PELLING
35
The flue gas pipes should be from non-inflammable materials that are suitable and
resistant to combustion products and to their possible condensation.
The chimney connection must be put in the chimney 20mm inwards to prevent any
condensation from the chimney to the boiler. Horizontal parts should have a slope of
at least 3% upwards. The length of the horizontal part should be minimal and not
longer than 2 meters with the ability to clean and remove the accumulated ash. The
chimney connection should be carried out with a maximum of two angles of 90°C.
As flue pipe do not use metal flexible hoses. All parts of the flue pipes
should be safe and replaceable, allowing internal cleansing. Avoid
horizontal deviation.