5.1.4 Objects and links
Table 22: RAM 712
Cheops drive
No.
RAM 712
No.
Cheops drive
Comments
Object name
Object name
7
Heating control
variable
0
Control variable
Actuator receives heating
actuating value and moves the
valve position
Table 23: RAM 712
RAM 712
No.
RAM 712
Comments
Object name
No.
Object name
11
Input 1 switching
5
Window position
Object 11 sends the window
status to object 5 (input for
window contact)
via the bus.
Both objects are connected to
each other via a common group
address.
Table 24: TR 644
RAM 712
No.
TR 644 S EIB
No.
RAM 712
Comments
Object name
Object name
0
Channel 1 Valuator
3
Operating mode preset
Channel 1 of timer:
ON= 2 (standby)
OFF= 3 (night)
Table 25: Compact office EIB
RAM 712
No.
Compact office EIB
No.
RAM 712
Comments
Object name
Object name
9
Presence output
4
Presence
Switches RAM 712 to comfort
mode when presence is
detected.