T9901096-3-3 CAN-USA-ENG (v9)
Page | 1
0A
1
0
.1 Remote switch contacts IN0, IN1
Terminals IN0 and IN1 on the Ecopower PCB inside the air
curtain can be used to provide different control strategies
using remote volt-free contacts (see Fig 8). This could be to
provide remote On/Off from a timer or BMS Digital/Output
contact, to work with a door switch or for simple weather
compensation control to disable heating when outdoor air
temperatures become warmer. Table 4 describes the
different functions:
Function
IN0
Notes
Remote
On/Off
(INHIBIT)
Unit operates
normally in
MANUAL Mode or
AUTO Mode
from the Remote
Control
Unit switches off
after 15s, with fan
run-on at Medium
fan speed if
DIP 2 = OFF
Use the Remote Control to set up unit and
then hide it away if required. *
On/Off is then done via IN0 using a remote
volt-free contact.
Function
IN1
DIP 4
IN0
Notes
Door
Switch
Control
After 30s the
heating is disabled
and the fan goes to
low speed
Unit operates
normally in
MANUAL Mode or
AUTO Mode
from the Remote
Control
ON
Door Open:-
Normal Control
Door Closed:-
Heating Off
Low Fan Speed
Summer
Winter
Unit operates
normally in
MANUAL Mode or
AUTO Mode
from the Remote
Control
COLD DAY
Heating is disabled
straight away,
Fan speeds
operate normally
from the Remote
Control
WARM DAY
OFF
Simple weather
compensation control
using an outdoor air
thermostat with volt free
contacts
(see Section 12.3)
1
0
. EXTERNAL CONTROLS
Fig 8
WARNING:
Do not apply any voltage to terminals IN0 and IN1 as this will damage the Ecopower
PCB inside the air curtain.
Table 4
NOTE:
Wire volt-free, remote switch contacts to 2-way screw terminals IN0 and IN1 using 2-core
cable.
*
NOTE:
The Ecopower Remote Control must stay plugged-in for the air curtain to keep working.
An optional plug-in EEPROM is available from Thermoscreens so the Remote Control can be un-
plugged and the air curtain stay working. Visit the Thermoscreens website for details.