ELECTRICAL CONNECTIONS

The following instructions are mandatory.

1  Use a multi-pole, magnetic thermal, earth leakage breaker and disconnector that conforms to legislation in the count-

ry of installation.

2  Respect the L (Phase) - N (Neutral) polarity. Keep the ground wire about 2 cm longer than the power wires.

3  Make sure the product is correctly connected to ground.

 

a

It is strictly forbidden to use water pipes to ground the product.

 

a

Do not route the power cable near hot surfaces (like hot water pipes). Use a suitable class of cable if there is any 

possibility of contact with parts at temperatures above 50°C.

 

b

The manufacturer declines all responsibility for damage caused by failing to ground the product adequately or by 

failure to respect the wiring diagrams provided in this manual.

FILLING PROCEDURE, PRIMARY CIRCUIT

 

b

Fill and bleed the primary circuit with the water at ambient temperature.

 - Open the primary circuit inlet and outlet ball valves.

 - Set the controller for operation in manual mode (see parameter 3.2).

 - Switch on the primary circuit pump.

 - Open the vent valve.

 - Pump water around the circuit until all air bubbles have been eliminated.

 - Close the vent valve.

 - Set the controller for operation in automatic mode (see parameter 3.1).

PUTTING INTO SERVICE

 

b

CAUTION!

 Completely fill the water circuit before putting the product into service.

 - Check that the non-return valves are in the right position.

 - Fill and bleed the primary circuit.

 - Fill the secondary (DHW) circuit.

 - Check that the mixer is water-tight.

 - Power on the mixer.

 - Check that the system works correctly.

 

b

All fittings are assembled in the factory. It is nevertheless advisable to check their tightness after installing the pro-

duct. It is also necessary to test the product for water tightness at operating pressure when putting it into service.

Summary of Contents for MODEX ACS 40 E

Page 1: ...WORK ON THE PRODUCT The manufacturer reserves the right to modify the product without notice for the purpose of introducing technical im provements or to facilitate production installation and positio...

Page 2: ...h leakage breaker in accordance with appli cable standards Correct functioning is only guaranteed provided the product is used with the pump for which it is designed The manufacturer cannot be held re...

Page 3: ...e with temperature sensor primary outlet 5 Pump primary circuit 6 Ball valves DN 20 3 4 F 1 M secondary circuit 7 Red knob for ball valve DHW outlet 8 Blue knob for ball valve cold water inlet 9 Non r...

Page 4: ...orage cylinder at 55 C and DHW water delivery at 10 45 C 94 0 kW Water draw at 10 45 C with storage cylinder at 55 C 38 5 l min Thermal power absorbed with storage cylinder at 60 C and DHW water deliv...

Page 5: ...M1 1283 75PWM1 800 85PWM1 p kPa H m P1 W Q m h Q l s Q Igpm Q m h max m ax Wilo Yonos Para RS 15 7 0 20 7 0 25 6 30 7 0 1 230 V Rp1 2 Rp3 4 Rp1 Rp1 1 4 n 1 min PWM 1 45 40 40 45 50 55 60 65 70 75 80 8...

Page 6: ...MP RS RP EAFS UACS 480 100 80 75 55 45 225 840 ACS 40 E MP Primary inlet 1 M 3 4 F RP Primary outlet return 1 M 3 4 F EAFS Domestic cold water inlet 1 M 3 4 F UACS DHW outlet 1 M 3 4 F RS Recirculati...

Page 7: ...G DIAGRAM S5 S4 LATO SONDE E CONTROLLO LATO ALIMENTAZIONE 230 V SENSOR AND CONTROL TERMINALS 230 V POWER TERMINALS S4 Storage cylinder top sensor S5 Storage cylinder bottom sensor Connect to controlle...

Page 8: ...The manufacturer s responsibility ends with the supply of the product The product must be installed in conformity to applicable standards by suitably qualified persons employed by a company that assum...

Page 9: ...rage cylinder in order to avoid unnecessary heat loss from the connecting pipes b b Handle with care Remove the product from its packaging and remove the polypropylene cover Drill the wall at the posi...

Page 10: ...iency of the water heating system The ACS 40 E hot water mixer is made from materials that conform to the requirements of Ministerial Decree 174 2004 Italy implementing Council Directive 98 83 EC All...

Page 11: ...ROCEDURE PRIMARY CIRCUIT b b Fill and bleed the primary circuit with the water at ambient temperature Open the primary circuit inlet and outlet ball valves Set the controller for operation in manual m...

Page 12: ...d by the technician and by the user of the system before installing setting and operating the controller All accident prevention directives IEC standards local power utility regulations pertinent EN s...

Page 13: ...nces dispose of the controller with ordinary household refuse Dispose of the controller only at designated collection points or return it to the dealer or manufacturer TECHNICAL SPECIFICATIONS Electri...

Page 14: ...AN CAN VFS2 VFS1 V2 S6 Control circuit max 12 VAC DC Terminal Connection for S1 Recirculation optional S2 Cold water S3 Primary circuit flow rate optional S4 Top of storage cylinder S5 V1 PWM signal p...

Page 15: ...s of key functions increase decrease values scroll menu up down yes no confirm cancel Info additional information Back return to previous screen ok confirm selection Confirm confirm setting Finally ac...

Page 16: ...ure measured is the temperature at the outlet of the heat exchanger which could differ from that measured at the taps Small fluctuations in temperature at the taps are compensated generally by mixing...

Page 17: ...it settings 4 1 Tset The MFWC controller maintains a constant recirculation temperature by controlling the speed of the hot water pump 4 2 Tmax Maximum draw off temperature at the vor tex flow sensor...

Page 18: ...es the return to the centre or bottom of the storage cylinder on the basis of temperature This menu sets the temperature differential between the return and the storage cylinder If return temperature...

Page 19: ...is no lower than 0 C and no higher than the Tmin recirculation setpoint Settings range On Off Default see table 5 4 Seizing protection If seizing protection is active the controller switches on the re...

Page 20: ...lt setting for Relay 1 is Always on The default setting for Relay 2 is Recirculation Bear in mind that recirculation settings only appear in the settings menu if the recirculation function is activate...

Page 21: ...l high efficiency pump If a pump function is ac tivated e g recirculation solar additional pump etc the additional settings and speed control for pump V2 must also be set See the technical specificati...

Page 22: ...nction is active the clock updates automatically when Daylight Saving Time DST commences and finishes 6 15 Sleep mode When sleep mode is selected the display goes blank after two minutes of inactivity...

Page 23: ...rs etc 9 LANGUAGE Menu 9 Language can be used to select the language in which menus are displayed and navigated Selection is prompted automatically at start up The choice of languages may differ depen...

Page 24: ...se limescale to form in the heat exchanger REPLACING THE FUSE b b Repairs and maintenance must be entrusted exclu sively to an expert service technician Disconnect the controller from the electricity...

Page 25: ...g protection Daily Weekly Off Off 6 SPECIAL FUNCTIONS 6 1 1 Pump type 0 10V PWM PWM 6 1 2 Pump Solar Heating Profile 1 11 Manual Heating 6 1 3 Output signal Normal inverted inverted 6 1 4 PWM off Sola...

Page 26: ...the checks listed in the table below DESCRIPTION OK All automatic or manual filling pumps removed Safety valve calibrated to 6 bar and flow open Drain pipe from safety valve routed suitably Expansion...

Page 27: ......

Page 28: ...Legnago VR www thermital it The manufacturer strives to continuously improve all products Appearance dimensions technical specifications standard equipment and accessories are therefore liable to modi...

Reviews: