All installations and services must be performed by qualified service personnel.
44
ADJUSTMENT”, SECTION L.
: Do not start burner unless blower door is
secured in place.
D. CLEANING OR REPLACING FLUE PIPES
Flue pipes should be inspected during the annual maintenance check-up or during each
subsequent service call.
Check all flue pipes for restrictions due to soot, or carbon build-up, as well as foreign
matter, or any materials, that cause the venting system to restrict the proper venting of
combustion products. If a restriction is found, the flue pipe
must
be cleaned or replaced
to ensure proper venting.
Flue pipes should also be inspected for any signs of corrosion, deterioration or leakage
that may cause combustion by-products to infiltrate the home or indoor environment.
If signs of corrosion, deterioration or leakage are evident, the flue pipe
must
be replaced
with a properly sized, agency-approved, flue pipe.
E. EXTENDED SHUTDOWN
If this furnace is shut down or off for an extended period of time, several steps can be taken to
help insure a smooth and reliable start.
ON SHUT DOWN:
1.
Close the fuel supply shutoff valve(s).
2.
Turn the furnace power switch “off” and disconnect electrical power to the unit.
3.
Fill the oil tank to prevent condensation (oil units only).
4.
If shutdown exceeds one season, an oil stabilizer should be added to the oil tank as
recommended by your oil supplier (oil units only).
ON START-UP:
1.
Have the heating system (and furnace) inspected and started by a qualified service person.
2.
Check for a clean, adequate supply of fuel.
3.
Set the room thermostat above room temperature.
4.
Open all shutoff valves in the fuel supply line.
5.
Turn “on” the main power at the disconnecting switch and at the furnace power switch to
start the burner. If the burner does not start, immediately reset the burner primary
(ignition) control module. On oil furnaces, if required, vent the fuel of air as soon as the
burner motor starts. If the burner stops during venting, wait three to five minutes before
attempting to restart.
Summary of Contents for OME-72D36
Page 2: ......
Page 7: ...All installations and services must be performed by qualified service personnel 4a...
Page 21: ...All installations and services must be performed by qualified service personnel 18 Figure 6...
Page 34: ...All installations and services must be performed by qualified service personnel 31...
Page 53: ...All installations and services must be performed by qualified service personnel 50...
Page 54: ...All installations and services must be performed by qualified service personnel 51...
Page 55: ......