36
INSTALLER
ENGLISH
DRAINING THE CONDENSATE
ELECTRICAL CONNECTIONS
b
Always maintain a slope “i” of over 3° and ensure
that the diameter of the condensate drain hose is
always greater that of the drain fitting on the boiler .
b
Check and clean the condensate drain siphon and
pipes at least once a year, as instructed in “Cleaning
the condensate drain siphon” section.
b
The connection to the waste water drain pit must be
made in compliance with national and local legislation
and standards.
b
Condensate from the boiler and that from the flue
stack should be channelled to the same drain pit .
b
The surface on which the boiler stands must be per-
fectly horizontal and flat over the entire area of the
boiler frame in order to avoid condensate drainage
problems.
b
Any condensate neutralisation units deemed neces-
sary may be connected downstream from the siphon.
Evaluate the neutralisation unit after one year of opera-
tion to estimate the duration of the neutralisation char-
ge. The total duration of the charge can be estimated
from the level after one year.
b
It is mandatory to use a condensate trap (see the
THERMITAL
catalogue).
i
i
≥
3°
BOILER
Drain
Condensate from stack
Condensate
from boiler
To drain or
neutralisation
unit if installed
Flue
THC V E OIL BLU
condensing boilers are fully wired in
the factory. Only the following electrical connections re-
main to be made:
- Power supply
- Outside sensor
- Room unit (not supplied)
- The automatic shut-off device (not supplied; only where
required; see also the “Fuel connections” section)
- CH circuit pump and/or other components not supplied
with the boiler.
1