BTH Electric Boilers USE & CARE MANUAL 

(Revision June.2014)

,                                                                                     Page 

13.

 

buttons  are  pressed  again  the  offset  value  will 
change  up  to  a  value  of  +  -10F(5C)  from  the 
original  setting  made  in  the  configuration  menu. 
The  new  value  will  blink  during  5  sec.  and  the 
display  will  then  go  back  to  the  standard  view 
and the new target temperature will be shown.  

Afterward,  when  the 
button  will  be  pressed,  it  will  show  the  value  of 
the  offset  made  previously  and  can  be  re-
adjusted. 

 

Boost system operation  

The  controller  incorporates  a  unique  feature  that 
enables the target boiler temperature to automatically 
be  increased  when  the  building  heat  load  increases 
but  cannot  be  fulfilled  with  the  actual  boiler  target 
temperature and consequently the room thermostat(s) 
cannot be satisfied within a pre-determined period. 
 
Example: 
-Return to normal heat load after low demand periods 
occurring during sunny days. 
-Long  periods  without  heating  which  needs  higher 
boiler temp. to recuperate. 
-Return 

to 

normal 

room 

temperature 

after 

thermostat’s “nights set back” program 

80F
27C

70F
21C

60F
15C

50F

10C

10F

-12C

40F

4C

30F

0C

20F

-7C

0F

-17C

-10F
-23C

-20F
-29C

70F/21C

80F/27C

100F/-38C

90F/32C

110F/43C

120F/49C

130F/54C

Température ext.  / Outdoor temperature 

T

e

m

p

d

e

 co

n

si

g

n

e

 /

 T

a

rg

e

te

m

p

NOR

MAL

BOO

ST

HAUSSE AUTOMATIQUE DU POINT DE CONSIGNE 

« BOOST »

AUTOMATIC INCREASE OF TARGET TEMPERATURE

 

The  controller  will  engage  the  “Boost”  program 
when  the  heat  demand  on  terminals  W&R  has 
been  maintained  for  a  pre-determined  period 
according  to  the  type  of  selected  application. 
Once this  period  has been  reached, the “Boost” 

icon  will  appear  on the  display and the boiler 

target  temperature  will  start  increasing  very 
slowly over a pre-determined period and up to a 
pre-calculated  maximum  value  until  the  heat 
demand  applied  on  W&R  terminals  has  been 
completed. 
On  a  new  heat  demand,  the  previous  boost 
period  is  forgotten  and  the  boiler  target  gets 
back to its original setting  
If  the  system  is  in  “boost”  most  of  the  time,  this 
means 

that  the 

boiler 

target  parameter 

established during “Setting procedure” would  be 
too low for the heating system on which the unit 
is  applied.  This  boiler  target  could  simply  be 
gradually  increased  by  pressing  the  +  button  or 
by re-setting the operating parameters using the 
tool menus. 
N.B. The boost program is  a  marvellous feature 
that  works  fine  on  applications  where  the 
number of room thermostats is in limited quantity 
otherwise  it  may  happen  that  during  very  cold 
periods  the  heat  demand  from  all  the 
thermostats may not become satisfied.  
If  your  application  needs  the  boost  program  to 
be  cancelled,  you  can  do  it  by  pressing    the 
button 

for 6 sec. and the display will show 

icon and the two options ON or OFF will blink 

and  can  be  selected  using  the  +  -  button.  The 
controller  will  register  the  selected  option  and 
return to normal operation if the buttons remains 
untouched  for  5  sec.  or  if  the 

button  is 

pressed. 
 

Summary of Contents for MINI Ultra 12

Page 1: ...tion and maintenance of this product It is imperative that all persons who are expected to install operate or adjust this boiler should read these instructions carefully Any questions regarding the operation maintenance service or warranty of this electric boiler should be directed to the supplier When all installation steps have been completed insert this installation manual in its original envel...

Page 2: ...e Max 5amp 1 6hp of the circulating pump if it is connected directly to the boiler A higher capacity cable an breaker could be required In all cases the local Electrical Code has priority Can be connected to a 208Vac 1ph electrical supply The resulting capacity will be of 75 of the nominal capacity at 240V and the amperage will be of 87 Dimensions Connections Overall dimensions Inlet heating retur...

Page 3: ... in the absence of local codes with the National Plumbing Code and the National Electric Code current edition In any case where instructions in this manual differ from local or national codes the local or national codes take precedence SECURITY CONSIDERATIONS All installations have a maximum design operating pressure limited to 30 psi 207kPa by a safety relief valve Boiler operating temperature ra...

