4
WATER CIRCUIT
TECHNICAL SPECIFICATIONS
EAF
5
9
4
6
6
3
2
1
1
10
1
8
7
8
1 Valve with temperature sensor
2 Modulating pump
3 Heat exchanger
4 Flow meter
5 Valve with temperature sensor
6 Non-return valve
7 Manual bleed valve
8 Manual drain valve
9 Recirculation pump (accessory kit)
10 Safety valve
DESCRIPTION
ACS 40 E
Thermal power absorbed with storage cylinder at 50°C and DHW water delivery at 10-45°C
72
kW
Water draw at 10-45°C with storage cylinder at 50°C
29,5
l/min
Thermal power absorbed with storage cylinder at 55°C and DHW water delivery at 10-45°C
94,0
kW
Water draw at 10-45°C with storage cylinder at 55°C
38.5
l/min
Thermal power absorbed with storage cylinder at 60°C and DHW water delivery at 10-40°C
92
kW
Water draw at 10-40°C with storage cylinder at 60°C
44
l/min
Maximum flow-rate primary
1850
l/h
Minimum permissible temperature, DHW circuit
2
°C
Maximum operating temperature
90
°C
Maximum operating pressure, primary circuit
10
bar
Opening pressure, primary circuit non-return valves
28
mbar
Opening pressure, DHW circuit non-return valves
28
mbar
Consumption
47
W
Power supply voltage
230
V
Power supply frequency
50-60
Hz
Index of protection
40
IP
Net weight
19,2
kg
Water capacity
6,6
l