background image

6

www.thermastor.com • [email protected]

Toll-Free 1-800-533-7533

5.  Rotate the blower outlet toward you as you remove it. 

Use care to avoid hooking wiring, tubing or electrical 
components.

6.  Reassembling with the new blower in the above 

procedure reversed.

4.6 Compressor/Capacitor Replacement

This compressor is equipped with a two terminal external 
overload, run capacitor, but no start capacitor or relay (see 
Fig. 3).

CAUTION-ELECTRICAL SHOCK HAZARD: Electrical power 
must be present to perform some tests; these tests should 
be performed by a qualified service person.

                  

4.6A Checking Compressor Motor Circuits

Perform the following tests if the blower runs but the 
compressor does not with the power switch ON.
.  Turn the power switch OFF and unplug the unit, remove 

top panel and the cabinet front (6 screws).

2.  Plug in the unit and turn the power switch ON. Use 

a voltmeter to check for 0 to 20 volts between 
(a) the relay terminal that the black wire from the 
compressor connects to and (b) the capacitor terminal 
with the 2 white wires & blue wire connected. If 
voltage is present, go to step 3. If no voltage, the 
low pressure control or relay are open or there is a 
loose connection in the compressor circuit. Test each 
component for continuity; see the appropriate section 
if a defect is suspected.

3.  Turn the power switch OFF and unplug the unit, then 

disconnect the red and yellow wires from compressor 
terminals R & S. Using an ohmmeter, check continuity 
between the points listed below.

4.  Compressor terminals C and S: No continuity indicates 

an open start winding; the compressor must be 
replaced. Normal start winding resistance 3 to 7 
ohms.

5.  Compressor terminals C and R: No continuity indicates 

an open run winding; the compressor must be 
replaced. Normal run winding resistance is .5 to 2 
ohms.

6.  Compressor terminal C and overload terminal : No 

continuity indicates a defective overload lead.

7.  Overload terminals  and 3: If there is no continuity, 

the overload may be tripped; wait 0 minutes and try 
again. If there is still no continuity, it is defective and 
must be replaced.

8.  Compressor terminal C and compressor case: 

Continuity indicates a grounded motor; the compressor 
must be replaced.

9.  Disconnect the wires from the capacitor. Set the 

ohmmeter to the Rx scale; the capacitor is shorted 
and must be replaced if continuity exists across its 
terminals. If there is no needle movement with the 
meter set on the Rx00000 scale, the capacitor is 
open and must be replaced.

0. Reconnect the wires to the compressor and capacitor; 

plug in and turn on the unit. If the compressor fails to 
start, replace the run capacitor.

. If the unit still does not start, adding a hard-start kit 

will provide greater starting torque. If this does not 
work, the compressor has an internal mechanical 
defect and must be replaced.

4.6B Replacing a Burned Out Compressor

The refrigerant and oil mixture in a compressor is 
chemically very stable under normal operating conditions. 
However, when an electrical short occurs in the 
compressor motor, the resulting high temperature arc 
causes a portion of the refrigerant oil mixture to break 
down into carbonaceous sludge, a very corrosive acid, 
and water. These contaminants must be carefully removed 
otherwise even small residues will attack replacement 
compressor motors and cause failures.
The following procedure is effective only if the system is 
monitored after replacing the compressor to insure that 
the clean up was complete.
.  This procedure assumes that the previously listed 

compressor motor circuit tests revealed a shorted or 
open winding. If so, cautiously smell the refrigerant 
from the compressor service port for the acid odor of 
a burn out. 

WARNING: The gas could be toxic and highly acidic. If no 
acid odor is present, skip down to the section on changing 
a non-burn out compressor.

2.  Remove and properly dispose of the system charge. 

DO NOT vent the refrigerant or allow it to contact your 
eyes or skin.

3.  Remove the burned out compressor. Use rubber gloves 

if there is any possibility of coming in contact with the 
oil or sludge.

4.  To facilitate subsequent steps, determine the type of 

burn out that occurred. If the discharge line shows no 
evidence of sludge and the suction line is also clean 
or perhaps has some light carbon deposits, the burn 
out occurred while the compressor was not rotating. 
Contaminants are therefore largely confined to the 
compressor housing. A single installation of liquid 
and suction line filter/driers will probably clean up the 
system.

Summary of Contents for Phoenix 200 MAX

Page 1: ...s for drying areas to much lower humidity levels than conventional dehumidifiers The Phoenix 200 MAX an improved version of the original Phoenix 200 is the culmination of over a decade of LGR manufact...

Page 2: ...e used INDOORS ONLY If used in a wet area plug it into a GROUND FAULT INTERRUPTER DO NOT use the Phoenix 200 MAX as a bench or table It must always be used in the upright position Read the operation a...

Page 3: ...ft in the condensate pump reservoir for moving or storage Pressing and holding the pump purge switch will cause the condensate pump to run Hold the switch in until the flow from the condensate hose st...

Page 4: ...ain it completely Walk under out of the hose to open end If the unit will not be exposed to freezing temperatures an alternative to reduce biological growth is to flush the unit with a bio fungicide t...

Page 5: ...r but not as much as expected 1 Air temperature and or humidity have dropped 2 Humidity meter and or thermometer used are out of calibration 3 Unit has entered defrost cycle Sec 2 9 4 7 4 Air filter d...

Page 6: ...motor the compressor must be replaced 9 Disconnect the wires from the capacitor Set the ohmmeter to the Rx1 scale the capacitor is shorted and must be replaced if continuity exists across its terminal...

Page 7: ...tween the accumulator and compressor If the low side refrigerant temperature drops due to excessive frost formation on the evaporator coil the thermostat opens The compressor is then cycled off and on...

Page 8: ...www thermastor com sales thermastor com Toll Free 1 800 533 7533 Figure 3 Electrical schematic of 200 MAX 5 Wiring Diagram...

Page 9: ...1 Filter Drier 11 4024073 2 Foot 12 4026094 1 Handle Assembly 13 4021597 1 Hour Meter 14 4024918 1 Instruction Label 15 4022219 1 Low Pressure Control 16 4021796 1 Pump Purge Switch 17 4021822 1 Power...

Page 10: ...10 www thermastor com sales thermastor com Toll Free 1 800 533 7533 This page intentionally left blank...

Page 11: ...rmal care This warranty does not cover any defect malfunction etc resulting from misuse abuse lack of normal care corrosion freezing tampering modification unauthorized or improper repair or installat...

Reviews: