2/6
COPYRIGHT NOTICE
No part of this document may be reproduced, republished, translated or digitalized in any form or by
any means, without prior written permission of TESLA.
Information contained in this manual relates exclusively to the TERA system component specified on the
title page. New versions and modifications may be developed without prior notice to current users. TESLA
has made every attempt to provide you with complete, error-free and accurate information in this manual.
TESLA is not liable for errors or omissions contained in this document, or for any damages however resulted
from using or relying on any information contained herein. TESLA's liability for errors shall be strictly limited
to correcting such errors and providing advisory services as described below.
Users should be familiar with operation basis of used product. If you experience any problems with your
product, please contact us at:
TESLA
Podebradska 56/186
180 66 Prague 9
www.tesla.cz
1
Introduction
This document describes technical specifications and user operation of the TAR2 Wireless Actuator.
Product was developed and manufactured in the Czech Republic. All rights reserved TESLA. Offer or
delivery of products or services related to the product does not include transfer of ownership rights.
Before using the product, please read this manual carefully and understand all operating and safety
precautions. Compliance with operational and safety precaution can prevent from damage to equipment or
injuries to personnel. Operating and safety instructions in the document are marked as follows:
Attention!
This formatted text indicates the operating and safety instructions.
The product may only be used in the specified manner and for its intended purpose. The product may be
provided to third persons along with this documentation only.
2
Description and Utilization
TAR2 actuator is wireless switching unit of a system (wireless relay) which allows direct switching low
power input load or switching control signals of high power relay which can then switch even very high
power inputs. The actuator is equipped with memory relay which minimizes consumption because the relay
only consumes current during switching pulse at the duration of 10 msec. This allows supplying the unit
from a replaceable lithium battery with an estimated life longer than 2 years of operation.
Attention! For setting and controling of the Actuator it is essential to have wireless Central Unit in
system, see
http://www.tesla.cz/en/tera-centrala/
. The Central Unit is not included with package of
TAR2 and it is sold and delivered extra.
Setting and configuration of TAR2 Wireless Actuator and whole system is also managed by connected
computer to Cenral Unit and TERAview application on PC.
TERAview application, drivers and user manual with detail configuration description is free downloaded on
website:
http://www.tesla.cz/en/ke-stazeni/
.
TAR2 Wireless Actuator can be used in this system:
TERA System for Regulating Radon Concentrations (Figure 1)
Regulating system diagram description - Radon measuring probes located in a building transmit their
current radon concentration values to central unit wirelessly. The central unit analyzes this information and
on the basis of measured (set) concentration level value it sends wireless command to actuator which is
hardwired with power relay. Power relay switches on a fan which decreases radon concentration within an
area. After decreasing of radon concentration, the actuator receives a command to switch off the fan. This
cycle repeats depending on an increasing or decreasing volume activity of radon a building.