background image

3

www.thermastor.com • [email protected]

Toll-Free 1-800-533-7533

•  The air inlet on top & the side outlet must be at least  

 foot from walls and other obstructions to air flow.

•  If the humid area is very large, dehumidification can 

be improved by adding an outlet duct to circulate air to 
stagnant areas (see Sec. 2.5). 

2.3 Electrical Requirements

The Phoenix 200 MAX plugs into a common grounded 
outlet on a 5 Amp circuit. It draws 7.4 Amps at 80°F,  
60% RH. Amp draw increases with increasing temperature 
and\or humidity; e.g. 0.2 amps at 90°F, 85% RH. If used 
in a wet area, a ground fault interrupter (GFI) is required. 
If an extension cord is required, it must have a minimum of 
4 gauge conductors if 25 feet long or less and 2 gauge 
conductors if greater than 25 feet long.

2.4 Condensate Removal

The Phoenix 200 MAX is equipped with an internal 
condensate pump to remove the water that is condensed 
during dehumidification. This allows the condensate to be 
pumped 30’ with the attached hose. If the condensate 
must be pumped more than 20 feet above the unit, a 
second pump must be added to relay the condensate. If 
the pump fails and the unit must be used before it can be 
replaced, the condensate can be drained by gravity (see 
Sec. 4.9).

2.5 Ducting

A detachable rectangular exhaust collar is supplied 
that will allow 0” round lay-flat duct to be attached to 
the Phoenix 200 MAX outlet. Lay-flat plastic ducting is 
available from Therma-Stor.
To attach ducting to a collar, put the plastic duct end 
through the collar center and roll the duct end outward 
so that it overlaps the outside of the collar. The duct and 
collar may then be quickly attached to the Phoenix 200 
MAX by snapping the collar over the four screws at the 
blower outlet.

2.6 Power Switch

The power switch (right of hour meter) lights up when 
the unit is turned on. The unit will continue to run in 
all conditions until the switch is turned off; there is no 
dehumidistat. If the unit is going to run for more than 2 
hours in an area below 50°F, the defrost timer should be 
adjusted to improve performance (see Sec. 2.9).

 

2.7 Pump Purge Switch

This switch (left of hour meter) minimizes the water left 
in the condensate pump reservoir for moving or storage. 
Pressing and holding the pump purge switch will cause the 
condensate pump to run. Hold the switch in until the flow 
from the condensate hose stops.

2.8 Hour Meter

The digital hour meter measures the cumulative time that 
the unit is turned on to tenths of an hour. It stores its 
total when the unit is unplugged; the previous total will be 
displayed when the unit is next turned on. It resets to zero 
after 99,999.9 hours of operation.

2.9 Defrost Control Adjustment

When the Phoenix 200 MAX is used in a cool area, or the 
dewpoint is below 50°, frost will form on the cooling coil 
as it dehumidifies. When enough frost forms, the defrost 
thermostat will initiate the timed defrost cycle. The cycle 
periodically turns off the compressor while allowing the 
blower to run. The frost is melted by the air that the blower 
draws through the cooling coil.

DRYING TIP: Air’s ability to absorb moisture from wet 
surroundings and the Phoenix 200 MAX’s ability to remove 
moisture from that air is greatly improved at higher 
temperatures. We recommend that the area to be dried be 
heated to over 70°F if possible. Less drying time will be 
required and efficiency will improve.

The defrost cycle is automatic and designed for optimum 
performance above 50°F. If the unit is used in an area that 
is below 50°F for more than 2 hours, adjustment of the 
defrost timer is recommended. To adjust the defrost timer:
.  Unplug the unit.
2.  Remove the top panel and the front cover (6 screws).
3.  The timer is fastened to the base at the front of the 

unit. Every fourth peg around the dial is pushed out 
from the dial center except one section with 5 pegs 
out in a row. See figure . Each fourth “out” peg 
represents 5 minutes of compressor “off” time 
during every hour that the unit is in the defrost cycle.

4.  To improve performance below 50°F, the compressor 

“off” time must be increased to 30 minutes per hour 
to allow the frost to completely melt. To do this, push 
the pegs out from the dial center so that the pegs 
alternate with 2 toward the center, then 2 out from 
the center, all the way around the dial except for the 
section now with 6 pegs out in a row (see Fig. ).

 5.  Replace the cover and top panel.
Change the timer pegs back to the original pattern for use 
above 50°F.

Above 50° F

Below 50° F

Figure 1: Defrost 
timer adjustment

Summary of Contents for Phoenix 200 MAX

Page 1: ...s for drying areas to much lower humidity levels than conventional dehumidifiers The Phoenix 200 MAX an improved version of the original Phoenix 200 is the culmination of over a decade of LGR manufact...

Page 2: ...e used INDOORS ONLY If used in a wet area plug it into a GROUND FAULT INTERRUPTER DO NOT use the Phoenix 200 MAX as a bench or table It must always be used in the upright position Read the operation a...

Page 3: ...ft in the condensate pump reservoir for moving or storage Pressing and holding the pump purge switch will cause the condensate pump to run Hold the switch in until the flow from the condensate hose st...

Page 4: ...ain it completely Walk under out of the hose to open end If the unit will not be exposed to freezing temperatures an alternative to reduce biological growth is to flush the unit with a bio fungicide t...

Page 5: ...r but not as much as expected 1 Air temperature and or humidity have dropped 2 Humidity meter and or thermometer used are out of calibration 3 Unit has entered defrost cycle Sec 2 9 4 7 4 Air filter d...

Page 6: ...motor the compressor must be replaced 9 Disconnect the wires from the capacitor Set the ohmmeter to the Rx1 scale the capacitor is shorted and must be replaced if continuity exists across its terminal...

Page 7: ...tween the accumulator and compressor If the low side refrigerant temperature drops due to excessive frost formation on the evaporator coil the thermostat opens The compressor is then cycled off and on...

Page 8: ...www thermastor com sales thermastor com Toll Free 1 800 533 7533 Figure 3 Electrical schematic of 200 MAX 5 Wiring Diagram...

Page 9: ...1 Filter Drier 11 4024073 2 Foot 12 4026094 1 Handle Assembly 13 4021597 1 Hour Meter 14 4024918 1 Instruction Label 15 4022219 1 Low Pressure Control 16 4021796 1 Pump Purge Switch 17 4021822 1 Power...

Page 10: ...10 www thermastor com sales thermastor com Toll Free 1 800 533 7533 This page intentionally left blank...

Page 11: ...rmal care This warranty does not cover any defect malfunction etc resulting from misuse abuse lack of normal care corrosion freezing tampering modification unauthorized or improper repair or installat...

Reviews: