AUTO-CUT 300 XT
3-�
INSTALLATION
Manual 0-5300
C. Creating An Earth Ground
1. To create a solid, low resistance, earth ground, drive a 1/2 in (12 mm) or greater diameter copper clad ground
rod at least 6 - 8 ft (1.8 - 2.4 m) into the earth so that the rod contacts moist soil over most of its length. Depend
-
ing on location, a greater depth may be required to obtain a low resistance ground (see NOTE). Ground rods,
typically 10 ft (3.0 m) long, may be welded end to end for greater lengths. Locate the rod as close as possible to
the work table. Install a ground wire, 1/0 AWG (European 50 mm2) or greater, between the ground rod and the
star ground point on the cutting table.
NOTE!
Ideally, a properly installed ground rod will have a resistance of
three ohms or less.
D. Low Cost Ground Rod Tester
1. A key component of reduced EMI is a good low resistance earth ground rod. There are several very expensive
instruments to measure the ground but cost from several hundred to a few thousand dollars. Below is a low
cost alternative which can be constructed by qualified personnel familiar with established electrical construction
and safety practices. Previously suggested method using an incandescent light bulb will not work with GFCI
outlets which are increasingly being used and the bulbs are becoming obsolete.
2. This method, as well as the light bulb method and some of the expensive instruments, assumes the utility ground
is perfect, Zero ohms. It connects the rod being tested in series with the utility ground and measures the resis
-
tance of both in series. If the utility ground is not zero ohms, no matter how good your rod is, you won’t get a
low reading due the higher resistance of the utility ground. Fortunately this is rare. Also if your rod is right next
to another earth grounded structure you may get a false lower reading of only resistance between that structure
and your rod rather than to gnd.
NOTE!
In the United States most standard AC outlets are 120 VAC 60 Hz.
Elsewhere most outlets are 220 VAC 50Hz.
3. Obtain a transformer rated for at least 25 VA with primary voltage and frequency matching your standard outlets.
The transformer should have an isolated secondary of either 220 VAC (220 -240 is OK) or 120 VAC (110-120 is
OK) and be rated for at least 100 ma. The transformer could also have dual 115VAC primaries wired in series
for 220V or in parallel for 120 VAC. An example is Triad N-68X, shown below, rated 50VA, 50/60 Hz.
Obtain a power resistor of either 1200 (1.2K) ohms, 15-25W min, if using a 120V secondary or 2200 (2.2K) ohms,
25 -30W for a 220V secondary.
4. Assemble the transformer and power resistor in a metal box. Connect a 3 wire (w/gnd) power cord with ground
wire attached to the metal box for safety. If a plastic box is used instead, connect the transformer core and the
resistor mounts to the power cord ground wire. There should be a fuse ¼ - ½ A, in series with the transformer
primary. From the transformer secondary connect one wire to the utility safety ground. This could be the cutting
table frame, the ground terminal of the 120 or 220 VAC outlet or the test box if grounded as indicated.
An excellent ground measures 1 ohm or less. Up to 3 ohms is often acceptable, higher reduces the effectiveness
of the EMI suppression.
Summary of Contents for AUTO-CUT 300 XT
Page 6: ...This Page Intentionally Blank...
Page 13: ...AUTO CUT 300 XT Manual 0 5300 SAFETY INSTRUCTIONS 1 5 This Page Intentionally Blank...
Page 52: ...This Page Intentionally Blank...
Page 105: ...AUTO CUT 300 XT Manual 0 5300 APPENDIX A 19 Display PCB Test Points TP1 GND TP2 5VDC TP3 24VDC...
Page 114: ...AUTO CUT 300 XT APPENDIX Manual 0 5300 APPENDIX 11 Cap Bias Bottom PCB Layout Art A 11685_AB...
Page 115: ...AUTO CUT 300 XT Manual 0 5300 APPENDIX A 29 APPENDIX 12 Cap Bias Top PCB Layout Art A 11686_AB...
Page 116: ...AUTO CUT 300 XT APPENDIX Manual 0 5300 APPENDIX 13 Suppressor PCB Layout Art A 11684_AB...
Page 161: ......