Continuation:
Designation
Values
Description
Parameter for
value for light scene
type of value
Scene number
Scene 1
..
..
Scene 64
Sends the selected scene number
(call scene)
Save when long time
operation
No
Yes
Should a saved scene telegram be
sent with a long keystroke?
Long keystroke
starting at
1 sec.
2 sec.
3 sec.
5 sec.
This function serves to clearly
differentiate between long and short
keystrokes.
If the keystroke at least as long as the
set time, then a long keystroke will
be registered.
Parameter for
valuator for blinds
type of value
2.8 m
0 .. 100 % in 5 % increments
Sends a positioning telegram to the
blinds / shutter actuator
Slats
0 .. 100 % in 5 % increments
What slat position should be sent to
the actuator together with the
positioning telegram?
Special function after
long time operation
What function should be carried out
with a long keystroke?
No
None
All the way UP (0%)
Slats to 0% and move blinds up to
upper stopping point
All the way DOWN (100%)
Slats to 100% and move blinds down
to lower stopping point
Common parameters
Reaction when setting
the lock
Ignore lock
Disable telegrams are ignored
Lock
After a lock telegram (status =1) is
received, the channel no longer
transmits.
Reaction when
cancelling the lock
No reaction when cancelling
the lock
No reaction when cancelling the lock
Update
When the lock is cancelled
(status=0), the current channel status
should be sent again.