23
SYSTEM MANAGER
ENGLISH
START-UP
Have
THERMITAL
’s Technical Assistance Service start-up your boiler for the first time. Once this has been done, the
boiler can be left to function automatically. Under certain circumstances, such as after long periods of disuse, the user
may need to re-start it without involving the Technical Assistance Service. Before doing so, perform the following checks
and operations:
- Check that the fuel cock and heating system water
cock are shut.
- While the system is still cold, check that the pressure
(1) in the heating circuit is
over 1 bar
but below the
maximum limit specified for the boiler. If water pressu-
re is low, contact
THERMITAL
’s Technical Assistance
Service.
- Switch the electricity supply ON at the system’s main
switch and at the control panel.
Check that the display comes on.
- When the boiler is first powered on, it performs a num-
ber of self-tests. These may take a few minutes. When
the tests are completed, the display reads out boiler
temperature.
Perform the following operations on the boiler control
panel.
- Press the "
OK
" button.
Select "
Operator unit
" and press "
OK
".
Select "
Language
" and press "
OK
".
Set the language you want.
Boiler temperature
Time of day and date
Operator unit
ON
OFF
1
SECTION RESERVED FOR SYSTEM MANAGER (ONLY FOR THC V 55 E OIL BLU MODEL)
SYSTEM MANAGER