13
ENGLISH
- The manufacturer’s name plate and other factory marks applied to the controller must not be altered, removed or made
illegible.
- Only the settings described in these instructions are able to guarantee the correct operation of the controller.
ABOUT THE CONTROLLER
The MFWC controller enables efficient use and operational control of the mixer system. For each of the single setting
procedures, the keys are assigned to specific functions and explained.
The controller menu contains key words for the measured values and settings, as well as help texts and graphs.
Main features of the MFWC controller:
- Backlit display showing text and graphic content
- Simple viewing of current measurement values
- Analysis and monitoring of the system by means of statistical graphs, etc.
- Extensive setting menus with explanations
- Menu lock: activated to prevent unintentional alteration of settings
- Function allowing restoration of previously selected values or factory settings
- Wide range of additional functions.
DISPOSAL
The controller conforms to the European RoHS directive 2002/95/EC regarding restrictions on the use of certain hazar-
dous substances in electrical and electronic equipment.
b
Never under any circumstances dispose of the controller with ordinary household refuse. Dispose of the controller
only at designated collection points or return it to the dealer or manufacturer.
TECHNICAL SPECIFICATIONS
Electrical specifications
Voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100-230VAC
Frequency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50 - 60Hz
Consumption . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0.5W – 2.5W
- electromechanical relays R1-R3 . . . . . . . . . . . . . . . . . . . . . . . . 460VA for AC1 / 460W for AC3
- PMV output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . for 10 kΩ load
Internal fuse . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . T2A / 250V slow-blow
Ingress protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . IP40
Protection class . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . II
Sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 x 2 x VFS (vortex flow sensors)
Measuring range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . PT 1000 -40°C up to 300°C
Vortex flow sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0°C to 100°C (-25°C /120°C short term)
1 l/min - 12 l/min (VFS1-12) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0-0.6 bar
1 l/min – 20 l/min (VFS1-20) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0-1 bar
2 l/min - 40 l/min (VFS2-40) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0-1.6 bar
5 l/min - 100 l/min (VFS5-100) . . . . . . . . . . . . . . . . . . . . . . . . . . . 0-2.5 bar
10 l/min – 200 l/min (VFS10-200) . . . . . . . . . . . . . . . . . . . . . . . . . 0-4 bar
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0-6 bar
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0-10 bar
Permissible ambient conditions
Ambient temperature:
- for controller operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0°C÷40°C
- for transport/storage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0°C÷60°C
Air humidity:
- for controller operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . max. 85% relative humidity at 25 °C
- for transport/storage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . no moisture condensation permitted
Other specifications and dimensions
Housing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-part, ABS plastic
Overall dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 163mm x110mm x 52mm
Installation aperture dimen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 157mm x 106mm x 31mm
Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Full graphic display, 128 x 128 pixels
LED . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Multicolour red/green
Programming . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 entry keys
Temperature resistance table for Pt1000 sensors
°C
0
10
20
30
40
50
60
70
80
90
100
Ω
1000
1039
1077
1116
1155
1194
1232
1270
1308
1347
1385
Summary of Contents for MODEX ACS 40 E