![Thermo Scientific Thermo Scientific 3906 Operating Manual Download Page 48](http://html.mh-extra.com/html/thermo-scientific/thermo-scientific-3906/thermo-scientific-3906_operating-manual_1104831048.webp)
| Handling and Control
8-2
|
Model 3900 Series
Thermo Scientific
Chapter 8
Figure 8-2
Main Power
Figure 8-3
Switches
Switch and Indicator Light (Figure 8-3).
The refrigeration switch controls power to the refrigeration system. The refrigeration
indicator lights when the refrigeration switch is on and the compressor is receiving power.
Defrost Switch and Indicator Light (Figure 8-3).
The defrost switch controls power to the defrost system. Setting the defrost switch to Auto
will provide two 15-minute defrost cycles during a twenty-four hour period. The defrost
indicator lights when the defrost switch is on and the environmental chamber is in a
defrost cycle.
Humidity Switch and Indicator (Figure 8-3)
The humidity switch controls the power to the humidification system circuit. The humidity
indicator light will cycle as the controller toggles between humidify and dehumidify.
Dehumidify Switch and Indicator (Figure 8-3)
Indicator lights
Indicator lights
Dehumidify
Switch
Defrost
Switch
Humidify
Switch
Refrigeration
Switch
The defrost switch must be set to Auto when the temperature setpoint is 10°C, or
below.
NOTE
When set temperature is above 10°C and the defrost switch is set to Auto,
periodic temperature inconsistencies can occur.
Summary of Contents for Thermo Scientific 3906
Page 6: ...Table of Contents A 4 Model 3900 Series Thermo Scientific ...
Page 12: ... Safety Notes 1 6 Model 3900 Series Thermo Scientific Chapter 1 ...
Page 22: ... Installation 4 6 Model 3900 Series Thermo Scientific Chapter 4 ...
Page 42: ... Product Description 5 20 Model 3900 Series Thermo Scientific Chapter 5 ...
Page 46: ... Operation 7 2 Model 3900 Series Thermo Scientific Chapter 7 ...
Page 76: ... Disposal 11 2 Model 3900 Series Thermo Scientific Chapter 11 ...
Page 84: ... Specifications 12 8 Model 3900 Series Thermo Scientific Chapter 12 ...
Page 94: ... Service 13 10 Model 3900 Series Thermo Scientific Chapter 13 ...
Page 95: ...Thermo Scientific Model 3900 Series 13 11 Service Chapter 13 ...
Page 99: ...Thermo Scientific Model 3900 Series 13 15 Service Chapter 13 ...
Page 100: ... Service 13 16 Model 3900 Series Thermo Scientific Chapter 13 ...
Page 101: ...Thermo Scientific Model 3900 Series 13 17 Service Chapter 13 ...
Page 102: ... Service 13 18 Model 3900 Series Thermo Scientific Chapter 13 ...