Page 4: ...age of the tank or water connections will result in damage to the adjacent area or to lower floors of the structure When such areas cannot be avoided a suitable drain pan or non flammable catch pan adequately drained and must be installed under the boiler The pan must be connected to a drain NOTE Auxiliary catch pan MUST conform to local codes The boiler can be mounted directly on a wall with adeq...

Page 5: ...ocation in case of discharge The piping diameter used for the discharge piping shall not be smaller than that of the valve outlet No valve of any type restriction or reducer coupling should be installed on the discharge line Local codes shall govern the installation of relief valves Expansion tank The expansion tank must be able to store the required volume of boiler water during maximum design op...

Page 6: ...t allows the unit to be drained for the eventual replacement of a defective component Strainer This component is used to collect potential sediments coming from the distribution system and more particularly from systems made of steel piping and radiators If such sediments accumulate at the bottom of the boiler it could be harmful to the heat transfer of the elements and generate premature failures...

Page 7: ...ceed 5A 1 6HP Multiple pumps zoning applications Components shall be connected in such a way that when a thermostat is calling for heat only the corresponding pump be operated and an auxiliary contact X X closes to give the signal of the heat demand to the boiler otherwise the elements will not be working To do so you will need relays as illustrated below Boiler terminals PP will not be used N B D...

Page 8: ...BTH Electric Boilers USE CARE MANUAL Revision June 2014 Page 8 ...

Page 9: ... The electronic control uses an LCD display to make all adjustments and to visualize the operation of the system OPERATION OF THE INTERFACE The controller uses four push buttons at the bottom of the display to select and adjust the parameters The button is used to access to the configuration menu and confirm a selection The buttons are used to select an item or adjust a value The button enables th...

Page 10: ...alculated by the controller in relation to the parameters selected in the menu and the maximum target temperature required when the outdoor temperature will get to 10F 23C The STD curve corresponds to the default maximum temperature for a typical system and this value can be modified from the MIN to MAX value shown on the following tables The following tables show the values of the target temperat...

Page 11: ...pplies heat to a lodger Systems connected to a geothermic heat pump where we do not want the electric boiler to be operating unless the outdoor temperature drops to a selected degree CONFIGURATION OF THE CONTROLLER Since each type of heating distribution system is designed to operate at water temperatures that are particular to its operation the proper configuration of the operating parameters of ...

Page 12: ... period that the pump will be running once the heat demand is completed Select OFF if the heat system is equipped with electric zone valves OFF 15 sec to 60min ON 30sec Select the outdoor temperature at which no heating of the building is required the outdoor sensor has to be installed 0F à 105F 75F Note1 Once these parameters have been set the controller will automatically return to its normal vi...

Page 13: ...TURE The controller will engage the Boost program when the heat demand on terminals W R has been maintained for a pre determined period according to the type of selected application Once this period has been reached the Boost icon will appear on the display and the boiler target temperature will start increasing very slowly over a pre determined period and up to a pre calculated maximum value unti...

Page 14: ...erminals of the boiler it can be activated by selecting ON in the configuration menu after having pressed for 2 seconds Adjust the UltraSmart boiler temperature controller as explained earlier and set the purge delay of the pump from On to its normal operation setting Set the room thermostat ON to generate a heat demand The pump shall start The heating elements shall gradually come on and the boil...

Page 15: ...outlet of this valve if a dripping condition occurs Twice a year Check for the proper operation of the automatic air purger s and eliminate air from the radiators Annually It is recommended that a visual inspection be made on the electrical compartments of the boiler to check the water tightness of the gasket on the element flange and also check for any signs of overheating of the components and w...

Page 16: ... the unit is not in short or open circuit Do not install a jumper between S1 S1 when the sensor is not required Check the resistance value ohms of the sensor It should correspond to the value shown on the table below otherwise it should be replaced Check for proper connection of the wires inside the boiler connected to S1S1 and at the controller terminals The display shows Er2 and blinks The contr...

Page 17: ...ipator If available to obtain longer operating cycles Replace defective elements If a boiler water temperature higher is required to satisfy the heat demands of the thermostats a boiler having a larger capacity is required Boiler stays in demand even when the thermostat is not in demand Systems with more than one thermostat On systems with electric zone valves one or many end switches included in ...

Page 18: ...rranty is void and shall not apply if 1 Defects or malfunctions resulting from installation repair maintenance and or usage that are not done in conformity with the manufacturer s installation manual or 2 Defects or malfunctions resulting from installation maintenance or repair that are not done in accordance with regulations in force or 3 Defects or malfunctions resulting from improper installati...

Reviews: