Electric Standby Mechanical Diagnosis (Rev. 1/99)
84
Unit in vacuum. Frost on
expansion valve only
Ice plugging expansion valve orifice
Apply hot wet cloth to expansion
valve. Moisture indicated by
increase in suction pressure.
Replace drier
Plugged expansion valve strainer
Clean strainer or replace expansion
valve
Sensor bulb lost charge
Replace expansion valve
ELECTRIC STANDBY SERVICE CHECKS
1. Motor does not run
1. Check for power at source
2. Check for power at plug
3. Check for power at compressor contactor
4. Check for power at overload terminals (contactor
closed)
5. Check for power at motor terminals
2. Power at motor terminals but motor does not run
1. Replace motor
3. Motor hums but does not run
1. Check for locked rotor
2. Check for worn bearings. Replace if necessary
3. Check for locked compressor and repair
4. Power source for single phasing
5. Check capacitors (on single phase units)
4. Check transformer
1. Check for power output 16 Vac, 12 volt system
5. Check rectifier
1. Check for rectifier output 14 Vdc, 12 volt system
CONDITION
POSSIBLE CAUSE
REMEDY
Summary of Contents for 914 724
Page 4: ......
Page 8: ......
Page 14: ...4...
Page 16: ...6...
Page 32: ...22...
Page 38: ...28...
Page 98: ...88...
Page 107: ...97 Model 10 and 20 Schematic Diagram...
Page 108: ...98 Model 10 Wiring Diagram...
Page 109: ...99 Model 20 Wiring Diagram...
Page 110: ...100 Model 20 Single Phase with Heat Option Schematic Diagram...