5.1 Handling the product
Cortina is a heavy product, and care should be taken when carrying the boiler to the room where it
is going to be installed. The total weight of each boiler is indicated in technical data section.
Carrying equipment of the product must be of enough capacity to support that weight. To avoid
damage during transport, boiler should be moved with forklift or transpalet. Use the transport
feets on the wooden pallets.
NOTICE
Damage to property
•
Do not use hard and sharp objects while removing the package around the
boiler to prevent damage of the painted jackets.
5.2 Room selection
Cortina series boilers must be installed in an individual boiler room particularly organized for
heating. The boiler room should be of enough volume for installation, firing, and maintenance of
the boiler. There should be enough space from the wall for easy removing the geared motor and
the shaft for service intervention. For appropriate dimensions look into “clearances around boiler”
section.
There should be enough fresh air circulation for combustion, the chimney design must ensure an
adequate draught for related boiler type, and must comply with construction criteria given further
in this manual and in mandatory regulations. Your boiler must never be installed in open spaces or
balconies, in spaces occupied by people like kitchen, living room, bathroom and bedroom, in
spaces where there are explosive and combustible materials.
The boiler room should have air ventilation holes through outside to let fresh air in. One air
ventilation hole must be built maximum 40 cm below the level of room ceiling; the other must be
built maximum 50 cm above the floor level. These ventilation holes should always be kept open.
The upper hole should be at least 40x40 cm in size, the lower hole at least 30x30 cm.
All hydraulic and electrical circuits must be arranged by authorized staff in accordance with
mandatory regulations specified by legal organizations.
Pellets should be stored by keeping minimum 800 mm distance from the boiler. We recommend
you to keep the solid fuel in another room.
Cortina boiler should be installed on a concrete plinth made of a fireproof material. For minimum
sizes of the plinth following table should be referred:
Model
Cortina 12/18 / 24
Cortina 32 / 40
Plinth height (mm)
50
Plinth width (mm)
800
900