PELLING ECO
23
NOTE: A constantly high-set stage can lead to overheating. A constantly too
low set stage can lead to greater pollution of the boiler.
5.3.5
Cleaning interval (small cleaning)
The boiler regularly makes a "small cleaning" when he burns down part from
burning chamber. Depending on the quality of the pellets varies often
necessary.
If the burner tray to overcrowding tends (through higher embers much ash in
the burner shell), the cleaning interval should be set shorter.
- MENU - button until the SETTINGS menu
-
▼
- button until the menu item CLEANING
- MENU - Button to enter into the point
- Use the
▼
and
▲
- buttons, the desired cleaning interval can be set
- MENU - Button to exit the setting
5.3.1
Overrun-Nachlauf (external request)
With the control input by external demand, the boiler via an external potential
free contact will be switched on and off.
This may for example be a room thermostat. However, if the contact has a
short response time (eg by circulation of air), the boiler would shut constantly
short and ignite again.
To avoid this, a boiler can be set overrun.
FUNCTION: If the contact is opened, the boiler will run for the submitted time.
If the contact is only opened briefly and then closed again, boiler will continue
to work without turning off.
- MENU - button until the SETTINGS menu
-
▼
- button until the menu item OVERRUN
- MENU - Button to enter into the point
- Use the
▼
and
▲
- buttons the desired delay time can be set in minutes
- MENU - Button to exit the setting
NOTE: If the boiler overheat during this time, it switches off prematurely.
Summary of Contents for PELLING 25 ECO
Page 2: ...2...
Page 15: ...PELLING ECO 15 4 2 Technical data...
Page 18: ...PELLING ECO 18...
Page 19: ...PELLING ECO 19...
Page 20: ...PELLING ECO 20...
Page 38: ...PELLING ECO 38 7 4 Hidraulic connection diagrams...
Page 39: ...PELLING ECO 39...
Page 40: ...PELLING ECO 40...
Page 43: ...PELLING ECO 43...
Page 56: ...PELLING ECO 56...
Page 57: ...PELLING ECO 57...