 

NOTE

Do not let these four hanging rods come below 

the bottom of the unit casing or they may prevent the 
recessed grille fitting properly. 

Fig 3 

Summary of Contents for HX1000AR

Page 1: ...9901098 2 2 Page 1 AIR CURTAIN HX RECESSED RANGE INSTALLATION OPERATION AND MAINTENANCE INSTRUCTIONS N America English...

Page 2: ...E SYSTEM 15 16 SIGN OFF 15 17 FAULT CONDITIONS 16 18 SERVICE MAINTENANCE 17 19 WARRANTY 18 APPENDIX 1 DIMENSIONS OF HX RECESSED AIR CURTAIN 19 APPENDIX 2A WIRING DIAGRAM HX1000ER 208V 20 APPENDIX 2B W...

Page 3: ...rs and controls A 25mm 1in size cable gland or conduit connector should be used for the Electrical Supply into the air curtain The air curtain must be grounded Air Curtain Model Electrical Supply V ph...

Page 4: ...o be recess mounted inside a building and located horizontally over a doorway They must not be installed on the outside of a building Please complete the following details for your reference Date of P...

Page 5: ...tdoor Air Sensor Optional Available for weather compensation control The following tools are required for installation Flat head screwdrivers Phillips head screwdrivers 10mm wrench Adjustable wrench E...

Page 6: ...p 1 Cut an aperture in the ceiling to the dimensions in Appendix 1 Cut notches if necessary to clear screws in the air curtain casing Step 2 Fix M10 3 8 UNC threaded rods not supplied through the 2 ho...

Page 7: ...ctly as shown in the diagram in Appendix 1 For the design of the water pipework system and pump water flow rates and pressure drops for maximum heat output of the air curtain are given in the table be...

Page 8: ...nd attach it to the bottom of the air curtain casing using the Philips head screws supplied Start with the screws shown in Fig 7 and then fit the two at each end of the discharge grille Step 3 If fitt...

Page 9: ...he back case and secure back case to switch box using 2 x mounting screws not supplied see Fig 11 Step 3 Connect the RJ plug to the RJ socket on the PCB Step 4 Refit the front case On the back of the...

Page 10: ...or Switch Control After 30s the heating is disabled and the fan goes to low speed Unit operates normally in MANUAL Mode or AUTO Mode from the Remote Control ON Door Open Normal Control Door Closed Hea...

Page 11: ...ree contacts supplied by the installer to a north facing wall Use a 2 core cable to connect the outdoor air thermostat to 2 way terminal IN1 on the Ecopower PCB see Fig 10 On the Ecopower PCB set DIP...

Page 12: ...d Thermostat master For master slave installations Only the air sensor thermistor in the thermostat master air curtain will be used for measuring air temperature Set DIP switch 1 to ON in the air curt...

Page 13: ...When remote controller is set to automatic the outdoor air temperature determines the heat output as follows Less than 10 C 50 F full heat operates Between 10 C 50 F and 15 C 60 F half heat operates...

Page 14: ...54 HX1500 52 HX2000 54 1120 660 1540 905 2165 1275 LOW red wire 3 2 4 7ft 10in HX1000 50 HX1500 49 HX2000 50 925 545 1290 760 1815 1070 4 1 9 6ft 3in HX1000 47 HX1500 46 HX2000 47 730 430 965 570 144...

Page 15: ...scale shows the level selected Automatic mode Heat output is controlled automatically according to Room air temperature Incoming air temperature or External air temperature This is dependent on the se...

Page 16: ...air curtain be given adequate instruction and supervision by a person responsible for their safety Children and those with reduced physical sensory or mental capabilities should not operate the air cu...

Page 17: ...ill flash green 17 2 Fuses In the event of an electrical fault internal electrical fuses may operate There are two internal fuses located on the motherboard inside the air curtain Fuse 6 3A T supplies...

Page 18: ...t dirt and debris Unclip the fan motor electrical connector Unfasten 4 x M6 nuts bolts on each fan deck Unfasten M4 screws at bottom edge of fan deck Carefully lift the fan deck away from the air curt...

Page 19: ...n in compiling these instructions to ensure they are correct Thermoscreens Canada disclaims all liability for damage resulting from any inaccuracies and or deficiencies in this documentation Thermoscr...

Page 20: ...1m unit 5 for 1 5m 2m units Use all drop rod holes B C 200 7 9 Rp in BSPP LPHW connections E Effective Width of Airstream Entry points for electrical supply and controls mm inch 2235 88 0 1185 46 7 72...

Page 21: ...ite Red Yellow Black REMOTE CONTROL To Slave Air Curtain M a s t e r S l a v e C a b l e Red 85 C H11 Auto Thermal Trip F1 6 3A T F2 100mA F Link TERMINAL BLOCK L1 L2 L3 L1 L2 L3 208V 3ph 60Hz E E F3...

Page 22: ...S la v e C a b l e Red 85 C H11 Auto Thermal Trip F1 6 3A T F2 100mA F Link F3 F4 F3 F4 6 3A T External Air Sensor TERMINAL BLOCK L1 L2 L3 L1 L2 L3 208V 3ph 60Hz E E Fan Motor 1 Red Black Blue A1 A2 1...

Page 23: ...3 K8 K3 K4 K6 K7 K9 Neutral K10 HEALTHY J3 J2 F1 F2 INHIBIT LED 1 ECOPOWER CONTROLLER CVR 1008 Black Black Blue Red White Fan Motor 1 Fan Motor 2 First Stage Heating bottom elements Second Stage Heat...

Page 24: ...ral K10 HEALTHY J3 J2 F1 F2 INHIBIT LED 1 ECOPOWER CONTROLLER CVR 1008 White Red Yellow Black Fan Motor 1 CONTACTOR 230V AC Coil A1 A2 13NO 14NO 1 2 3 4 5 6 K1 CONTACTOR 230V AC Coil A1 A2 13NO 14NO 1...

Page 25: ...White Red Yellow Black Red 85 C H11 Auto Thermal Trip x2 F1 6 3A T F2 100mA F Link Fan Motor s star point connection 1st Stage 2 5mm Black tri rated cables 2nd Stage 2 5mm Grey tri rated cables First...

Page 26: ...OLLER CVR 1008 Black Blue Red White White Red Yellow Black Fan Motor 1 Fan Motor 2 CONTACTOR 230V AC Coil A1 A2 13NO 14NO 1 2 3 4 5 6 K1 CONTACTOR 230V AC Coil A1 A2 13NO 14NO 1 2 3 4 5 6 K2 Red Black...

Page 27: ...Motor 2 Fan Motor 1 Live 1 K2 K1 Live 2 K5 Live 3 K8 K3 K4 K6 K7 K9 Neutral K10 HEALTHY J3 J2 F1 F2 INHIBIT LED 1 ECOPOWER CONTROLLER CVR 1008 Black Blue Red White Black Blue Red White F3 F3 F4 6 3A T...

Page 28: ...High speed Medium speed Low speed Neutral Fan Motor 2 Fan Motor 1 Live 1 K2 K1 Live 2 K5 Live 3 K8 K3 K4 K6 K7 K9 Neutral K10 HEALTHY J3 J2 F1 F2 INHIBIT LED 1 ECOPOWER CONTROLLER CVR 1008 Brown Blue...

Reviews: