43
INSTALLER
ENGLISH
Residual pressure
THC V
35 E OIL BLU
55 E OIL BLU
Maximum residual pressure in flue
gas vent (*)
Pa
50
75
(*) Values referred to atmospheric pressure at sea level.
Maximum equivalent length of pipes
THC V
35 E OIL BLU
55 E OIL BLU
Category
Flue Ø
(mm)
Maximum length of flue pipe (m) (*)
open
B23 - B23P
80
10
10
twin flue pipes
C63
80
10+10
10+10
concentric flue pipes
C13 - C33
80/125
6
6
(*) These length must be reduced by 3 metres for every 90° curve and by 1.5 metres for every 45° curve.
b
All flue seals must be made from condensate (acid)
resistant materials.
THERMITAL THC V E OIL BLU
boilers can also be
installed in B23 open configurations using suitable
piping in compliance with applicable laws and stan-
dards.
b
Even if the flue pipes pass through combustible
walls, it is not necessary to respect a minimum
installation distance (between the flue and the
walls), since flue gas temperature is below the
maximum permitted temperature for the flue pipes
(according to EN 15035). You should nevertheless
always respect the specifications given in the tech-
nical data sheets for the materials used in the walls.
THERMITAL THC V E OIL BLU
boilers derive their
comburent air from the room in which they are installed.
Suitable air vents must therefore be provided in com-
pliance with applicable laws and standards.
a
Never obstruct or restrict the air vents in the room
where the appliance is installed.