background image

4

www.thermastor.com • [email protected]

Toll-Free 1-800-533-7533

2.10 Low Pressure Control

If the low side refrigerant pressure drops to 5 PSIG, the 
low pressure control opens and shuts off the compressor 
and blower. It is an automatically reset control. Its primary 
function is to prevent damage to the compressor if a leak 
develops in the refrigeration system. It may also open if 
the unit is A) used in a cool area (below 50°F) and the 
defrost timer is not adjusted (see Sec. 2.9) or B) stored 
where it is below 40°F and then started. Under these 
conditions, the unit will restart within several minutes; it 
may cycle several times until the unit warms up.

3 Maintenance

3.1 Air Filter

The Phoenix 200 MAX is equipped with a pleated fabric air 
filter that must be checked regularly. The standard filter 
is a MERV- high efficiency filter. Operating the unit with 
a dirty filter will reduce the dehumidifier’s capacity and 
efficiency and may cause the compressor to cycle off and 
on unnecessarily on the defrost control.
The filter can generally be vacuumed clean several times 
before needing replacement. Replacement filters can be 
ordered from the factory or purchased locally if available. 
DO NOT operate the unit without the filter or with a less 
effective filter as the heat exchange coils inside the unit 
could become clogged and require disassembly to clean.

3.2 Storage

There are two issues to consider when the Phoenix 200 
MAX is stored between uses and both pertain to the 
water trapped in the unit: damage caused by freezing or 
biological growth. The effect of the trapped water can be 
greatly reduced if precautions are taken to remove as 
much as possible before storage.
.  Use the pump purge switch (see Sec. 2.7 & Fig. 4) to 

reduce the water level in the reservoir.

2.  Stretch the hose flat to drain it completely. Walk under 

out of the hose to open end.

If the unit will not be exposed to freezing temperatures, an 
alternative to reduce biological growth is to flush the unit 
with a bio-fungicide that is approved for use with copper, 
aluminum and polyethylene. To flush:
.  Run the hose to a drain.
2.  Plug in the unit but do not turn it on.
3.  Remove the air filter. Slowly pour a quart of the 

chemical through the heat exchanger

4.  Hold in the pump purge switch to reduce the water 

level in the reservoir.

5.  Flush with water.

4 Service

CAUTION: Servicing the Phoenix 200 MAX with its high 
pressure refrigerant system and high voltage circuitry 
presents a health hazard which could result in death, 
serious bodily injury, and/or property damage. Only 
qualified service people should service this unit.

4.1 Warranty

A warranty certificate has been enclosed with this unit; 
read it before any repair is initiated. If a warranty repair 
is required, call the factory first at -800-533-7533 for 
warranty claim authorization and technical assistance.

4.2 Technical Description

The Phoenix 200 MAX uses a refrigeration system similar 
to an air conditioner’s to remove heat and moisture from 
incoming air, and to add heat to the air that is discharged 
(see Fig. 2).

Hot, high pressure refrigerant gas is routed from the 
compressor to the condenser coil (see Figure 2). The 
refrigerant is cooled and condensed by giving up its heat 
to the air that is about to be discharged from the unit. 
The refrigerant liquid then passes through a filter/drier 
and capillary tubing which cause the refrigerant pressure 
and temperature to drop. It next enters the evaporator 
coil where it absorbs heat from the incoming air and 
evaporates.
The evaporator operates in a flooded condition, which 
means that all the evaporator tubes contain liquid 
refrigerant during normal operation. A flooded evaporator 
should maintain constant pressure and temperature 
across the entire coil, from inlet to outlet.

Figure 2: Refrigeration system of Phoenix

Summary of Contents for Phoenix 200 MAX

Page 1: ...s for drying areas to much lower humidity levels than conventional dehumidifiers The Phoenix 200 MAX an improved version of the original Phoenix 200 is the culmination of over a decade of LGR manufact...

Page 2: ...e used INDOORS ONLY If used in a wet area plug it into a GROUND FAULT INTERRUPTER DO NOT use the Phoenix 200 MAX as a bench or table It must always be used in the upright position Read the operation a...

Page 3: ...ft in the condensate pump reservoir for moving or storage Pressing and holding the pump purge switch will cause the condensate pump to run Hold the switch in until the flow from the condensate hose st...

Page 4: ...ain it completely Walk under out of the hose to open end If the unit will not be exposed to freezing temperatures an alternative to reduce biological growth is to flush the unit with a bio fungicide t...

Page 5: ...r but not as much as expected 1 Air temperature and or humidity have dropped 2 Humidity meter and or thermometer used are out of calibration 3 Unit has entered defrost cycle Sec 2 9 4 7 4 Air filter d...

Page 6: ...motor the compressor must be replaced 9 Disconnect the wires from the capacitor Set the ohmmeter to the Rx1 scale the capacitor is shorted and must be replaced if continuity exists across its terminal...

Page 7: ...tween the accumulator and compressor If the low side refrigerant temperature drops due to excessive frost formation on the evaporator coil the thermostat opens The compressor is then cycled off and on...

Page 8: ...www thermastor com sales thermastor com Toll Free 1 800 533 7533 Figure 3 Electrical schematic of 200 MAX 5 Wiring Diagram...

Page 9: ...1 Filter Drier 11 4024073 2 Foot 12 4026094 1 Handle Assembly 13 4021597 1 Hour Meter 14 4024918 1 Instruction Label 15 4022219 1 Low Pressure Control 16 4021796 1 Pump Purge Switch 17 4021822 1 Power...

Page 10: ...10 www thermastor com sales thermastor com Toll Free 1 800 533 7533 This page intentionally left blank...

Page 11: ...rmal care This warranty does not cover any defect malfunction etc resulting from misuse abuse lack of normal care corrosion freezing tampering modification unauthorized or improper repair or installat...

Reviews: