PD120 OWNERS MANUAL 

Drawing No.  :-  TPC325 
Issue 

:-  11 

Date 

:-  07/09/18

 

 
 
 
 
 
 
 
 
 

 

EBAC MODEL PD120 

INDUSTRIAL DEHUMIDIFIER 

OWNER’S MANUAL

 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 
 

Ebac Industrial Products, Inc. 

700 Thimble Shoals Blvd, Suite 109 

Newport News, VA. 23606-2575 

Tel: (757) 873 6800 Fax: (757) 873 3632  

Website www.ebacusa.com 

Summary of Contents for 1028200

Page 1: ...TPC325 Issue 11 Date 07 09 18 EBAC MODEL PD120 INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL Ebac Industrial Products Inc 700 Thimble Shoals Blvd Suite 109 Newport News VA 23606 2575 Tel 757 873 6800 Fax 757 873 3632 Website www ebacusa com ...

Page 2: ...11 Date 07 09 18 PD120 PD120 PD120 PD120 PACKAGE CONTENTS PACKAGE CONTENTS PACKAGE CONTENTS PACKAGE CONTENTS Item Description Quantity 1028200 Dehumidifier 1 3014338 PVC tube 12mm I D 3M 3086101 Jubilee clip 1 3035157 Humidistat 1 TPC325 Manual 1 ...

Page 3: ...aws the moist air through the cold evaporator coil which cools the air below its dew point Moisture forms on the evaporator coil and is collected in the condensate tray which is equipped with a permanent drain The cooled air then passes through the hot condenser coil where it is reheated using the same energy removed during the cooling phase plus the additional heat generated by the compressor The...

Page 4: ...PTH EPTH EPTH 26 660mm W W W WEIGHT EIGHT EIGHT EIGHT 176 lbs 80Kg A A A AIRFLOW IRFLOW IRFLOW IRFLOW Low 261 CFM 445 M3 hr High 491 CFM 835 M3 hr P P P POWER OWER OWER OWER 1000 W P P P POWER OWER OWER OWER S S S SUPPLY UPPLY UPPLY UPPLY 110V 115V 60Hz 1ph F F F FINISH INISH INISH INISH Powder coated Epoxy R R R REFRIGERANT EFRIGERANT EFRIGERANT EFRIGERANT T T T TYPE YPE YPE YPE Q Q Q QTY TY TY T...

Page 5: ...he unit inlet and outlet must have a clearance of 0 5M from all adjacent surfaces and or structures Before connecting this unit to the relevant power supply the following must be carried out Selecting the correct fan speed The PD120 has a low fan speed and a high fan speed and the required speed must be chosen before installation To select the correct fan speed firstly remove the air outlet cover ...

Page 6: ... running for 15 minutes E Observe the evaporator coils behind the filter on the air inlet end of the unit to confirm frost formation i If the air temperature is below 70ºF an even coating of frost should cover the entire evaporator coil except for the last one or two coils ii If the air temperature is about 70ºF frost and or droplets of condensed water should cover the entire evaporator coil F As ...

Page 7: ...g the fins Alternatively vacuum clean the coils WARNING DO NOT STEAM CLEAN REFRIGERATION COILS 2 Check that the fan is firmly secured to the motor shaft and that the fan rotates freely The fan motor is sealed for life and therefore does not need oiling 3 To check the refrigerant charge run the unit for 15 minutes and briefly remove the cover The evaporator coil should be evenly frost coated across...

Page 8: ...de of the refrigerant compressor The charging stub should be crimped and rebrazed after servicing NEVER allow permanent service valves to be fitted to any part of the circuit Service valves may leak causing further loss of refrigerant gas 3 The refrigerant compressor fitted to the dehumidifier is a durable unit that should give many years of service Compressor failure can result from the machine l...

Page 9: ... extraction 1 Insufficient air flow 2 Compressor fault 3 Loss of refrigerant gas 1 Check all of the above 2 Contact the Factory Service Center 3 Contact the Factory Service Center Unit vibrates excessively 1 Loose compressor mounts 2 Damaged fan 1 Tighten the nuts on the compressor mounts 2 Replace fan Water flooding inside the machine 1 Drain pipe blocked frozen 2 Drain pipe too high 1 Clear the ...

Page 10: ...RS HOURS HOURS 80F 80F 80F 80F 60 60 60 60 RH RH RH RH 107 R R R REFRIGERANT EFRIGERANT EFRIGERANT EFRIGERANT 1600 Grams V V V VOLTAGE OLTAGE OLTAGE OLTAGE 115 Volts P P P POWER OWER OWER OWER 1 1 KW P P P PHASE HASE HASE HASE Single H H H HZ Z Z Z 60 Hz C C C CURRENT URRENT URRENT URRENT 10 A C C C CONTROL ONTROL ONTROL ONTROL V V V VOLTAGE OLTAGE OLTAGE OLTAGE 5 V DC T T T TIME IME IME IME D D D...

Page 11: ... hazard This product contains fluorinated greenhouse gases covered by the Kyoto Protocol The refrigeration system is hermetically sealed The Global Warming Potential GWP of refrigerants used in products manufactured by Ebac Industrial Products Ltd is as follows R134a 1300 R407c 1610 For type and weight of refrigerant contained in this unit please refer to the product data label Due to the high pre...