25
ENGLISH
DEFAULT PARAMETER SETTINGS TABLE
Menu
Parameter
Setting range
Default
User setting
4. SETTINGS
4.1
Tset
30°C ÷ 90°C
45°C
4.2
Tmax
50°C ÷ 95°C
60°C
4.3
VFS type
1-12 l/min, 1-20 l/min,
2-40l /min, 5-100 l/min,
10-200 l/min, 20-400l /min
2-40 l/min
4.4.1
Recirculation
Request / Periods /
Periods /
Always on
Periods
4.4.2
Tmin recirculation
10°C ÷ 85°C
35°C
4.4.3
Recirculation hysteresis
1K ÷ 20K
5K
4.4.4
Maximum recirculation flow
1 ÷ 50 l/min
15 l/min
4.4.5
Recirculation periods
00:00 ÷ 23:59
06:00 ÷ 20:00
4.4.6
Draw-off support
On / Off
On
4.4.7
Minimum storage temperature
0÷80°C
65°C
4.11
Comfort
On / Off
Off
5. PROTECTIVE FUNCTIONS
5.1
Anti-legionella
On / Off
Off
5.2
Limescale protection
On / Off
Off
5.3
Setpoint auto-regulation
On / Off
Off
5.4
Seizing protection
Daily / Weekly / Off
Off
6. SPECIAL FUNCTIONS
6.1.1
Pump type
0-10V / PWM
PWM
6.1.2
Pump
Solar / Heating
Profile 1-11 / Manual
Heating
6.1.3
Output signal
Normal / inverted
inverted
6.1.4
PWM off
Solar 0 to 50%
Heating 50 to 100%
Off 98%
6.1.5
PWM on
Solar 0 to 50%
Heating 50 to 100%
On 87%
6.1.6
PWM Max
Solar 0 to 50%
Heating 50 to 100%
Max 7%
6.2.1
Max speed
70 ÷ 100%
100%
6.2.2
Min speed
10 ÷ 95%
10%
6.5
Relay1
Always On / Off
Off
6.5.2.1
Thermostat
On / Off
On
6.5.2.2
Storage T min
10-85 °C
50 °C
6.5.2.3
Storage T set
45-95 °C
60 °C
6.5.2.4
Hysteresis
1-30 °C
5 °C
6.5.2.5
Thermostat period
00:00 - 23:59
06:00 - 20:00
6.6
Relay2 Recirculation
On / Off
Off
6.9
Pressure control
On / off
Off
6.9.2
RPS1/RPS2
Off / 0-0,6 bar / 0-1 bar /
0-1,6 bar / 0-2,5 bar /
0-4 bar / 0-6 bar / 0-10 bar
6.9.3
Pmin
Off / 0.0 to 1.6 bar
-
6.9.4
Pmax
Off / 0.0 to 10 bar
-
6.14
Daylight saving time
Yes / No
Yes
6.15
Sleep mode
On / Off
On
7. MENU LOCK
7.1
Menu lock
On / Off
Off
7.2
Expert mode
Simple / Expert
Expert