Specifications (Rev. 12/03)
3
ELECTRICAL COMPONENTS
NOTE: Disconnect components from unit circuit to check resistance.
Current Draw (Amps)
Resistance—Cold
at 12.5 Vdc
(Ohms)
Fuel Solenoid
1.4
8.8
Damper Solenoid
5.7
2.2
Throttle Solenoid
2.9
4.3
Glow Plug
7.1
1.8
Pilot Solenoid
0.7
17.0
Starter Motor—Gear Reduction Type
250-375*
Modulation Valve (Optional)
1.7**
7.6
Hot Gas Bypass Valve (Optional)
1.1
11.1
* On-the-engine cranking check. Bench test is approximately 100 amps on the direct drive starter and
approximately 80 amps on the gear reduction starter.
**Test at 12.5 Vdc
SMART REEFER µP-VI MICROPROCESSOR TEMPERATURE CONTROLLER
Temperature Controller:
Type
Electronic THERMOGUARD µP-VI Microprocessor with digital
thermostat, thermometer and fault indicator monitor
Setpoint Range
-20 to 80 F (-29 to 27 C)
Programmable setpoint range to -25 to 90 F (-32 to 32 C)
Digital Temperature Display
-40 to 99.9 F (-40 to 40 C)
Internal Defrost Timer:
Temperature Pulldown
2, 4, 6, 8 or 12 hours (selectable, standard setting 4)
Temperature In-range
4, 6, 8 or 12 hours (selectable, standard setting 6)
Defrost Initiation: Coil Sensor
Coil must be below 45 F (7 C)
Defrost Termination: Coil Sensor
Terminates defrost with coil temperature above 58 F (13 C)
Interval Timer
Terminates defrost 30 to 45 minutes (programmable) after initiation
if coil sensor has not terminated defrost
Summary of Contents for SB-190 30
Page 4: ......
Page 8: ......
Page 14: ...4...
Page 26: ...Unit Description Rev 12 03 16 Front View AJA890...
Page 40: ...Operating Instructions Rev 12 03 30...
Page 74: ...64...
Page 92: ...82...
Page 100: ...90...
Page 113: ...103 SB 100 190 Schematic Diagram Page 1 of 2...
Page 114: ...104 SB 100 190 Schematic Diagram Page 2 of 2...
Page 115: ...105 SB 100 190 Wiring Diagram Page 1 of 5...
Page 116: ...106 SB 100 190 Wiring Diagram Page 2 of 5...
Page 117: ...107 SB 100 190 Wiring Diagram Page 3 of 5...