CHARACTERISTICS

Conditions for application

The DCC-9 is an Energy Management System specially designed to 
allow the connection of an EV Charger to be connected to a power 
source without affecting load calculation.

Installations types

Group installation, Wall installation, Ceiling installation

Main Power Supply (CB)

The DCC – Charge controller for electric vehicles can be powered by a 
240/208V AC single phase source. The following options are offered by 
each DCC model:

Models

Breaker

Main power supply

EV charger

60A

70A

80A

90A

100A 125A

DCC-9-30A

30A

DCC-9-40A

40A

DCC-9-50A

50A

DCC-9-60A

60A

Voltage and wiring

240/208V AC single phase:
L1, L2, Neutral, Ground.

Terminals size

up to 2/0 

(CU/AL)

Frequency

50 to 60 Hz

Operation temperature

-22°F to 113°F (-30°C to 45°C)

Dimensions

*

 

(H" x W" x D")

Total weight

*

12" x 12" x 7.5"

17 lb (7,71 kg)

NEMA 3R enclosure

14" x 13" x 8"

18 lb (8,16 kg)

*Approximative and can change without notice.

V1

 

Secondary Load Supply (EVC)

The DCC – Charge controller for electric vehicles will provide power to 
a charging station through a 30A, 40A, 50A or 60A 240/208V AC circuit 
breaker, L1, L2 and ground. The DCC is equipped with a Square D cir-
cuit breaker (QUO230, QUO240, QUO250 or QUO260). 

Trip Percentage (TP)

The DCC - Charge controller for electric vehicles is factory set to turn 
off the charging station if the total consumption of a service exceeds 
80%. For other configurations, please contact the factory.

Power outage

In the event of a power outage, the DCC – Charge controller for elec-
tric vehicles automatically restore the power supply to the vehicle 
charging station when power returns.

Recovery time (RT)

Following a power cut to the electric vehicle supply equipment (EVSE), 
a 15 minutes delay is initiated to monitor the total consumption of the 

electrical power system. Power to the vehicle will then be restored if 
the total load consumption is lower than 80% of the main circuit brea-
ker rating during a period exceeding the 15 minutes’ recovery time.

TYPICAL INSTALLATION 

 

 NOTES 

For outdoor installation, use our NEMA 3R enclosure 

(DCC-9-XXA-3R). 

for HOMES

DCC-9 

with 

MAIN DISCONNECT

DCC-9 

with 

SUB PANEL

for C
ONDOS

DCC-9 

with 

METER STACK

Summary of Contents for DCC-9 Series

Page 1: ...240 208V Single Phase 60A 70A 80A 90A 100A 125A ALIMENTATION PRINCIPALE 120 240 208V Monophas 60A 70A 80A 90A 100A 125A APPROVED MARKET North America MARCH AGR Am rique du Nord MODELS MOD LES DCC 9 3...

Page 2: ...2...

Page 3: ...licensors Additional information s are available on request The following logos are trade names or trademarks of THERMOLEC LTE E RECHARGE V HICULE LECTRIQUE in the United States and in Canada The DCC...

Page 4: ...ric power source is adequate for the use of the DCC Charge controller for electric vehicles Do not use any cleaning solvents to clean the DCC Charge controller for electric vehicles Limited warranty 1...

Page 5: ...for electric vehicles will provide power to a charging station through a 30A 40A 50A or 60A 240 208V AC circuit breaker L1 L2 and ground The DCC is equipped with a Square D cir cuit breaker QUO230 QUO...

Page 6: ...proper ins tallation Ceiling installation The installation may be done in any direction WARNING Warranty automatically void if the DCC is installed incorrectly STEP 3 INSTALLATION Ceiling installation...

Page 7: ...T Suivre les codes lectriques nationaux et locaux ainsi que les instructions contenues dans l appareil IMPORTANT Wire in accordance with local and National Electrical codes Read instructions carefully...

Page 8: ...240 208V Orange STEP 6 START UP DCC power supply 1 Supply electrical power to the DCC 2 Wait ten 10 seconds 3 Check if the contactor is switched on 4 Check the pilot light GREEN at all time compliant...

Page 9: ...rging station will be de energized Yellow The charging station is not energized The total loads exceed 80 The resumption time will start when the total load is lower than 80 Yellow The charging statio...

Page 10: ...dants de licence Ce manuel d installation ne peut pas tre modifi reproduit ou copi en tout ou en partie sans l autorisation crite pr alable de THERMOLEC LTE E RECHARGE V HICULE LECTRIQUE et ses conc...

Page 11: ...s assurer que la source d alimentation lectrique soit suffisante pour permettre l utilisation d un ou de plusieurs DCC Contr leur de charge pour v hicules lectriques Ne pas utiliser de solvants de net...

Page 12: ...riques peut per mettre l alimentation d une borne de recharge avec un disjoncteur de 30A 40A 50A ou 60A 240 208V CA L1 L2 et avec mise la terre Le DCC est muni par d faut d un disjoncteur Square D QUO...

Page 13: ...vous aux indications sur le boitier afin d assurer que l orientation de l installation soit conforme Installation au plafond L installation peut tre faite dans toutes les orientations ATTENTION Garant...

Page 14: ...208V Orange T 24V 240V 208V COM TRANSFORMER TRANSFORMATEUR 50VA 240 208V Orange TAPE 6 MISE EN MARCHE Alimentation du DCC 1 Alimenter le DCC en lectricit 2 Attendre dix secondes 3 V rifier si le conta...

Page 15: ...NT Suivre les codes lectriques nationaux et locaux ainsi que les instructions contenues dans l appareil IMPORTANT Wire in accordance with local and National Electrical codes Read instructions carefull...

Page 16: ...IP switch 3 V rifier si les transformateurs de courant CT sont bien connect s et bien enclench s 4 V rifier la connexion des transformateurs de courant aux terminaux de la carte lec tronique et la pol...

Reviews: